Siemens

3VL8716-1SG30-0AA0

3VL8716-1SG30-0AA0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3VL8716-1SG30-0AA0 Siemens

3VL8716-1SG30-0AA0 Siemens - circuit breaker VL1600N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection trip unit ETU22, LSIG 3 phases/3 lines In=1600A, rated current IR=640...1600A, overload protection, ISD=1.5 to 8xIR, II=9XIN short-circuit protection without auxiliary release without auxiliary/alarm switch

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 3VL8716-1SG30-0AA0
Product Description circuit breaker VL1600N standard breaking capacity Icu=55kA, 415V AC 3-pole, line protection trip unit ETU22, LSIG 3 phases/3 lines In=1600A, rated current IR=640...1600A, overload protection, ISD=1.5 to 8xIR, II=9XIN short-circuit protection without auxiliary release without auxiliary/alarm switch, spare part product only for replacement purposes
Product family Not available
Product Lifecycle (PLM) PM410:Product cancellation
PLM Effective Date Product is cancelled since: 01.10.2021
Notes Sucessor:www.siemens.com/conversion-tool This product is a Spare Part, please visit the Spares & Service section for more information If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : EAR99 / AL : N
Estimated dispatch time (Working Days) 20 Day/Days
Net Weight (kg) 33,480 Kg
Packaging Dimension 290,00 x 630,00 x 245,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4011209826427
UPC Not available
Commodity Code 85362090
LKZ_FDB/ CatalogID LV10.1
Product Group 3740
Group Code P360
Country of origin Mexico
Compliance with the substance restrictions according to RoHS directive Since: 01.07.2006
Product class C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back Obligation No
REACH Art. 33 Duty to inform according to the current list of candidates Reach Information There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern. We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
SCIP number

Model

Type Of The Driving Mechanism Motor Drive No
Design Of The Overcurrent Release Etu22

General Technical Data

Number Of Poles 3
Size Of The Circuit-Breaker 3Vl8
Mechanical Service Life (Operating Cycles) Typical 3 000
Electrical Endurance (Operating Cycles) Typical 1 500
Utilization Category A
Performance Class For Circuit Breaker N
Reference Code According To Din 40719 Extended According
To Iec 204-2 According To Iec 750Q
Operating Frequency Maximum 30 1/S

Voltage

Rated Operational Voltage Ue Max. 690 V
Insulation Voltage Rated Value 800 V
Insulation Voltage (Ui) At Ac Rated Value 800 V
Surge Voltage Resistance Rated Value 8 Kv
Operating Voltage
Rated Value Maximum 690 V
For Main Current Circuit At Ac At 50 Hz Maximum 690 V
For Main Current Circuit At Ac At 60 Hz Maximum 690 V

Protection Class

Protection Class Ip Ip20
Protection Function Of The Overcurrent Release Lsig

Main Circuit

Operating Frequency
1 Rated Value 50 Hz
2 Rated Value 60 Hz

Auxiliary Circuit

Number Of Co Contacts For Auxiliary Contacts 0
Number Of Nc Contacts For Auxiliary Contacts 0
Number Of No Contacts For Auxiliary Contacts 0
Suitability
Suitability For Use System/Generator Protection

Adjustable Parameters

Adjustable Current Response Value Current Of The Short-Time
Delayed Short-Circuit Release Full-Scale Value12 800 A
Adjustable Current Response Value Current Of The Current-
Dependent Overload Release Initial Value640 A

Product Component

Trip Indicator No
Auxiliary Switch No
Voltage Trigger No
Undervoltage Release No
Undervoltage Release With Leading Contact No
Product Extension Optional Motor Drive Yes

Product Function

Product Function
Of Thermal Overload Trip Unit Adjustable
Grounding Protection Yes
For Neutral Conductors Short-Circuit And Overload Proof No
Overload Protection Yes
Short Circuit
Operating Short-Circuit Current Breaking Capacity (Ics)
At 240 V Rated Value 35 Ka
At 415 V Rated Value 28 Ka
At 500 V Rated Value 20 Ka
At 690 V Rated Value 10 Ka
Maximum Short-Circuit Current Breaking Capacity (Icu)
At 240 V Rated Value 65 Ka
At 415 V Rated Value 55 Ka
At 440 V Rated Value 35 Ka
At 480 V According To Nema Rated Value 25 Ka
At 500 V Rated Value 25 Ka
At 600 V According To Nema Rated Value 20 Ka
At 690 V Rated Value 20 Ka

Connections

Arrangement Of Electrical Connectors For Main Current Circuit Front Side
Type Of Connectable Conductor Cross-Sections For Auxiliary
Contacts
Solid 0.75 ... 1.5 Mm²
Finely Stranded With Core End Processing 0,75 ... 1.0 Mm²
Type Of Electrical Connection For Main Current Circuit Without Connection Accessoires

Mechanical Design

Height 406.5 Mm
Width 228.5 Mm
Depth 333.5 Mm
Fastening Method Fixed Mounting

Ambient Temperature During Operation

Minimum -25 °C
Maximum 70 °C

Ambient Temperature During Storage

Minimum -40 °C
Maximum 80 °C