Description for 1SCA022709R9330 ABB

1SCA022709R9330 ABB - OS200B03P SWITCH FUSE

Extended Description for 1SCA022709R9330 ABB

1SCA022709R9330 ABB - Switch Fuses,Front Operated,3-pole,03 (Left Side),British Standard,B1-B2,Handle and shaft included,

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£292.46 Exc. VAT
£350.95 Inc. VAT

Dimensions

Product Net Weight 2.8 kg6.3 lb
Product Net Depth / Length 130 mm
Product Net Height 199 mm
Product Net Width 177 mm

Technical

Number of Poles 3
Fuse System British Standard
Rated Insulation Voltage (Ui) 1000 V
Standards IEC 60947-3
Rated Conditional Short-Circuit Current (Inc) (690 V) 80 kA
Rated Current (In) Main Circuit 200 A
Terminal Width 20 mm
Rated Operational Current AC-21A (Ie) (500 V) 200 A(690 V) 200 A
Pollution Degree 3
Switches Operating Mechanism 03 (Left Side)
Position of Line Terminals Top In - Bottom Out, Bottom In - Top Out
Handle Type Pistol handle and shaft included
Rated Operational Current AC-22A (Ie) (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A
Rated Operational Current AC-23A (Ie) (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A
Tightening Torque 15 ... 22 N·m
Conventional Free-air Thermal Current (Ith) Θ = 40 °C 200 A
Terminal Type Lug terminals
Conventional Thermal Current (Ithe) Fully Enclosed 200 A
Rated Impulse Withstand Voltage (Uimp) 12 kV
Mounting Type Base mounting
Rated Operational Power AC-23A (Pe) (220 ... 240 V) 60 kW(400 V) 110 kW(415 V) 110 kW(500 V) 132 kW(690 V) 200 kW
Operating Mode Front Operated
Power Loss at Rated Operating Conditions per Pole 17 W
Rated Operational Voltage Main Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw) for 1 s 8 kiloampere rms
Fuse Size B1-B2

Ordering

Minimum Order Quantity 1 piece
Customs Tariff Number 85365080
Country of Origin Finland (FI)

Circular Value

Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
RoHS Information 1SCC011020D0201
REACH Declaration 1SCC011021D0201

Classifications

eClass V11.1 : 27371401
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
ETIM 9 EC001040 - Fuse switch disconnector
Object Classification Code Q

Technical UL/CSA

Tightening Torque 15 ... 22 N·m

Environmental

RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019