This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

ABB

1SCA115325R1001

1SCA115325R1001 ABB

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 1SCA115325R1001 ABB

1SCA115325R1001 ABB - OS63GB12P SWITCH FUSE

Extended Description for 1SCA115325R1001 ABB

1SCA115325R1001 ABB - Switch Fuses,Front Operated,3-pole,12 (Between the Poles),British Standard,A2-A3,Handle and shaft included,

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£169.00 Exc. VAT
£202.80 Inc. VAT

Classifications

WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
ETIM 9 EC001040 - Fuse switch disconnector
eClass V11.1 : 27371401
Object Classification Code Q

Technical

Rated Insulation Voltage (Ui) 1000 V
Terminal Type Screw Terminals
Conventional Thermal Current (Ithe) Fully Enclosed 63 A
Tightening Torque 3 N·m4 N·m
Rated Operational Current AC-23A (Ie) (500 V) 63 A(690 V) 63 A
Rated Operational Voltage Main Circuit 690 V AC
Position of Line Terminals Top In - Bottom Out, Bottom In - Top Out
Fuse Size A2-A3
Cable Cross-Section 2.5 ... 25 mm²
Number of Poles 3
Rated Conditional Short-Circuit Current (Inc) (690 V) 80 kA
Handle Type Pistol handle and shaft included
Pollution Degree 3
Switches Operating Mechanism 12 (Between the Poles)
Power Loss at Rated Operating Conditions per Pole 7.5 W
Rated Operational Current AC-22A (Ie) (500 V) 63 A(690 V) 63 A
Rated Operational Power AC-23A (Pe) (220 ... 240 V) 18.5 kW(400 V) 30 kW(415 V) 30 kW(500 V) 37 kW(690 V) 55 kW
Rated Short-time Withstand Current Low Voltage (Icw) for 1 s 2.5 kiloampere rms
Standards IEC 60947-3
Mounting Type Base mounting
Fuse System British Standard
Rated Operational Current AC-21A (Ie) (500 V) 63 A(690 V) 63 A
Conventional Free-air Thermal Current (Ith) Θ = 40 °C 63 A
Operating Mode Front Operated
Rated Impulse Withstand Voltage (Uimp) 12 kV
Rated Current (In) Main Circuit 63 A

Dimensions

Product Net Width 112 mm
Product Net Height 125 mm
Product Net Depth / Length 109 mm
Product Net Weight 1.18 kg2.6 lb

Environmental

RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Ordering

Country of Origin Finland (FI)
Customs Tariff Number 85365080
Minimum Order Quantity 1 piece

Technical UL/CSA

Tightening Torque 3 N·m4 N·m

Circular Value

REACH Declaration 1SCC011021D0201
RoHS Information 1SCC011020D0201
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible