Description for 2CSB202001R0250 ABB

2CSB202001R0250 ABB - DDA202 AC-25/0.01 Residual Current Device Block

Extended Description for 2CSB202001R0250 ABB

2CSB202001R0250 ABB - The RCD block DDA200 series is suitable for assembly with MCBs S200 series and S300P. It assures protection against the effects of sinusoidal alternating earth fault currents, protection, against indirects contacts and additional protection against direct (with sensitivity = 30 mA) contacts. Applications: residential, commercial, industrial.

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£119.31 Exc. VAT
£143.17 Inc. VAT

Environmental

Degree of Protection IP2X
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH Declaration 9AKK108467A9482
RoHS Information 9AKK106713A5614
Resistance to Vibrations acc. to IEC 60068-2-6 0.1 mm or 1 g - 20 cycles at 5…150…5 Hz
Environmental Information Refer to RoHS
Ambient Air Temperature Operation -25...55 °C
Conflict Minerals Reporting Template (CMRT) 9AKK108468A3363
Resistance to Shock acc. to IEC 60068-2-27 25g 2 shocks 13 ms
Ambient Temperature -25...55 °C

Classifications

eClass V11.0 : 27142210
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B Business To Consumer
ETIM 9 EC002297 - Residual current circuit breaker (RCCB) module
Object Classification Code F
CN8 85363030

Ordering

Package Level 1 Units box 1 piece
Minimum Order Quantity 1 piece
Package Level 1 Gross Weight 0.245 kg

Technical

Power Loss 2 W
Type of Residual Current AC type
Rated Frequency (f) 50 … 60 Hz
Electrical Endurance 10000 cycle
Rated Residual Current 10 mA
Rated Insulation Voltage (Ui) 500 V
Rated Current (In) 25 A
Number of Poles 2
Power Supply Connection Arbitrary
Connecting Capacity Rigid 25 ... 25 mm²Flexible 25 ... 25 mm²
Leakage Current Type AC
Standards IEC/EN 61009 Ann. G
Rated Voltage (Ur) 230/400 V
Rated Impulse Withstand Voltage (Uimp) 4 kV
Operating Characteristic Instantaneous
Rated Operational Voltage 230 V

Technical UL/CSA

Short-Circuit Current Rating (SCCR) 0.01 ... 0.01 A

Installation

Instructions and Manuals 9AKK108467A7091

Dimensions

Product Net Width 70 mm
Product Net Height 93 mm
Product Net Weight 0.210 kg