This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Allen Bradley

513-EFB-1-4R-6XP-9A-50-901

Allen Bradley

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 513-EFB-1-4R-6XP-9A-50-901 Allen Bradley

513-EFB-1-4R-6XP-9A-50-901 Allen Bradley - NEMA Size 4 COMB Starter Circuit Breaker

Extended Description for 513-EFB-1-4R-6XP-9A-50-901 Allen Bradley

513-EFB-1-4R-6XP-9A-50-901 Allen Bradley - NEMA Combination Starter, Circuit Breaker Type, NEMA 4, 480 Volts (B), Type 3R/4/12 - Enclosure Code "F"

Free Delivery to UK Mainland on orders over £25

Product Detail

Current Product Selection Availability (may change based on options selected below) Catalog is configured at order entry
Please Note Preferred availability options are available in blue below Standard Options are available in black below Engineered-To-Order (ETO) options are available in purple below (Lead-Time Based on Options)
Factory or User Assembled? Factory Assembled
Line Voltage 460V 60Hz
Horsepower 100 HP
NEMA Size NEMA 4
Enclosure Type 3R/4/12 - Enclosure Code "F"
Control Voltage 120V 60Hz
Horsepower Code 100 HP (Motor Protection)
Circuit Breaker Type Instantaneous Trip, Standard
Overload Relay Eutectic Alloy
Full Load Amps Eutectic Overload
Factory Installed Modifications START-STOP Push ButtonPilot LightsTransformer, w/2 Prim & 1 Sec FuseAuxiliary Contact (On Starter OR Disconnect OR Breaker)N.C. Auxiliary Contact (On Eutectic Overload Relay)
Enclosure Size [length x width x depth] 30 x 20 x 10 in.
Continuous VA (Transformer Rating) 350
Load Voltage 115…575 (V)
Continuous Current Rating 135 (A)
Service Limit Current Rating 156 (A)
Maximum Hp Rating (Non-plugging and non-jogging duty) Single-Phase - (Hp)
Maximum Hp Rating (Non-plugging and non-jogging duty) Three-Phase 75 (Hp)
Maximum Circuit Closing Inrush Current, Peak Including Offset 1581 (A)
Mechanical Life 5 (Millions of Operations)
Maximum Number of Auxiliary Contacts 8
Pick-up Operating Time (Average) 2 (ms)
Drop-out Operating Time (Average) 20 (ms)
Wire size for Power Terminals 6…4/0 (AWG)
Required Torque 275 (lb•in)
Type of Power Terminal Pressure Terminals
Operating Position Vertical
Temperature Range -13…+149°F(-25…+65°C)
Altitude 10,000 (feet before derating)
Corrosion-Resistance All metal parts are treated for corrosion-resistance

Replacement Parts

Catalog Number 500F-EOD930
Description 500F, 500FC NEMA AC/DC Contactor,Motor Loads,Feed-Through ,SIZE 4, Open, 115-120V 60Hz, 3 Power Poles, Yes , 135 , 110/120V 50/60 Hz ,
Quantity 1
Additional Information NEMA Contactor and Starter Specification
Catalog Number 592-EUTE
Description NEMA Eutectic Alloy Overload Relay, Manual Reset, 165A, N.C. Contact
Quantity 1
Catalog Number 599-PLF-120R
Description Pilot Light, Red, LED, 30mm, Type 4/12, 120V
Quantity 1
Additional Information 30 mm Push Button Specifications Technical Data (rockwellautomation.com)

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible