This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Schneider Electric

LC1D65AF7TQ

LC1D65AF7TQ Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for LC1D65AF7TQ Schneider Electric

LC1D65AF7TQ Schneider Electric - contactor TeSys LC1-D - 3 poles- AC-3 - 440 V 65 A - coil 110 V AC

Extended Description for LC1D65AF7TQ Schneider Electric

LC1D65AF7TQ Schneider Electric - TeSys D contactor, 3 poles (3NO), for motor control applications up to 65A/690V AC-3/3e (7.5kW@400V).,It provides a low consumption 110V AC 50/60 Hz coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals.,For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability.,Compact (45mm width), DIN-rail mounting or screw fixing.,Pack of 10 units.,Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£161.12 Exc. VAT
£193.34 Inc. VAT

Main

Range TeSys
range of product TeSys Deca
product or component type Contactor
Device short name LC1D
Contactor application Motor control,Resistive load
Utilisation category AC-1,AC-3,AC-3e,AC-4,AC-1
Poles description 3P
[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current 65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit,50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit,80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 24 V AC 50 Hz

Complementary

Motor power kW 37 kW at 500 V AC 50 Hz (AC-3),37 kW at 660...690 V AC 50 Hz (AC-3),37 kW at 415...440 V AC 50 Hz (AC-3),18.5 kW at 220...230 V AC 50 Hz (AC-3),30 kW at 380...400 V AC 50 Hz (AC-3e),37 kW at 500 V AC 50 Hz (AC-3e),37 kW at 660...690 V AC 50 Hz (AC-3e),37 kW at 415...440 V AC 50 Hz (AC-3e),18.5 kW at 220...230 V AC 50 Hz (AC-3e),22 kW at 380...400 V AC 50 Hz,25 kW at 415 V AC 50 Hz
Motor power hp 20 hp at 200/208 V AC 60 Hz for 3 phases motors,20 hp at 230/240 V AC 60 Hz for 3 phases motors,40 hp at 460/480 V AC 60 Hz for 3 phases motors,50 hp at 575/600 V AC 60 Hz for 3 phases motors,3 hp at 115 V AC 60 Hz for 1 phase motors,7.5 hp at 230/240 V AC 60 Hz for 1 phase motors
compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 60 °C) for control circuit,80 A (at 60 °C) for power circuit
Irms rated making capacity 900 A at 440 V for power circuit conforming to IEC 60947,140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity 900 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating 125 A gG at <= 690 V coordination type 2 for power circuit,10 A gG for control circuit conforming to IEC 60947-5-1,100 A gG at <= 690 V coordination type 1 for power circuit
Power dissipation per pole 6.3 W AC-3e,3.7 W AC-3,9.6 W AC-1
[Ui] rated insulation voltage Power circuit: 600 V CSA certified,Power circuit: 600 V UL certified,Control circuit: 690 V conforming to IEC 60947-1,Power circuit: 690 V conforming to IEC 60947-1,Control circuit: 600 V CSA certified,Control circuit: 600 V UL certified
Overvoltage category III
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 6000000 cycles
Control circuit type AC at 50 Hz
Coil technology Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz,1...1.1 Uc (60…70 °C):operational AC 50/60 Hz,0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz,0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
Inrush power in VA 140 VA cos phi 0.75 (at 20 °C),160 VA cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 20 °C),15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4…5 W at 50/60 Hz for control circuit
Operating time 4...19 ms opening,12...26 ms closing
Maximum operating rate 3600 cyc/h 60 °C
Connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end,Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: rigid,Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: rigid,Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable end,Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable end,Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable end,Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable end,Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: rigid,Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid
Tightening torque Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² - with screwdriver hex (Allen key)4 mm,Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 35 mm² - with screwdriver hex (Allen key)4 mm,Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm,Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver Philips No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1, type mirror contact 1 NC conforming to IEC 60947-4-1
Terminals description ISO n°1 (13-14)NO,(21-22)NC
Minimum switching voltage 17 V for control circuit
Minimum switching current 5 mA for control circuit
Insulation resistance > 10 MOhm for control circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contacts,1.5 ms on energisation between NC and NO contacts
mounting support Plate,Rail

Environment

Standards IEC 60947-4-1,EN 60947-5-1,CSA C22.2 No 14,IEC 60947-5-1,EN 60947-4-1,UL 508
Product certifications GL,GOST,CCC,UL,LROS (pending),BV,CSA,UKCA,GOST,DNV
IP degree of protection IP2X conforming to IEC 60529,IP2X conforming to VDE 0106
Climatic withstand conforming to IACS E10 exposure to damp heat
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor opened (2 Gn, 5...300 Hz) ,Vibrations contactor closed (4 Gn, 5...300 Hz) ,Shocks contactor opened (10 Gn for 11 ms) ,Shocks contactor closed (15 Gn for 11 ms)
Height 127 mm
Width 75 mm
Depth 119 mm
net weight 1.4 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 6.2 cm
Package 1 Width 13.7 cm
Package 1 Length 15.2 cm
Package 1 Weight 1.046 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Instruction sheet

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible