This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Schneider Electric

LC1F1154P7

LC1F1154P7 Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for LC1F1154P7 Schneider Electric

LC1F1154P7 Schneider Electric - TeSys F contactor - 4P (4 NO) - AC-1 - <= 440 V 200 A - coil 230 V AC

Extended Description for LC1F1154P7 Schneider Electric

LC1F1154P7 Schneider Electric - TeSys F contactor, 4 poles (4NO), 200A/690V AC-1, for non-inductive load applications.,It provides a low sealed consumption 230V 40-400Hz AC coil, bolt terminals for bars or cables with lugs.,For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability.,It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately).,Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£838.77 Exc. VAT
£1,006.53 Inc. VAT

Main

Range TeSys
range of product TeSys F
product or component type Contactor
Device short name LC1F
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage <= 690 V AC 50/60 Hz,<= 460 V DC
[Uc] control circuit voltage 230 V AC 40...400 Hz
[Ie] rated operational current 200 A (at <40 °C) at <= 440 V AC-1

Complementary

[Uimp] rated impulse withstand voltage 8 kV
[Ith] conventional free air thermal current 200 A (at 40 °C)
Rated breaking capacity 920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 1100 A 40 °C - 10 s,640 A 40 °C - 30 s,520 A 40 °C - 1 min,400 A 40 °C - 3 min,320 A 40 °C - 10 min
Associated fuse rating 125 A aM at <= 440 V,200 A gG at <= 440 V
Average impedance 0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1,1500 V conforming to VDE 0110 group C
Power dissipation per pole 15 W AC-1
Overvoltage category III
power pole contact composition 4 NO
Control circuit voltage limits Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C),Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)
Mechanical durability 10 Mcycles
Inrush power in VA 770 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA 8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Maximum operating rate 2400 cyc/h 55 °C
Operating time 35 ms closing (at Uc) ,130 ms opening (at Uc)
Connections - terminals Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm,Power circuit: lugs-ring terminals 1 cable(s) 95 mm²,Power circuit: connector 1 cable(s) 95 mm²,Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end,Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end,Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end,Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end,Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end,Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end,Power circuit: bolted connection
Tightening torque Power circuit: 10 N.m,Control circuit: 1.2 N.m
mounting support Plate
Heat dissipation 5.9…7.2 W
Standards IEC 60947-4-1,EN 60947-4-1,EN 60947-1,IEC 60947-1,JIS C8201-4-1
Product certifications CCC,LROS (Lloyds register of shipping),DNV,RMRoS,ABS,RINA,BV,UL,CB,UKCA
compatibility code LC1F
Control circuit type AC at 40...400 Hz

Environment

IP degree of protection IP2X front face with shrouds conforming to IEC 60529,IP2X front face with shrouds conforming to VDE 0106
Protective treatment TH
Ambient air temperature for operation -40…60 °C
Ambient air temperature for storage -60…80 °C
Permissible ambient air temperature around the device 60…70 °C at Uc
Height 162 mm
Width 200.5 mm
Depth 171 mm
Operating altitude 3000 m without derating
net weight 3.83 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 22.0 cm
Package 1 Width 21.5 cm
Package 1 Length 26.5 cm
Package 1 Weight 4.82 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible