This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Schneider Electric

LC1F185BD

LC1F185BD Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for LC1F185BD Schneider Electric

LC1F185BD Schneider Electric - TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 185 A - coil 24 V DC

Extended Description for LC1F185BD Schneider Electric

LC1F185BD Schneider Electric - TeSys F contactor, 3 poles (3NO), 185A/690V AC-3, for motor applications up to 90kW@400V.,It provides a low sealed consumption 24V DC coil, bolt terminals for bars or cables with lugs.,For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability.,It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately).,Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£613.22 Exc. VAT
£735.86 Inc. VAT

Main

Range TeSys
range of product TeSys F
product or component type Contactor
Device short name LC1F
Contactor application Motor control,Resistive load
Utilisation category AC-4,AC-1,AC-3
Poles description 3P
[Ue] rated operational voltage <= 460 V DC,<= 690 V AC 50/60 Hz
[Uc] control circuit voltage 24 V DC
[Ie] rated operational current 275 A (at <40 °C) at <= 440 V AC-1,185 A (at <55 °C) at <= 440 V AC-3

Complementary

[Uimp] rated impulse withstand voltage 8 kV
[Ith] conventional free air thermal current 275 A (at 40 °C)
Rated breaking capacity 1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 1500 A 40 °C - 10 s,920 A 40 °C - 30 s,740 A 40 °C - 1 min,500 A 40 °C - 3 min,400 A 40 °C - 10 min
Associated fuse rating 200 A aM at <= 440 V,315 A gG at <= 440 V
Average impedance 0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1,1500 V conforming to VDE 0110 group C
Power dissipation per pole 12 W AC-3,25 W AC-1
Overvoltage category III
power pole contact composition 3 NO
Motor power kW 90 kW at 380...400 V AC 50/60 Hz (AC-3),100 kW at 415 V AC 50/60 Hz (AC-3),100 kW at 440 V AC 50/60 Hz (AC-3),110 kW at 500 V AC 50/60 Hz (AC-3),110 kW at 660...690 V AC 50/60 Hz (AC-3),55 kW at 220...230 V AC 50/60 Hz (AC-3),33 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits Operational: 0.85...1.1 Uc (at 55 °C),Drop-out: 0.15...0.2 Uc (at 55 °C)
Mechanical durability 10 Mcycles
Inrush power in W 800 W (at 20 °C)
Hold-in power consumption in W 5 W at 20 °C
Maximum operating rate 2400 cyc/h 55 °C
Operating time 30...40 ms closing,30...50 ms opening
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end,Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end,Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end,Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end,Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end,Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end,Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm,Power circuit: lugs-ring terminals 1 cable(s) 150 mm²,Power circuit: connector 1 cable(s) 150 mm²,Power circuit: bolted connection
Tightening torque Control circuit: 1.2 N.m,Power circuit: 18 N.m
mounting support Plate
Heat dissipation 5 W
motor power range 30…50 kW at 200…240 V 3 phases,55…100 kW at 200…240 V 3 phases,55…100 kW at 380…440 V 3 phases,55…100 kW at 480…500 V 3 phases,110…220 kW at 480…500 V 3 phases
Motor starter type Direct on-line contactor
Contactor coil voltage 24 V DC standard
Standards EN 60947-1,IEC 60947-4-1,IEC 60947-1,JIS C8201-4-1,EN 60947-4-1
Product certifications RMRoS,LROS (Lloyds register of shipping),ABS,CB,DNV,BV,RINA,UL,CSA,UKCA
compatibility code LC1F
Control circuit type DC standard

Environment

IP degree of protection IP2X front face with shrouds conforming to IEC 60529,IP2X front face with shrouds conforming to VDE 0106
Protective treatment TH
Ambient air temperature for operation -5…55 °C
Ambient air temperature for storage -60…80 °C
Permissible ambient air temperature around the device -40…70 °C
Height 174 mm
Width 168.5 mm
Depth 181 mm
Operating altitude 3000 m without derating
net weight 4.65 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 21.000 cm
Package 1 Width 22.000 cm
Package 1 Length 23.500 cm
Package 1 Weight 4.933 kg
Unit Type of Package 2 P06
Number of Units in Package 2 8
Package 2 Height 75.000 cm
Package 2 Width 80.000 cm
Package 2 Length 60.000 cm
Package 2 Weight 50.824 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible