LC1G800KUEN Schneider Electric - High power contactor, TeSys Giga, 3 pole (3NO), AC-3 <=440V 800A, standard version, 100â¦250V wide band AC/DC coil

Extended Description for LC1G800KUEN Schneider Electric

LC1G800KUEN Schneider Electric - TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 800A 450kW@440V.,It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA).,Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C.,It procures high reliability and durability with 5 Mcycles mechanical durability.,Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators.,It is possibility to replace switching module (main contacts), enhancement contactor life.,Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor.,To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement.,It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106.,It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude.,The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings.,Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach).,Unique QR code provides quick access to complete product data.

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£2,066.73 Exc. VAT
£2,480.08 Inc. VAT

Main

Range TeSys
range of product TeSys Giga
product or component type Contactor
Device short name LC1G
Contactor application Power switching,Motor control
Utilisation category AC-1,AC-3,AC-3e,AC-4,AC-5a,AC-5b,AC-6a,AC-6b,AC-8a,AC-8b,DC-1,DC-3,DC-5
Poles description 3P
[Ue] rated operational voltage <= 1000 V AC 50/60 Hz,<= 460 V DC
[Ie] rated operational current 1050 A (at <40 °C) at <= 1000 V AC-1,800 A (at <60 °C) at <= 440 V AC-3
[Uc] control circuit voltage 100...250 V AC 50/60 Hz,100...250 V DC
Control circuit voltage limits Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C),Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)

Complementary

[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal current 1050 A (at 40 °C)
Rated breaking capacity 5870 A at 440 V
[Icw] rated short-time withstand current 5.5 kA - 10 s,4.6 kA - 30 s,3.6 kA - 1 min,2.6 kA - 3 min,1.7 kA - 10 min
Associated fuse rating 800 A aM at <= 440 V for motor,630 A aM at <= 690 V for motor,1250 A gG at <= 690 V
Average impedance 0.000065 Ohm
[Ui] rated insulation voltage 1000 V
Power dissipation per pole 70 W AC-1 - Ith 1050 A,42 W AC-3 - Ith 800 A
compatibility code LC1G
Pole contact composition 3 NO
Auxiliary contact composition 1 NO + 1 NC
Motor power kW 200 kW at 230 V AC 50/60 Hz (AC-3e),335 kW at 400 V AC 50/60 Hz (AC-3e),355 kW at 415 V AC 50/60 Hz (AC-3e),375 kW at 440 V AC 50/60 Hz (AC-3e),425 kW at 500 V AC 50/60 Hz (AC-3e),560 kW at 690 V AC 50/60 Hz (AC-3e),450 kW at 1000 V AC 50/60 Hz (AC-3e),250 kW at 230 V AC 50/60 Hz (AC-3),450 kW at 400 V AC 50/60 Hz (AC-3),450 kW at 415 V AC 50/60 Hz (AC-3),450 kW at 440 V AC 50/60 Hz (AC-3),500 kW at 500 V AC 50/60 Hz (AC-3),560 kW at 690 V AC 50/60 Hz (AC-3),450 kW at 1000 V AC 50/60 Hz (AC-3),200 kW at 230 V AC 50/60 Hz (AC-4),375 kW at 400 V AC 50/60 Hz (AC-4),355 kW at 415 V AC 50/60 Hz (AC-4),375 kW at 440 V AC 50/60 Hz (AC-4),400 kW at 500 V AC 50/60 Hz (AC-4),475 kW at 690 V AC 50/60 Hz (AC-4),400 kW at 1000 V AC 50/60 Hz (AC-4)
Motor power hp 300 hp at 200/208 V 60 Hz,350 hp at 230/240 V 60 Hz,700 hp at 460/480 V 60 Hz,800 hp at 575/600 V 60 Hz
Irms rated making capacity 7640 A at 440 V
Coil technology Built-in bidirectional peak limiting
Safety reliability level B10d = 100000 cycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 1800000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 5 Mcycles
inrush power in VA (50/60 Hz, AC) 800 VA
inrush power in W (DC) 680 W
hold-in power consumption in VA (50/60 Hz, AC) 15.0 VA
hold-in power consumption in W (DC) 9.5 W
Operating time 40...70 ms closing,15...50 ms opening
Maximum operating rate 600 cyc/h AC-3,600 cyc/h AC-3e,300 cyc/h AC-1,150 cyc/h AC-4
Connections - terminals Power circuit: bar 2 - busbar cross section: 52 x 20 mm,Power circuit: lugs-ring terminals 1 185 mm²,Power circuit: bolted connection,Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end,Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end,Control circuit: push-in 2 0.5…1.0 mm² with cable end,Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end,Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch 70 mm
mounting support Plate
Standards EN/IEC 60947-4-1,EN/IEC 60947-5-1,UL 60947-4-1,CSA C22.2 No 60947-4-1,JIS C8201-4-1,JIS C8201-5-1,IEC 60335-1:Clause 30.2,IEC 60335-2-40:Annex JJ,UL 60335-1,UL 60335-2-40:Annex JJ
Product certifications CB Scheme,CCC,cULus,EAC,CE,UKCA,EU-RO-MR by DNV-GL
Tightening torque 58 N.m
Height 284 mm
Width 211 mm
Depth 266 mm
net weight 14.2 kg

Environment

IP degree of protection IP2X front face with shrouds conforming to IEC 60529,IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation -25…60 °C
Ambient air temperature for storage -60…80 °C
Mechanical robustness Vibrations 5…300 Hz 2 gn contactor open,Vibrations 5…300 Hz 4 gn contactor closed,Shocks 10 gn 11 ms contactor open,Shocks 15 gn 11 ms contactor closed
Colour Dark grey
Protective treatment TH
Permissible ambient air temperature around the device -40…70 °C at Uc

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 30.000 cm
Package 1 Width 34.500 cm
Package 1 Length 60.500 cm
Package 1 Weight 16.416 kg
Unit Type of Package 2 S06
Number of Units in Package 2 2
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 42.832 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

User guide

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible