Description for LC1SKGC301P7 Schneider Electric

LC1SKGC301P7 Schneider Electric - TeSys SK mini contactor - 3P (3 NO) - AC-3 - 690 V 9 A - 230 V AC coil

Extended Description for LC1SKGC301P7 Schneider Electric

LC1SKGC301P7 Schneider Electric - TeSys SKGC mini-contactor, 3 poles (3NO), for non-inductive load applications up to 20A/690V AC-1,,and for 3-phase motor control applications up to 9A/690V AC-3 (4kW@400V).,It provides a 230V 50/60Hz AC control circuit, 1NC auxiliary contact, a transparent protective cover to prevent front face access, connection by screw terminals.,For operating rates until 1200 cycles/hour and ambient temperature -20/+50°C, it procures high reliability and durability.,For use in modular panels, compact (45mm width), clipping on 35mm DIN rail or fixing by 2 screws.,Location available to insert a suppressor module LA4SK (to be ordered separately).,Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£18.58 Exc. VAT
£22.30 Inc. VAT

Main

Range TeSys
Product name TeSys SK
product or component type Mini contactor
Device short name LC1SKGC
Contactor application Resistive load,Motor control
Utilisation category AC-3,AC-1
power pole contact composition 3P
Pole contact composition 3 NO
Auxiliary contact composition 1 NC
[Ie] rated operational current 20 A (at <50 °C) AC AC-1,9 A at <= 400 V AC AC-3
[Ue] rated operational voltage Power circuit: 690 V AC 50/60 Hz,Signalling circuit: 690 V AC <= 400 Hz

Complementary

Control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 230 V AC 50/60 Hz
Motor power kW 4 kW at 380...415 V AC 50/60 Hz,4 kW at 660...690 V AC 50/60 Hz,1.1 kW at 220...230 V AC 50/60 Hz
[Ith] conventional free air thermal current 20 A (at 55 °C) for power circuit,10 A (at 55 °C) for signalling circuit
Irms rated making capacity 85 A AC conforming to NF C 63-110,85 A AC conforming to IEC 60947
Rated breaking capacity 68 A at <= 400 V conforming to NF C 63-110,68 A at <= 400 V conforming to IEC 60947
[Icw] rated short-time withstand current 60 A 55 °C for power circuit
Associated fuse rating 20 A gI at <= 440 V for power circuit,10 A gI for signalling circuit conforming to IEC 60947,10 A gI for signalling circuit conforming to VDE 0660
Average impedance 4 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit: 690 V conforming to BS 5424,Power circuit: 690 V conforming to IEC 60947,Power circuit: 690 V conforming to UL 508,Power circuit: 690 V conforming to VDE 0110 group C,Power circuit: 690 V conforming to CSA C22.2 No 14
mounting support Panel,Rail
Standards EN/IEC 60947-4-1,UL 60947-4-1,CSA C22.2 No 60947-4-1
Product certifications CB Scheme,CE,UKCA,EAC,cULus
Connections - terminals Connector 1 cable(s) 1.5…6 mm²solid,Connector 2 cable(s) 1.5…4 mm²solid,Connector 1 cable(s) 0.5…6 mm²flexible without cable end,Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end,Connector 1 cable(s) 0.35…6 mm²flexible with cable end,Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end
Tightening torque Power circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1
Operating time 6...8 ms coil de-energisation and NO opening,7...14 ms coil energisation and NO closing,8...16 ms coil energisation and NC opening,8...10 ms coil de-energisation and NC closing
Mechanical durability 10 Mcycles
Maximum operating rate 1200 cyc/h
Control circuit voltage limits Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C),Drop-out: 0.2...0.75 Uc at 50/60 Hz (at <55 °C)
Inrush power in VA 23 VA 50/60 Hz (at 20 °C)
Hold-in power consumption in VA 4.9 VA 50/60 Hz (at 20 °C)
Heat dissipation 1.5 W at 50/60 Hz
Signalling circuit frequency <= 400 Hz

Environment

IP degree of protection IP2X conforming to VDE 0106
Protective treatment TC conforming to IEC 60068,TC conforming to DIN 50015
Ambient air temperature for operation -20…50 °C
Ambient air temperature for storage -50…70 °C
Operating altitude 2000 m without derating
Height 58 mm
Width 45 mm
Depth 56 mm
net weight 0.175 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.8 cm
Package 1 Width 6.0 cm
Package 1 Length 6.2 cm
Package 1 Weight 164.0 g
Unit Type of Package 2 S01
Number of Units in Package 2 28
Package 2 Height 15.0 cm
Package 2 Width 15.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 4.796 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible