RSB1A120B7S Schneider Electric - interface plug-in relay - Harmony RSB - 1 C/O - 24 V AC - 12 A - with socket

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£14.81 Exc. VAT
£17.77 Inc. VAT

Main

range of product Harmony Electromechanical Relays
Series name Interface relay
product or component type Plug-in relay
Device short name RSB
Contacts type and composition 1 C/O
Contact operation Standard
[Uc] control circuit voltage 24 V AC
[Ithe] conventional enclosed thermal current 12 A at -40…40 °C
Status LED Without
Control type Without push-button

Complementary

Shape of pin Flat
average coil resistance 400 Ohm network: AC at 20 °C +/- 15 %
[Ue] rated operational voltage 19.2...26.4 V AC 50 Hz,20.4...26.4 V AC 60 Hz
[Ui] rated insulation voltage 400 V conforming to EN/IEC 60947
[Uimp] rated impulse withstand voltage 3.6 kV conforming to IEC 61000-4-5
Contacts material Silver alloy (Ag/Ni)
[Ie] rated operational current 12 A (AC-1/DC-1) NO conforming to IEC,6 A (AC-1/DC-1) NC conforming to IEC
Minimum switching current 5 mA
Maximum switching voltage 300 V DC,400 V AC
minimum switching voltage 5 V
Maximum switching capacity 3000 VA AC,336 W DC
resistive rated load 12 A at 250 V AC,12 A at 28 V DC
Minimum switching capacity 300 mW at 5 mA
Operating rate <= 600 cycles/hour under load,<= 72000 cycles/hour no-load
Mechanical durability 30000000 cycles
Electrical durability 100000 cycles, 12 A at 250 V, AC-1 NO,100000 cycles, 6 A at 250 V, AC-1 NC
Operating time 10 ms between coil de-energisation and making of the Off-delay contact,12 ms between coil energisation and making of the On-delay contact
marking CE
average coil consumption 0.75 VA AC 60 Hz
Drop-out voltage threshold >= 0.15 Uc AC
Safety reliability data B10d = 100000
Protection category RT I
Operating position Any position
Sale per indivisible quantity 10
Device presentation Complete product

Environment

Dielectric strength 1000 V AC between contacts,2500 V AC between poles,5000 V AC between coil and contact
Standards UL 508,CSA C22.2 No 14,EN/IEC 61810-1
Product certifications UL,CSA,GOST
Ambient air temperature for storage -40…85 °C
Vibration resistance +/- 1 mm (f= 10…55 Hz) conforming to EN/IEC 60068-2-6
IP degree of protection IP40 conforming to EN/IEC 60529
Shock resistance 10 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27,5 gn (duration = 11 ms) for in operation conforming to EN/IEC 60068-2-27
Ambient air temperature for operation -40…70 °C (AC),-40…85 °C (DC)

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.7 cm
Package 1 Width 10.2 cm
Package 1 Length 34 cm
Package 1 Weight 52 g
Unit Type of Package 2 BB1
Number of Units in Package 2 20
Package 2 Height 7.7 cm
Package 2 Width 10.2 cm
Package 2 Length 34 cm
Package 2 Weight 1.09 kg
Unit Type of Package 3 S03
Number of Units in Package 3 140
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 8.174 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible