Schneider Electric

RXM2AB1B7TQ

RXM2AB1B7TQ Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for RXM2AB1B7TQ Schneider Electric

RXM2AB1B7TQ Schneider Electric - Miniature Plug-in relay - Harmony RXM 2 C/O 24 V AC 12 A

Free Delivery to UK Mainland on orders over £25

Main

range of product Harmony Relay
Series name Miniature
product or component type Plug-in relay
Device short name RXM
Contacts type and composition 2 C/O
[Uc] control circuit voltage 24 V AC 50/60 Hz
Status LED Without
Control type Lockable test button
Utilisation coefficient 20 %

Complementary

Shape of pin Flat
[Ui] rated insulation voltage 250 V conforming to IEC,300 V conforming to CSA,300 V conforming to UL
[Uimp] rated impulse withstand voltage 4 kV during 1.2/50 µs
Contacts material AgNi
[Ie] rated operational current 12 A at 28 V (DC) NO conforming to IEC,12 A at 250 V (AC) NO conforming to IEC,6 A at 28 V (DC) NC conforming to IEC,6 A at 250 V (AC) NC conforming to IEC,12 A at 28 V (DC) conforming to UL,12 A at 277 V (AC) conforming to UL
Continuous output current 10 A
Maximum switching voltage 250 V conforming to IEC
resistive rated load 12 A at 250 V AC,12 A at 28 V DC
Maximum switching capacity 3000 VA/336 W
Minimum switching capacity 170 mW at 10 mA, 17 V
Operating rate <= 1200 cycles/hour under load,<= 18000 cycles/hour no-load
Mechanical durability 10000000 cycles
Electrical durability 100000 cycles for resistive load
average coil consumption in VA 1.2 at 60 Hz
Average consumption 1.2 VA at 60 Hz
Drop-out voltage threshold >= 0.15 Uc
operate time 20 ms
release time 20 ms
average coil resistance 180 Ohm at 20 °C +/- 15 %
Rated operational voltage limits 19.2...26.4 V AC
Safety reliability data B10d = 100000
Protection category RT I
Operating position Any position
net weight 0.037 kg
Device presentation Complete product

Environment

Dielectric strength 1300 V AC between contacts with micro disconnection,2000 V AC between coil and contact with basic insulation,2000 V AC between poles with basic insulation
Product certifications UL,Lloyd's,GOST,CSA,CE
Standards EN/IEC 61810-1,UL 508,CSA C22.2 No 14
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation -40…55 °C
Vibration resistance 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation,5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
IP degree of protection IP40 conforming to EN/IEC 60529
Shock resistance 10 gn for in operation,30 gn for not operating
Pollution degree 3

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible