This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Schneider Electric

TM3DI32K

TM3DI32K Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for TM3DI32K Schneider Electric

TM3DI32K Schneider Electric - Modicon TM3 - 32 inputs (HE10) 24Vdc

Extended Description for TM3DI32K Schneider Electric

TM3DI32K Schneider Electric - This digital input module is part of the Modicon TM3 range of I/O expansion modules for Modicon controllers.,It consists in 32 logic inputs and it is supplied with 24V dc.,It is equipped with one removable HE10 connector and can be mounted on a symmetrical DIN rail 35 mm.,This digital I/O module complement the embedded I/O on Modicon M221, M221 Book, M241 and M251 logic controllers.,There is an insulation between input and internal logic at 500V AC and non-insulation between inputs.,It is furnished with HE-10 connector inputs for electrical connection. It is an IP20 rated product.,Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.11kg.,This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards.,This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller.,It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount.,Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers.,Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£122.14 Exc. VAT
£146.57 Inc. VAT

Main

range of product Modicon TM3
product or component type Discrete input module
Range compatibility Modicon M241,Modicon M251,Modicon M221,Modicon M262
Discrete input number 32 for input conforming to IEC 61131-2 Type 1
Discrete input logic Sink or source (positive/negative)
Discrete input voltage 24 V
Discrete input current 5 mA for input

Complementary

Discrete I/O number 32
Current consumption 5 mA at 5 V DC via bus connector (at state off),0 mA at 24 V DC via bus connector (at state on),0 mA at 24 V DC via bus connector (at state off),65 mA at 5 V DC via bus connector (at state on)
Discrete input voltage type DC
Voltage state 1 guaranteed 15...28.8 V for input
Current state 1 guaranteed >= 2.5 mA (input)
Voltage state 0 guaranteed 0...5 V for input
Current state 0 guaranteed <= 1 mA (input)
Input impedance 4.4 kOhm
Response time 4 ms (turn-on),4 ms (turn-off)
Local signalling 1 LED per channel (green) for input status
Electrical connection HE-10 connectorfor inputs
Maximum cable distance between devices Unshielded cable: <30 m for regular input
Insulation Between input and internal logic at 500 V AC,Non-insulated between inputs
marking CE
Mounting support Top hat type TH35-15 rail conforming to IEC 60715,Top hat type TH35-7.5 rail conforming to IEC 60715, plate or panel with fixing kit
Height 90 mm
Depth 81.3 mm
Width 33.5 mm
net weight 0.1 kg

Environment

Standards IEC 61131-2
Product certifications cULus,CE,UKCA,RCM,EAC,cULus HazLoc
Resistance to electrostatic discharge 8 kV in air conforming to IEC 61000-4-2,4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3,3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3,1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields 30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients 1 kV for I/O conforming to IEC 61000-4-4
Surge withstand 1 kV I/O common mode conforming to IEC 61000-4-5 DC
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to IEC 61000-4-6,3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011,Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
Ambient air temperature for operation -10…35 °C vertical installation,-10…55 °C horizontal installation
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation),10…95 %, without condensation (in storage)
IP degree of protection IP20 with protective cover in place
Pollution degree 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail,3 gn at 8.4…150 Hz on DIN rail,3.5 mm at 5…8.4 Hz on panel,3 gn at 8.4…150 Hz on panel
Shock resistance 15 gn for 11 ms

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.639 cm
Package 1 Width 10.55 cm
Package 1 Length 12.87 cm
Package 1 Weight 220.0 g
Unit Type of Package 2 CAR
Number of Units in Package 2 42
Package 2 Height 29.6 cm
Package 2 Width 40.3 cm
Package 2 Length 55.9 cm
Package 2 Weight 10.431 kg
Unit Type of Package 3 P12
Number of Units in Package 3 504
Package 3 Height 105 cm
Package 3 Width 120 cm
Package 3 Length 80 cm
Package 3 Weight 133 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

User guide

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible