This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Schneider Electric

VLVAF6P03518AB

VLVAF6P03518AB Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for VLVAF6P03518AB Schneider Electric

VLVAF6P03518AB Schneider Electric - VarSet capacitor bank Auto 400kvar DR3,8 xxB 400V 50Hz

Free Delivery to UK Mainland on orders over £25

Main

Network rated voltage 400 V AC 50 Hz,415 V AC 50 Hz
Reactive power rating 400 kvar
Operating mode Automatic
Range PowerLogic
Device short name automatic capacitor bank with detuned reactor
product or component type Capacitor bank

Complementary

Network pollution level Polluted
[Gh/Sn] harmonic pollution rate 25…50 %
[THDU] total harmonic distorsion of voltage 4…7 %
Tuning factor 3.8
Tuning frequency 190 Hz
Power per step 50 kvar
Step composition 2x50 + 3x100
Location of connection Bottom
Controller type PowerLogic PFC Controller VPL6
capacitor technology PowerLogic PFC Capacitor + Detuned Reactor
Poles description 3P
Capacitance tolerance - 5 % to 10 %
[Ui] rated insulation voltage 800 V
[Uimp] rated impulse withstand voltage 8 kV
Maximum permissible voltage 1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
[Imp] maximum permanent current Capacitor: 1.8 x In at 480 V conforming to IEC 60831,Battery: 1.19 x In at 400 V conforming to IEC 61439-2,Battery: 1.19 x In at 415 V conforming to IEC 61439-2
main incomer protection Without protection
[Icw] rated short-time withstand current 35 kA at 1 s (Icw)
Step protection type Overload: harmonic control from PowerLogic PFC Controller,Short-circuit: fuse
Accessibility for operation Front
Colour Grey (RAL 7035)
maximum weight 952 kg
Height 2200 mm
Width Capacitor: 800 mm,Detuned reactor: 600 mm
Depth 600 mm
Provided equipment Auxiliary transformer
Internal voltage transformer 400/230 V - 1000 VA
Function available GenSet shedding contact,Alarm contact

Environment

Standards IEC 61439-1,IEC 61921,IEC 61439-2
Product certifications CE,ASEFA,EAC
Mounting location Indoor
IP degree of protection Environment: IP31,Safety: IPxx B
IK degree of protection IK10
Relative humidity 0…95 %
Operating altitude <= 2000 m
Ambient air temperature for operation -5…45 °C
Average ambient air temperature for operation 35 °C (annual) ,45 °C (over 24 hours)

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible