Description for VLVAF6P03522AK Schneider Electric

VLVAF6P03522AK Schneider Electric - VarSet capacitor bank Auto 600kvar DR3,8 Top entry 400V 50Hz CB

Extended Description for VLVAF6P03522AK Schneider Electric

VLVAF6P03522AK Schneider Electric - Low voltage power factor correction solution, from VarSet family, helps to eliminate utility penalties.,To do energy savings, to lower capital costs, and to reduce CO² emissions by the reactive power compensation of inductive loads.,This hardware is compatible with power management software to take advantage of the IoT digital power installation and allow a seemless integration to EcoStruxture Power.,Smart monitoring and measurement features are available to secure operations.,To optimize perfomance and maintenance, across a broad range of applications, commercial or industrial.,This capacitor bank version, suitable for network voltage 400 to 415V 50Hz is providing a reactive power up to 600kvar with a tuning frequency of 190Hz.,The compensation is automatically adjusted by the Power factor controller from VarplusLogic family.,It is designed for network harmonic voltage up to 7% or network harmonic current up to 20%, network defined as a polluted harmonic network.,VarSet range is certified to CE, IEC 61921, IEC 61439 part 1 & IEC61439 part 2.,It is embedding high life expectancy capacitors from Varplus family designed as per IEC831 part 1 and IEC831 part 2.,And include a smart controller with modbus communication RS485.,The enclosure RAL7035 is a floor standing type with a top entry incoming connection protected by a circuit breaker.,Frame exterior dimensions are 1400 millimetres in width, 600 millimetres in depth, 2200 millimetres height and a max product weight of 952kg.,As a standard, the enclosures are IP31. Optionnal kits are available to transform them easily into a IP54.,This product is particularly adapted for power factor correction applications with variable or unstable loads.

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£24,406.50 Exc. VAT
£29,287.80 Inc. VAT

Main

Network rated voltage 400 V AC 50 Hz,415 V AC 50 Hz
Reactive power rating 600 kvar
Operating mode Automatic
Range PowerLogic
Device short name automatic capacitor bank with detuned reactor
product or component type Capacitor bank

Complementary

Network pollution level Polluted
[Gh/Sn] harmonic pollution rate 25…50 %
[THDU] total harmonic distorsion of voltage 4…7 %
Tuning factor 3.8
Tuning frequency 190 Hz
Power per step 100 kvar
Step composition 6x100
Location of connection Top
Controller type PowerLogic PFC Controller VPL6
capacitor technology PowerLogic PFC Capacitor + Detuned Reactor
Poles description 3P
Capacitance tolerance - 5 % to 10 %
[Ui] rated insulation voltage 800 V
[Uimp] rated impulse withstand voltage 8 kV
Maximum permissible voltage 1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
[Imp] maximum permanent current Capacitor: 1.8 x In at 480 V conforming to IEC 60831,Battery: 1.19 x In at 400 V conforming to IEC 61439-2,Battery: 1.19 x In at 415 V conforming to IEC 61439-2
main incomer protection Circuit breaker protection
Breaking capacity Icu 50 kA
Control type Rotary handle
Step protection type Overload: harmonic control from PowerLogic PFC Controller,Short-circuit: fuse
Accessibility for operation Front
Colour Grey (RAL 7035)
maximum weight 952 kg
Height 2200 mm
Width Capacitor: 800 mm,Detuned reactor: 600 mm
Depth 600 mm
Provided equipment Auxiliary transformer
Internal voltage transformer 400/230 V - 1000 VA
Function available Alarm contact,GenSet shedding contact

Environment

Standards IEC 61439-2,IEC 61439-1,IEC 61921
Product certifications EAC,ASEFA,CE
Mounting location Indoor
IP degree of protection Environment: IP31,Safety: IPxx B
IK degree of protection IK10
Relative humidity 0…95 %
Operating altitude <= 2000 m
Ambient air temperature for operation -5…45 °C
Average ambient air temperature for operation 35 °C (annual) ,45 °C (over 24 hours)

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 230.0 cm
Package 1 Width 80.0 cm
Package 1 Length 156.0 cm
Package 1 Weight 986.0 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

User guide

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible