Description for 3RB2383-4AC1 Siemens

3RB2383-4AC1 Siemens - Evaluation unit for full motor protection (bistable) Size S00...S12, class 5...30 Stand-alone installation Main circuit: -- Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£248.05 Exc. VAT
£297.66 Inc. VAT

Product

Article Number (Market Facing Number) 3RB2383-4AC1
Product Description Evaluation unit for full motor protection (bistable) Size S00...S12, class 5...30 Stand-alone installation Main circuit: -- Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset
Product family Ordering Data Overview
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 01.10.2023

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 3 Day/Days
Net Weight (kg) 0,293 Kg
Packaging Dimension 111,00 x 129,00 x 55,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4011209642010
UPC Not available
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 5812
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.07.2006
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

General Technical Data

Size Of Overload Relay S00 ... S12
Size Of Contactor Can Be Combined Company-Specific S00 ... S12
Power Loss [W] For Rated Value Of The Current At Ac In Hot
Operating State0.5 W
Per Pole 0.17 W
Insulation Voltage With Degree Of Pollution 3 At Ac Rated Value 300 V
Surge Voltage Resistance Rated Value 4 Kv
Reference Code According To Iec 81346-2 F
Substance Prohibitance (Date) 07/01/2006
Svhc Substance Name Lead - 7439-92-1
Lead Monoxide (Lead Oxide) - 1317-36-8
Weight 0.293 Kg

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -25 ... +60 °C
During Storage -40 ... +80 °C
During Transport -40 ... +80 °C
Relative Humidity During Operation 100 %

Main Circuit

Number Of Poles For Main Current Circuit 3
Adjustable Current Response Value Current Of The Current-
Dependent Overload Release0.3 ... 630 A
Operation Al Current Rated Value 630 A
Control Supply Voltage At Ac
At 50 Hz Rated Value 24 ... 240 V
At 60 Hz Rated Value 24 ... 240 V
Auxiliary Circuit
Number Of Nc Contacts For Auxiliary Contacts 2
Number Of No Contacts For Auxiliary Contacts 2
Operation Al Current Of Auxiliary Contacts At Ac-15
At 24 V 6 A
At 110 V 6 A
At 120 V 6 A
At 125 V 6 A
At 230 V 3 A
Operation Al Current Of Auxiliary Contacts At Dc-13
At 24 V 2 A
At 60 V 0.55 A
At 110 V 0.3 A
At 125 V 0.3 A
At 220 V 0.2 A
Protective And Monitoring Functions
Trip Class Class 5, 10, 20 And 30 Adjustable
Short-Circuit Protection
Design Of The Fuse Link
For Short-Circuit Protection Of The Auxiliary Switch Required Fuse Gl/Gg: 6 A
Installation/ Mounting/ Dimensions
Mounting Position Any
Fastening Method Stand-Alone Installation
Height 111 Mm
Width 45 Mm
Depth 95 Mm
Required Spacing
With Side-By-Side Mounting
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— Downwards 0 Mm
— At The Side 0 Mm
For Grounded Parts
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— At The Side 6 Mm
— Downwards 0 Mm
For Live Parts
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— Downwards 0 Mm
— At The Side 6 Mm

Connections/ Terminals

Product Component Removable Terminal For Auxiliary And
Control Circuityes
Type Of Electrical Connection
For Auxiliary And Control Circuit Spring-Loaded Terminals
Type Of Connectable Conductor Cross-Sections
For Auxiliary Contacts
— Finely Stranded With Core End Processing 2X (0.25 ... 1.5 Mm²)
For Awg Cables For Auxiliary Contacts 2X (24 ... 16)
Electrical Safety
Protection Class Ip On The Front According To Iec 60529 Ip20
Touch Protection On The Front According To Iec 60529 Finger-Safe, For Vertical Contact From The Front

Documentation