This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

3RN2010-2BW30

3RN2010-2BW30 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3RN2010-2BW30 Siemens

3RN2010-2BW30 Siemens - THERMISTOR MOTOR PROTECTION 2CO BIMETAL

Extended Description for 3RN2010-2BW30 Siemens

3RN2010-2BW30 Siemens - Thermistor motor prot. relay Standard evaluation unit 22.5 mm enclosure Spring-type terminals 2 CO contacts US = 24-240 V AC/DC Auto RESET Suitable for bimetal switches 2 LEDs (READY/TRIPPED) Galvanic separation

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£66.35 Exc. VAT
£79.62 Inc. VAT

Product

Article Number (Market Facing Number) 3RN2010-2BW30
Product Description Thermistor motor protection relay Standard evaluation unit 22.5 mm enclosure Spring-type terminal 2 change-over contacts US = 24 V-240 V AC/DC Auto-reset suitable for bimetallic switch 2 LEDs (READY/TRIPPED) galvanic isolation
Product family SIRIUS 3RN2 thermistor motor protection
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 5 Day/Days
Net Weight (kg) 0,172 Kg
Packaging Dimension 111,00 x 129,00 x 38,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047621004471
UPC 804766415586
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 4953
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 28.05.2009
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

General Technical Data

Product Function Thermistor Motor Protection
Display Version Led Yes
Power Loss [W] For Rated Value Of The Current
At Ac In Hot Operating State 1.4 W
At Dc In Hot Operating State 1.4 W
Insulation Voltage For Overvoltage Category Iii According To Iec
60664 With Degree Of Pollution 3 Rated Value300 V
Degree Of Pollution 3
Surge Voltage Resistance Rated Value 4 Kv
Shock Resistance According To Iec 60068-2-27 11G / 15 Ms
Vibration Resistance According To Iec 60068-2-6 10 ... 55 Hz: 0.35 Mm
Mechanical Service Life (Operating Cycles) Typical 10 000 000
Electrical Endurance (Operating Cycles) At Ac-15 At 230 V
Typical100 000
Thermal Current Of The Switching Element With Contacts
Maximum 5 A
Reference Code According To Iec 81346-2 K
Substance Prohibitance (Date) 05/28/2009
Svhc Substance Name Lead - 7439-92-1
Lead Monoxide (Lead Oxide) - 1317-36-8
Weight 0.172 Kg

Product Function

Product Function
Error Memory No
Dynamic Open-Circuit Detection No
External Reset No
Auto-Reset Yes
Manual Reset No
Control Circuit/
Type Of Voltage Of The Control Supply Voltage Ac/Dc
Control Supply Voltage At Ac
At 50 Hz Rated Value 24 ... 240 V
At 60 Hz Rated Value 24 ... 240 V
Control Supply Voltage At Dc Rated Value 24 ... 240 V
Operating Range Factor Control Supply Voltage Rated Value At
Dc
Initial Value 0.85
Full-Scale Value 1.1
Operating Range Factor Control Supply Voltage Rated Value At
Ac At 50 Hz
Initial Value 0.85
Full-Scale Value 1.1
Operating Range Factor Control Supply Voltage Rated Value At
Ac At 60 Hz
Initial Value 0.85
Full-Scale Value 1.1
Inrush Current Peak
At 24 V 0.6 A
At 240 V 12 A
Duration Of Inrush Current Peak
At 24 V 0.25 Ms
At 240 V 0.2 Ms
Measuring Circuit
Buffering Time In The Event Of Power Failure Minimum 40 Ms
Precision
Relative Metering Precision 9 %

Auxiliary Circuit

Material Of Switching Contacts Agsno2
Number Of Nc Contacts For Auxiliary Contacts 0
Number Of No Contacts For Auxiliary Contacts 0
Number Of Co Contacts For Auxiliary Contacts 2

Main Circuit

Operating Frequency Rated Value 50 ... 60 Hz
Ampacity Of The Output Relay At Ac-15 At 250 V At 50/60 Hz 3 A
Ampacity Of The Output Relay At Dc-13
At 24 V 1 A
At 125 V 0.2 A
Continuous Current Of The Diazed Fuse Link Of The Output
Relay6 A

Conducted Interference

Due To Burst According To Iec 61000-4-4 2 Kv (Power Ports) / 1 Kv (Signal Ports)
Due To Conductor-Earth Surge According To Iec 61000-4-5 2 Kv (Line To Ground)
Due To Conductor-Conductor Surge According To Iec
61000-4-51 Kv (Line To Line)
Electrostatic Discharge According To Iec 61000-4-2 6 Kv Contact Discharge / 8 Kv Air Discharge
Galvanic Isolation
Design Of The Electrical Isolation Galvanic Isolation
Galvanic Isolation
Between Input And Output Yes
Between The Outputs Yes
Between The Voltage Supply And Other Circuits Yes

Connections/ Terminals

Product Component Removable Terminal For Auxiliary And
Control Circuityes
Type Of Electrical Connection Spring-Loaded Terminal (Push-In)
For Auxiliary And Control Circuit Spring-Loaded Terminals (Push-In)
Type Of Connectable Conductor Cross-Sections
Solid 0.5 ... 4 Mm²
Finely Stranded With Core End Processing 0.5 ... 2.5 Mm²
Finely Stranded Without Core End Processing 0.5 ... 4 Mm²
For Awg Cables Solid 20 ... 12
For Awg Cables Stranded 20 ... 12
Connectable Conductor Cross-Section
Solid 0.5 ... 4 Mm²
Finely Stranded With Core End Processing 0.5 ... 2.5 Mm²
Finely Stranded Without Core End Processing 0.5 ... 4 Mm²
Awg Number As Coded Connectable Conductor Cross
Section
Solid 20 ... 12
Stranded 20 ... 12
Installation/ Mounting/ Dimensions
Mounting Position Any
Fastening Method Screw And Snap-On Mounting Onto 35 Mm Din Rail
Height 100 Mm
Width 22.5 Mm
Depth 90 Mm
Required Spacing
With Side-By-Side Mounting
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— Downwards 0 Mm
— At The Side 0 Mm
For Grounded Parts
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— At The Side 0 Mm
— Downwards 0 Mm
For Live Parts
— Forwards 0 Mm
— Backwards 0 Mm
— Upwards 0 Mm
— Downwards 0 Mm
— At The Side 0 Mm

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -25 ... +60 °C
During Storage -40 ... +85 °C
During Transport -40 ... +85 °C
Relative Humidity During Operation Maximum 70 %

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible