Description for 3RT1456-6AM36-Z X95 Siemens

3RT1456-6AM36-Z X95 Siemens - Contactor, AC-1, 275 A/690 V/40 °C, S6, 3-pole, 200-220 V AC/DC, with varistor, 2 NO+2 NC, Connection rail/ screw terminal, 9 units

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 3RT1456-6AM36-Z X95
Product Description power contactor AC-1 275 A / 690 V / 40 °C 3-pole, Uc: 200-220 V AC(50-60 Hz) / DC drive: conventional auxiliary contacts 2 NO + 2 NC main circuit: busbar control and auxiliary circuit: screw terminal
Product family Ordering Data Overview
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) On request
Net Weight (kg) 3,100 Kg
Package size unit of measure Not available
Quantity Unit 1 Piece
Packaging Quantity 1
Minimum order quantity 9

Additional Product Information

EAN Not available
UPC Not available
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 3706
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.05.2012
Product class C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Reach Information There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern. We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
SCIP number

General Technical Data

Size Of Contactor S6

Product Extension

Function Module For Communication No
Auxiliary Switch Yes
Power Loss [W] For Rated Value Of The Current
At Ac In Hot Operating State 86.4 W
At Ac In Hot Operating State Per Pole 28.8 W
Without Load Current Share Typical 5.2 W
Type Of Calculation Of Power Loss Depending On Pole Quadratic
Insulation Voltage
Of Main Circuit With Degree Of Pollution 3 Rated Value 1 000 V
Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value 500 V
Surge Voltage Resistance
Of Main Circuit Rated Value 8 Kv
Of Auxiliary Circuit Rated Value 6 Kv
Shock Resistance At Rectangular Impulse
At Ac 8,5G / 5 Ms, 4,2G / 10 Ms
At Dc 8,5G / 5 Ms, 4,2G / 10 Ms
Shock Resistance With Sine Pulse
At Ac 13,4G / 5 Ms, 6,5G / 10 Ms
At Dc 13,4G / 5 Ms, 6,5G / 10 Ms
Mechanical Service Life (Operating Cycles)
Of Contactor Typical 10 000 000
Of The Contactor With Added Electronically Optimized
Auxiliary Switch Block Typical5 000 000
Of The Contactor With Added Auxiliary Switch Block Typical 10 000 000
Reference Code According To Iec 81346-2 Q
Substance Prohibitance (Date) 05/01/2012
Weight 3.1 Kg

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -25 ... +60 °C
During Storage -55 ... +80 °C
Relative Humidity Minimum 10 %
Relative Humidity At 55 °C According To Iec 60068-2-30
Maximum 95 %
3Rt14566Am36-Z X95

Main Circuit

Number Of Poles For Main Current Circuit 3
Number Of No Contacts For Main Contacts 3
Number Of Nc Contacts For Main Contacts 0
Type Of Voltage For Main Current Circuit Ac
Operation Al Current
At Ac-1
— Up To 690 V At Ambient Temperature 40 °C Rated
Value275 A
— Up To 690 V At Ambient Temperature 55 °C Rated
Value250 A
— Up To 690 V At Ambient Temperature 60 °C Rated
Value250 A
At Ac-3
— At 400 V Rated Value 97 A
— At 690 V Rated Value 97 A
Minimum Cross-Section In Main Circuit At Maximum Ac-1 Rated
Value140 Mm²
No-Load Switching Frequency
At Ac 2 000 1/H
At Dc 2 000 1/H
Operating Frequency At Ac-1 Maximum 600 1/H
Control Circuit/
Type Of Voltage Ac/Dc
Type Of Voltage Of The Control Supply Voltage Ac/Dc
Control Supply Voltage At Ac
At 50 Hz Rated Value 200 ... 220 V
At 60 Hz Rated Value 200 ... 220 V
Control Supply Voltage At Dc Rated Value 200 ... 220 V
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Dc
Initial Value 0.8
Full-Scale Value 1.1
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Ac
At 50 Hz 0.8 ... 1.1
At 60 Hz 0.8 ... 1.1
Design Of The Surge Suppressor With Varistor
Apparent Pick-Up Power
At Minimum Rated Control Supply Voltage At Ac
— At 50 Hz 250 Va
— At 60 Hz 250 Va
At Maximum Rated Control Supply Voltage At Ac
— At 60 Hz 300 Va
— At 50 Hz 300 Va
Apparent Pick-Up Power Of Magnet Coil At Ac
At 50 Hz 300 Va
Inductive Power Factor With Closing Power Of The Coil
At 50 Hz 0.9
Apparent Holding Power
At Minimum Rated Control Supply Voltage At Dc 4.3 Va
At Maximum Rated Control Supply Voltage At Dc 5.2 Va
Apparent Holding Power
At Minimum Rated Control Supply Voltage At Ac
— At 50 Hz 4.8 Va
— At 60 Hz 4.8 Va
At Maximum Rated Control Supply Voltage At Ac
— At 50 Hz 5.8 Va
— At 60 Hz 5.8 Va
Apparent Holding Power Of Magnet Coil At Ac
At 50 Hz 5.8 Va
Inductive Power Factor With The Holding Power Of The Coil
3Rt14566Am36-Z X95
At 50 Hz 0.8
Closing Power Of Magnet Coil At Dc 360 W
Holding Power Of Magnet Coil At Dc 5.2 W
Closing Delay
At Ac 20 ... 95 Ms
At Dc 20 ... 95 Ms
Opening Delay
At Ac 40 ... 60 Ms
At Dc 40 ... 60 Ms
Arcing Time 10 ... 15 Ms
Control Version Of The Switch Operating Mechanism Standard A1 - A2

Auxiliary Circuit

Number Of Nc Contacts For Auxiliary Contacts 2
Attachable 4
Instantaneous Contact 2
Number Of No Contacts For Auxiliary Contacts 2
Attachable 4
Instantaneous Contact 2
Operation Al Current At Ac-12 Maximum 10 A
Operation Al Current At Ac-15
At 230 V Rated Value 6 A
At 400 V Rated Value 3 A
At 500 V Rated Value 2 A
At 690 V Rated Value 1 A
Operation Al Current At Dc-13
At 24 V Rated Value 10 A
At 48 V Rated Value 2 A
At 60 V Rated Value 2 A
At 110 V Rated Value 1 A
At 125 V Rated Value 0.9 A
At 220 V Rated Value 0.3 A
At 600 V Rated Value 0.1 A
Design Of The Miniature Circuit Breaker For Short-Circuit Protection
Of The Auxiliary Switch Requiredgg: 10 A (230 V, 400 A)
Contact Reliability Of Auxiliary Contacts 1 Faulty Switching Per 100 Million (17 V, 1 Ma)
Short-Circuit Protection
Product Function Short Circuit Protection No
Design Of The Fuse Link
For Short-Circuit Protection Of The Main Circuit
— With Type Of Coordination 1 Required Gg: 355 A (690 V, 100 Ka)
— With Type Of Assignment 2 Required Gr: 350 A (690 V, 100 Ka)
For Short-Circuit Protection Of The Auxiliary Switch Required Gg: 10 A (500 V, 1 Ka)
Installation/ Mounting/ Dimensions
Mounting Position With Vertical Mounting Surface +/-90° Rotatable, With Vertical Mounting Surface
+/- 22.5° Tiltable To The Front And Back
Fastening Method Side-By-Side Mounting Yes
Fastening Method Screw Fixing
Height 172 Mm
Width 120 Mm
Depth 170 Mm
Required Spacing
With Side-By-Side Mounting
— Forwards 20 Mm
— Upwards 10 Mm
— Downwards 10 Mm
— At The Side 0 Mm
For Grounded Parts
— Forwards 20 Mm
— Upwards 10 Mm
— At The Side 10 Mm
— Downwards 10 Mm
3Rt14566Am36-Z X95
For Live Parts
— Forwards 20 Mm
— Upwards 10 Mm
— Downwards 10 Mm
— At The Side 10 Mm

Connections/ Terminals

Type Of Electrical Connection
For Main Current Circuit Connection Bar
For Auxiliary And Control Circuit Screw-Type Terminals
At Contactor For Auxiliary Contacts Screw-Type Terminals
Of Magnet Coil Screw-Type Terminals
Width Of Connection Bar 17 Mm
Thickness Of Connection Bar 3 Mm
Diameter Of Holes 9 Mm
Number Of Holes 1
Connectable Conductor Cross-Section For Main Contacts
Solid Or Stranded 25 ... 120 Mm²
Stranded 25 ... 120 Mm²
Connectable Conductor Cross-Section For Auxiliary Contacts
Solid Or Stranded 0.5 ... 4 Mm²
Finely Stranded With Core End Processing 0.5 ... 2.5 Mm²
Type Of Connectable Conductor Cross-Sections
For Auxiliary Contacts
— Solid 2X (0.5 ... 1.5 Mm²), 2X (0.75 ... 2.5 Mm²), Max. 2X (0.75 ... 4 Mm²)
— Solid Or Stranded 2X (0,5 ... 1,5 Mm²), 2X (0,75 ... 2,5 Mm²), Max. 2X (0,75 ... 4 Mm²)
— Finely Stranded With Core End Processing 2X (0.5 ... 1.5 Mm²), 2X (0.75 ... 2.5 Mm²)
For Awg Cables For Auxiliary Contacts 2X (20 ... 16), 2X (18 ... 14), 1X 12

Product Function

Mirror Contact According To Iec 60947-4-1 Yes
Positively Driven Operation According To Iec 60947-5-1 No
Suitable For Safety Function Yes
Suitability For Use Safety-Related Switching Off Yes
Service Life Maximum 20 A
Proportion Of Dangerous Failures
With Low Demand Rate According To Sn 31920 40 %
With High Demand Rate According To Sn 31920 73 %
B10 Value With High Demand Rate According To Sn 31920 1 000 000
Failure Rate [Fit] With Low Demand Rate According To Sn
31920100 Fit
Iso 13849
Device Type According To Iso 13849-1 3
Overdimensioning According To Iso 13849-2 Necessary Yes
Iec 61508
Safety Device Type According To Iec 61508-2 Type A
Electrical Safety
Protection Class Ip On The Front According To Iec 60529 Ip00; Ip20 With Box Terminal/Cover
Touch Protection On The Front According To Iec 60529 Finger-Safe, For Vertical Contact From The Front With Box Terminal/Cover

Documentation