This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

3RT1485-6AP36

3RT1485-6AP36 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3RT1485-6AP36 Siemens

3RT1485-6AP36 Siemens - Power contactor, AC-1 1700 A, 3-pole AC (50...60 Hz) / DC operation 100...240 V AC / 100...220 V DC Operating mechanism: electronic Auxiliary contacts 2 NO + 2 NC Busbar connections Auxiliary switch and coil connections in screw-type technology

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 3RT1485-6AP36
Product Description power contactor AC-1 1700 A / 690 V / 40 °C 3-pole, Uc: 220-240 V AC(50-60 Hz) / DC drive: conventional auxiliary contacts 2 NO + 2 NC main circuit: busbar control and auxiliary circuit: screw terminal
Product family SIRIUS 3RT.4 contactors for weak or non-inductive loads (AC-1), 3-pole up to 2 650 A
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : EAR99
Estimated dispatch time (Working Days) 5 Day/Days
Net Weight (kg) 40,000 Kg
Packaging Dimension 500,00 x 450,00 x 300,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047621054766
UPC 195125051355
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 2234
Group Code R711
Country of origin South Korea
Compliance with the substance restrictions according to RoHS directive Since: 27.03.2020
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Reach Information There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern. We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
SCIP number

Product Extension

Function Module For Communication No
Auxiliary Switch Yes
Power Loss [W] For Rated Value Of The Current
At Ac In Hot Operating State 660 W
At Ac In Hot Operating State Per Pole 220 W
Without Load Current Share Typical 11 W
Type Of Calculation Of Power Loss Depending On Pole Quadratic
Insulation Voltage
Of Main Circuit With Degree Of Pollution 3 Rated Value 1 000 V
Of Auxiliary Circuit With Degree Of Pollution 3 Rated Value 600 V
Surge Voltage Resistance
Of Main Circuit Rated Value 8 Kv
Of Auxiliary Circuit Rated Value 6 Kv
Shock Resistance With Sine Pulse
At Ac 8G / 11 Ms
At Dc 8G / 11 Ms
Mechanical Service Life (Operating Cycles)
Of Contactor Typical 500 000
Substance Prohibitance (Date) 03/27/2020
Weight 40 Kg

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -25 ... +55 °C
During Storage -40 ... +80 °C
Relative Humidity Minimum 10 %
Relative Humidity At 55 °C According To Iec 60068-2-30
Maximum 95 %

Main Circuit

Number Of Poles For Main Current Circuit 3
Number Of No Contacts For Main Contacts 3
Number Of Nc Contacts For Main Contacts 0
Type Of Voltage For Main Current Circuit Ac
Operation Al Current
At Ac-1
— Up To 690 V At Ambient Temperature 40 °C Rated
Value1 700 A
— Up To 690 V At Ambient Temperature 55 °C Rated
Value1 700 A
— Up To 1000 V At Ambient Temperature 40 °C Rated
Value1 700 A
— Up To 1000 V At Ambient Temperature 55 °C Rated
Value1 700 A
Minimum Cross-Section In Main Circuit At Maximum Ac-1 Rated
Value1 500 Mm²
No-Load Switching Frequency
At Ac 300 1/H
At Dc 300 1/H
Operating Frequency At Ac-1 Maximum 300 1/H
Control Circuit/
Type Of Voltage Of The Control Supply Voltage Ac/Dc
Control Supply Voltage At Ac
At 50 Hz Rated Value 100 ... 240 V
At 60 Hz Rated Value 100 ... 240 V
Control Supply Voltage At Dc Rated Value 100 ... 220 V
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Dc
Initial Value 0.85
Full-Scale Value 1.1
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Ac
At 50 Hz 0.85 ... 1.1
At 60 Hz 0.85 ... 1.1
Design Of The Surge Suppressor With Varistor
Apparent Pick-Up Power Of Magnet Coil At Ac
At 50 Hz 1 800 Va
At 60 Hz 1 800 Va
Apparent Holding Power Of Magnet Coil At Ac
At 50 Hz 33 Va
At 60 Hz 33 Va
Closing Power Of Magnet Coil At Dc 2 800 W
Holding Power Of Magnet Coil At Dc 11 W
Closing Delay
At Ac 80 Ms
At Dc 80 Ms
Opening Delay
At Ac 70 Ms
At Dc 70 Ms
Control Version Of The Switch Operating Mechanism Standard A1 - A2

Auxiliary Circuit

Number Of Nc Contacts For Auxiliary Contacts 2
Attachable 4
Instantaneous Contact 2
Number Of No Contacts For Auxiliary Contacts 2
Attachable 4
Instantaneous Contact 2
Operation Al Current At Ac-12 Maximum 16 A
Operation Al Current At Ac-15
At 230 V Rated Value 3 A
At 400 V Rated Value 1.5 A
At 500 V Rated Value 1.4 A
Operation Al Current At Dc-13
At 48 V Rated Value 2 A
At 60 V Rated Value 2 A
At 110 V Rated Value 1 A
At 125 V Rated Value 0.55 A
At 220 V Rated Value 0.27 A
At 600 V Rated Value 0.1 A
Short-Circuit Protection
Product Function Short Circuit Protection No
Design Of The Fuse Link
For Short-Circuit Protection Of The Main Circuit
— With Type Of Assignment 2 Required Ar: 2200 A (1000 V, 42 Ka)
For Short-Circuit Protection Of The Auxiliary Switch Required Gg: 16 A (600 V, 1 Ka)
Installation/ Mounting/ Dimensions
Mounting Position +/-30° Rotation Possible On Vertical Mounting Surface; Can Be Tilted Forward And
Backward By +/- 30° On Vertical Mounting Surface
Fastening Method Side-By-Side Mounting No
Fastening Method Screw Fixing
Height 403 Mm
Width 431 Mm
Depth 246 Mm
Required Spacing
For Grounded Parts
— Forwards 245 Mm
— At The Side 215 Mm
Net Weight 34.6 Kg

Connections/ Terminals

Type Of Electrical Connection
For Main Current Circuit Busbar Connection
For Auxiliary And Control Circuit Screw-Type Terminals
At Contactor For Auxiliary Contacts Screw-Type Terminals
Of Magnet Coil Screw-Type Terminals
Width Of Connection Bar 103 Mm
Thickness Of Connection Bar 10 Mm
Diameter Of Holes 15 Mm
Connectable Conductor Cross-Section For Auxiliary Contacts
Solid Or Stranded 1 ... 2.5 Mm²
Finely Stranded With Core End Processing 1 ... 2.5 Mm²
Type Of Connectable Conductor Cross-Sections
For Auxiliary Contacts
— Solid 2X (1 ... 2,5 Mm²)
— Solid Or Stranded 2X (1 ... 2.5 Mm²)
— Finely Stranded With Core End Processing 2X (1 ... 2,5 Mm²)
For Awg Cables For Auxiliary Contacts 2X (16 ... 14)

Product Function

Mirror Contact According To Iec 60947-4-1 Yes
Positively Driven Operation According To Iec 60947-5-1 No
Suitable For Safety Function Yes
Suitability For Use Safety-Related Switching Off Yes
Service Life Maximum 20 A
Proportion Of Dangerous Failures
With Low Demand Rate According To Sn 31920 40 %
With High Demand Rate According To Sn 31920 73 %
B10 Value With High Demand Rate According To Sn 31920 1 000 000
Failure Rate [Fit] With Low Demand Rate According To Sn
31920100 Fit
Iso 13849
Device Type According To Iso 13849-1 3
Overdimensioning According To Iso 13849-2 Necessary Yes
Iec 61508
Safety Device Type According To Iec 61508-2 Type A
Electrical Safety
Protection Class Ip On The Front According To Iec 60529 Ip00

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible