This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

3RV2041-4FA10

3RV2041-4FA10 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3RV2041-4FA10 Siemens

3RV2041-4FA10 Siemens - CIRCUIT BREAKER. SCREW-TYPE. 40 A

Extended Description for 3RV2041-4FA10 Siemens

3RV2041-4FA10 Siemens - Circuit-breaker size s3 for motor protection. class 10. a-rel. 28...40 a. n-res. 520 a. screw terminal. standard switching capacity

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£128.52 Exc. VAT
£154.22 Inc. VAT

Product

Article Number (Market Facing Number) 3RV2041-4FA10
Product Description Circuit breaker size S3 for motor protection, CLASS 10 A-release 28...40 A N-release 520 A screw terminal Standard switching capacity
Product family SIRIUS 3RV2 motor starter protectors
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 5 Day/Days
Net Weight (kg) 2,190 Kg
Packaging Dimension 172,00 x 191,00 x 81,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047621013831
UPC 804766361814
Commodity Code 85362090
LKZ_FDB/ CatalogID CC-IC10
Product Group 3673
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.03.2017
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

General Technical Data

Size Of The Circuit-Breaker S3
Size Of Contactor Can Be Combined Company-Specific S3
Product Extension Auxiliary Switch Yes
Power Loss [W] For Rated Value Of The Current
At Ac In Hot Operating State 23 W
At Ac In Hot Operating State Per Pole 7.7 W
Insulation Voltage With Degree Of Pollution 3 At Ac Rated Value 1 000 V
Surge Voltage Resistance Rated Value 8 Kv
Shock Resistance According To Iec 60068-2-27 25G / 11 Ms Sinus
Mechanical Service Life (Operating Cycles)
Of The Main Contacts Typical 25 000
Of Auxiliary Contacts Typical 25 000
Electrical Endurance (Operating Cycles) Typical 25 000
Reference Code According To Iec 81346-2 Q
Substance Prohibitance (Date) 03/01/2017
Svhc Substance Name Lead - 7439-92-1
Weight 2.19 Kg

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -20 ... +60 °C
During Storage -50 ... +80 °C
During Transport -50 ... +80 °C
Relative Humidity During Operation 10 ... 95 %
Environmental Footprint
Global Warming Potential [Co2 Eq] Total 283.24 Kg
Global Warming Potential [Co2 Eq] During Manufacturing 18.5 Kg
Global Warming Potential [Co2 Eq] During Sales 1.24 Kg
Global Warming Potential [Co2 Eq] During Operation 265 Kg
Global Warming Potential [Co2 Eq] After End Of Life -1.5 Kg
Siemens Eco Profile (Sep) Siemens Ecotech

Main Circuit

Number Of Poles For Main Current Circuit 3
Adjustable Current Response Value Current Of The Current-
Dependent Overload Release28 ... 40 A
Operating Voltage
Rated Value 20 ... 690 V
At Ac-3 Rated Value Maximum 690 V
At Ac-3E Rated Value Maximum 690 V
Operating Frequency Rated Value 50 ... 60 Hz
Operation Al Current Rated Value 40 A
Operation Al Current
At Ac-3 At 400 V Rated Value 40 A
At Ac-3E At 400 V Rated Value 40 A
Operating Power
At Ac-3
— At 230 V Rated Value 11 Kw
— At 400 V Rated Value 18.5 Kw
— At 500 V Rated Value 22 Kw
— At 690 V Rated Value 37 Kw
At Ac-3E
— At 230 V Rated Value 11 Kw
— At 400 V Rated Value 18.5 Kw
— At 500 V Rated Value 22 Kw
— At 690 V Rated Value 37 Kw
Operating Frequency
At Ac-3 Maximum 15 1/H
At Ac-3E Maximum 15 1/H
Protective And Monitoring Functions

Product Function

Ground Fault Detection No
Phase Failure Detection Yes
Trip Class Class 10
Design Of The Overload Release Thermal
Maximum Short-Circuit Current Breaking Capacity (Icu)
At Ac At 240 V Rated Value 100 Ka
At Ac At 400 V Rated Value 65 Ka
At Ac At 500 V Rated Value 12 Ka
At Ac At 690 V Rated Value 6 Ka
Operating Short-Circuit Current Breaking Capacity (Ics) At Ac
At 240 V Rated Value 100 000 Ka
At 400 V Rated Value 30 Ka
At 500 V Rated Value 6 000 Ka
Response Value Current Of Instantaneous Short-Circuit Trip Unit 520 A
Ul/Csa Ratings
Full-Load Current (Fla) For 3-Phase Ac Motor
At 480 V Rated Value 40 A
At 600 V Rated Value 40 A
Yielded Mechanical Performance [Hp]
For Single-Phase Ac Motor
— At 110/120 V Rated Value 3 Hp
— At 230 V Rated Value 7.5 Hp
For 3-Phase Ac Motor
— At 200/208 V Rated Value 15 Hp
— At 220/230 V Rated Value 15 Hp
— At 460/480 V Rated Value 30 Hp
— At 575/600 V Rated Value 40 Hp
Short-Circuit Protection
Product Function Short Circuit Protection Yes
Design Of The Short-Circuit Trip Magnetic
Installation/ Mounting/ Dimensions
Mounting Position Any
Fastening Method Screw And Snap-On Mounting Onto 35 Mm Din Rail According To Din En 60715
Height 165 Mm
Width 70 Mm
Depth 176 Mm
Required Spacing
With Side-By-Side Mounting At The Side 0 Mm
For Grounded Parts At 400 V
— Downwards 70 Mm
— Upwards 70 Mm
— At The Side 10 Mm
For Live Parts At 400 V
— Downwards 70 Mm
— Upwards 70 Mm
— At The Side 10 Mm
For Grounded Parts At 500 V
— Downwards 110 Mm
— Upwards 110 Mm
— At The Side 10 Mm
For Live Parts At 500 V
— Downwards 110 Mm
— Upwards 110 Mm
— At The Side 10 Mm
For Grounded Parts At 690 V
— Downwards 150 Mm
— Upwards 150 Mm
— At The Side 30 Mm
For Live Parts At 690 V
— Downwards 150 Mm
— Upwards 150 Mm
— At The Side 30 Mm

Connections/ Terminals

Type Of Electrical Connection
For Main Current Circuit Screw-Type Terminals
Arrangement Of Electrical Connectors For Main Current
Circuittop And Bottom
Type Of Connectable Conductor Cross-Sections
For Main Contacts
— Solid 2X (2.5 ... 16 Mm²)
— Solid Or Stranded 2X (2,5 ... 50 Mm²), 1X (10 ... 70 Mm²)
— Finely Stranded With Core End Processing 2X (2.5 ... 35 Mm²), 1X (2.5 ... 50 Mm²)
— Finely Stranded Without Core End Processing 2X (10 ... 35 Mm²), 1X (10 ... 50 Mm²)
Tightening Torque
For Main Contacts For Ring Cable Lug 4.5 ... 6 N·M
Outer Diameter Of The Usable Ring Cable Lug Maximum 19 Mm
Tightening Torque
For Main Contacts With Screw-Type Terminals 4.5 ... 6 N·M

Safety Related Data

Product Function Suitable For Safety Function Yes
Suitability For Use
Safety-Related Switching On No
Safety-Related Switching Off Yes
Service Life Maximum 10 A
Test Wear-Related Service Life Necessary Yes
Proportion Of Dangerous Failures
With Low Demand Rate According To Sn 31920 40 %
With High Demand Rate According To Sn 31920 50 %
B10 Value With High Demand Rate According To Sn 31920 5 000
Failure Rate [Fit] With Low Demand Rate According To Sn
3192050 Fit
Iso 13849
Device Type According To Iso 13849-1 3
Overdimensioning According To Iso 13849-2 Necessary Yes
Iec 61508
Safety Device Type According To Iec 61508-2 Type A
T1 Value
For Proof Test Interval Or Service Life According To Iec
6150810 A
Electrical Safety
Protection Class Ip On The Front According To Iec 60529 Ip20
Touch Protection On The Front According To Iec 60529 Finger-Safe, For Vertical Contact From The Front
Display
Display Version For Switching Status Handle

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible