This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

3TK2822-2CB30

3TK2822-2CB30 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3TK2822-2CB30 Siemens

3TK2822-2CB30 Siemens - SIRIUS safety relay with relay enabling circuits (EC) 24 V AC/DC, 22.5 mm Spring-type terminal EC instantaneous: 2 NO EC delayed: 0 NO SC: 0 NC AUTOSTART Basic device Maximum achieved SIL: 3, PL: e

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 3TK2822-2CB30
Product Description SIRIUS safety relay with relay enabling circuits (EC) 24 V AC/DC, 22.5 mm Spring-type terminal EC instantaneous: 2 NO EC delayed: 0 NO SC: 0 NC AUTOSTART Basic device Maximum achieved SIL: 3, PL: e
Product family Not available
Product Lifecycle (PLM) PM490:Start of final year of support
PLM Effective Date Product discontinued since: 01.10.2020
Notes Product is no longer available Sucessor:The preferred successor is 3SK1111-2AB30 (one signaling circuit less) If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : N / AL : N
Estimated dispatch time (Working Days) 15 Day/Days
Net Weight (kg) 0,237 Kg
Packaging Dimension 28,00 x 106,50 x 124,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4011209445321
UPC 754554653365
Commodity Code 85364900
LKZ_FDB/ CatalogID CC-IC10
Product Group 5837
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 28.05.2009
Product class C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

Product Function
Automatic Start Yes
Light Barrier Monitoring No
Standstill Monitoring No
Protective Door Monitoring Yes
Magnetically Operated Switch Monitoring Nc-No No
Magnetically Operated Switch Monitoring Nc-Nc No
Rotation Speed Monitoring No
Laser Scanner Monitoring No
Light Array Monitoring No
Emergency Off Function No
Monitored Start-Up No
Pressure-Sensitive Mat Monitoring Yes
Suitability For Interaction Press Control No
Suitability For Use
Monitoring Of Floating Sensors Yes
Monitoring Of Non-Floating Sensors No
Position Switch Monitoring Yes
Emergency-Off Circuit Monitoring No
Valve Monitoring No
Opto-Electronic Protection Device Monitoring No
Tactile Sensor Monitoring No
Magnetically Operated Switch Monitoring No
Proximity Switch Monitoring No
Safety Switch Yes
Safety-Related Circuits Yes

General Technical Data

Certificate Of Suitability Ul Approval Yes
Product Feature Cross-Circuit-Proof Yes
Insulation Voltage Rated Value 300 V
Surge Voltage Resistance Rated Value 4 000 V
Protection Class Ip
Of The Enclosure Ip40
Of The Terminal Ip20
Shock Resistance 8G / 10 Ms
Vibration Resistance According To Iec 60068-2-6 5 ... 500 Hz: 0,075 Mm
Operating Frequency Maximum 1 000 1/H
Mechanical Service Life (Operating Cycles) Typical 10 000 000
Electrical Endurance (Operating Cycles) Typical 100 000
Thermal Current Of The Switching Element With Contacts
Maximum 5 A
Substance Prohibitance (Date) 05/28/2009
Svhc Substance Name Lead Monoxide (Lead Oxide) - 1317-36-8
Weight 0.237 Kg

Ambient Conditions

Installation Altitude At Height Above Sea Level Maximum 2 000 M
Ambient Temperature
During Operation -25 ... +60 °C
During Storage -40 ... +80 °C
Relative Humidity During Operation 10 ... 95 %
Air Pressure According To Sn 31205 90 ... 106 Kpa

Electromagnetic Compatibility

Installation Environment Regarding Emc This Product Is Suitable For Class A Environments Only. In Household
Environments, This Device Can Cause Unwanted Radio Interference. The User Is
Required To Implement Appropriate Measures In This Case.
Emc Emitted Interference En 60947-5-1

Safety Related Data

Stop Category According To Iec 60204-1 0
Iec 62061
Sil Claim Limit (Subsystem) According To En 62061 3
Pfhd With High Demand Rate According To Iec 62061 1.3E-9 1/H
Iso 13849
Category According To En Iso 13849-1 4
Iec 61508
Safety Integrity Level (Sil)
According To Iec 61508 3
Safety Device Type According To Iec 61508-2 Type A
Average Probability Of Failure On Demand (Pfdavg) With Low
Demand Rate Acc. To Iec 615081.1E-6 1/Y
Hardware Fault Tolerance According To Iec 61508 1
T1 Value For Proof Test Interval Or Service Life According To Iec
6150820 A
Electrical Safety
Touch Protection Against Electrical Shock Finger-Safe
Short-Circuit Protection
Design Of The Fuse Link For Short-Circuit Protection Of The No
Contacts Of The Relay Outputs Requiredgl/Gg: 6 A, Or Quick: 10 A
Inputs
Design Of Input
Cascading Input/Functional Switching No
Feedback Input Yes
Start Input Yes
Number Of Sensor Inputs
2-Channel 1
Outputs
Number Of Outputs As Contact-Affected Switching Element
As Nc Contact
— For Signaling Function Instantaneous Contact 0
As No Contact
— Safety-Related Instantaneous Contact 2
— Safety-Related Delayed Switching 0
Number Of Outputs As Contact-Less Semiconductor
Switching Element
For Signaling Function
— Delayed Switching 0
— Instantaneous Contact 0
Safety-Related
— Delayed Switching 0
— Instantaneous Contact 0
Switching Capacity Current Of The No Contacts Of The Relay
Outputs At Dc-13
At 24 V 5 A
At 115 V 0.2 A
At 230 V 0.1 A
Switching Capacity Current Of The No Contacts Of The Relay
Outputs At Ac-15
At 115 V 5 A
At 230 V 5 A
Wire Length Between Sensor And Electronics Evaluation
Device With Cu 1.5 Mm² And 150 Nf/Km Maximum500 M
Times
Make Time With Automatic Start
At Dc Maximum 125 Ms
At Ac Maximum 125 Ms
Backslide Delay Time In The Event Of Power Failure
Maximum 100 Ms
Recovery Time After Opening Of The Safety Circuits Typical 200 Ms
Recovery Time After Power Failure Typical 200 Ms
Pulse Duration
Of The Sensor Input Minimum 25 Ms
Of The On Pushbutton Input Minimum 0.04 S
Control Circuit/
Type Of Voltage Of The Control Supply Voltage Ac/Dc
Control Supply Voltage 1 At Ac
At 50 Hz Rated Value 24 V
At 60 Hz Rated Value 24 V
Control Supply Voltage Frequency
1 Rated Value 50 Hz
2 Rated Value 60 Hz
Control Supply Voltage 1 At Dc Rated Value 24 V
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Dc
Initial Value 0.85
Full-Scale Value 1.2
Operating Range Factor Control Supply Voltage Rated Value Of
Magnet Coil At Ac
At 50 Hz 0.85 ... 1.1
At 60 Hz 0.85 ... 1.1
Installation/ Mounting/ Dimensions
Mounting Position Any
Fastening Method Screw And Snap-On Mounting
Height 120 Mm
Width 22.5 Mm
Depth 120 Mm

Connections/ Terminals

Type Of Electrical Connection Spring-Loaded Terminals
Type Of Connectable Conductor Cross-Sections
Solid 2X (0.25 ... 1.5 Mm²)
Finely Stranded With Core End Processing 2 X (0.25 ... 1.5 Mm²)
Finely Stranded Without Core End Processing 2X (0.25 ... 1.5 Mm²)
For Awg Cables Solid 2X (24 ... 16)
For Awg Cables Stranded 2X (24 ... 16)
Connectable Conductor Cross-Section
Solid 0.25 ... 1.5 Mm²
Finely Stranded With Core End Processing 0.25 ... 1.5 Mm²
Finely Stranded Without Core End Processing 0.25 ... 1.5 Mm²
Awg Number As Coded Connectable Conductor Cross
Section
Solid 24 ... 16
Stranded 24 ... 16
Dc Resistance Of The Cable Maximum 30 Ω
Type Of Electrical Connection Plug-In Socket Yes

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible