This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

3UF7120-1AA01-0

3UF7120-1AA01-0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 3UF7120-1AA01-0 Siemens

3UF7120-1AA01-0 Siemens - Current/voltage measuring module for dry-running protection of centrifugal pumps in hazardous areas; Set current 0.3 ... 4 A, Voltage measurement up to 690 V, width 45 mm, straight-through transformer

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£789.10 Exc. VAT
£946.92 Inc. VAT

Product

Article Number (Market Facing Number) 3UF7120-1AA01-0
Product Description Current/voltage measuring module for dry-running protection of centrifugal pumps in hazardous areas; Set current 0.3 ... 4 A, Voltage measurement up to 690 V, width 45 mm, straight-through transformer
Product family SIMOCODE pro 3UF7 motor management and control devices
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 5 Day/Days
Net Weight (kg) 0,204 Kg
Packaging Dimension 75,00 x 98,00 x 55,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047621058191
UPC 804766765551
Commodity Code 85371098
LKZ_FDB/ CatalogID CC-IC10
Product Group 5836
Group Code R711
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 28.05.2009
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

General Technical Data

Measuring Procedure Rms Value Measurement
Size Of The Circuit-Breaker S00, S0

Product Function

Current Measurement Yes
Voltage Measurement Yes
Active Power Measurement Yes
Energy Measurement Yes
Frequency Measurement Yes
Active Power Monitoring For Pump Dry-Run According To
Ignition Protection Type Ex Byes
Measuring Procedure For Current Measurement Trms
Current Measuring Range Extension With External Current
Transformersyes
Measuring Procedure For Voltage Measurement Trms
Measurable Supply Voltage Between The Line Conductors At
Ac Maximum Rated Value690 V
Line Conductors And Neutral Conductors Internal Resistance
For Voltage Measurementrc-Based Voltage Divider

Product Component

Input For Thermistor Connection No
Consumed Active Power 0.5 W
Insulation Voltage
With Degree Of Pollution 3 At Ac Rated Value 690 V
For Wires Of Main Circuit According To Iec 60947-1 Rated
Value6 Kv
Surge Voltage Resistance Rated Value 6 000 V
Shock Resistance According To Iec 60068-2-27 15G / 11 Ms; With Basic Unit Snapped On
Vibration Resistance 1-6 Hz / 15 Mm; 6-500 Hz / 2 G; With Basic Unit Snapped On: 1G
Substance Prohibitance (Date) 05/28/2009
Svhc Substance Name Lead - 7439-92-1
Lead Monoxide (Lead Oxide) - 1317-36-8
2-Methyl-1-(4-Methylthiophenyl)-2-Morpholinopropan-1-One - 71868-10-5
Weight 0.204 Kg

Electromagnetic Compatibility

Emc Emitted Interference According To Iec 60947-1 Class A
Emc Immunity According To Iec 60947-1 Corresponds To Degree Of Severity 3

Conducted Interference

Due To Burst According To Iec 61000-4-4 2 Kv
Due To Conductor-Earth Surge According To Iec 61000-4-5 2 Kv
Due To Conductor-Conductor Surge According To Iec
61000-4-51 Kv
Field-Based Interference According To Iec 61000-4-3 10 V/M

Inputs/ Outputs

Number Of Outputs As Contact-Affected Switching Element 0
Protective And Monitoring Functions
Product Function
Power Factor Monitoring Yes
Ground-Fault Monitoring Yes
Voltage Detection Yes
Trip Class Class 5E
Product Function
Current Detection Yes
Overload Protection Yes
Precision
Measuring Precision
Of Frequency Measurement +/- 1.5 %, 0.25 A ... 8 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos
Phi (0.5...1), 50/60 Hz, 25 °C
For Current Measurement 1 +/- 1.5 %, In Range 0.25 A ... 8 A, In Range 0.85 X 110 V ... 1.1 X 690 V (Line-To-
Line Voltage S), 50/60 Hz, 25 °C
For Current Measurement 2 +/- 3%, In Range 8 A ... 32 A, In Range 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line
Voltage S), 50/60 Hz, 25 °C
For Voltage Measurement 1 +/- 1.5 %, In Range 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), 50/60 Hz,
25 °C
At Cos Phi-Measurement 1 +/- 1.5 %, 0.4 A ... 8 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos
Phi (0.5...1), 50/60 Hz, 25 °C
At Cos Phi-Measurement 2 +/- 5%, 8 A ... 32 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos-Phi
(0.5...1), 50/60 Hz, 25 °C
At Active Power Measurement 1 +/- 5 %, 0.25 ... 8 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos Phi
(0.5...1), 50/60 Hz, 25 °C
At Active Power Measurement 2 +/- 10%, 8 A ... 32 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos-Phi
(0.5...1), 50/60 Hz, 25 °C
At Energy Measurement 1 +/- 5 %, 0.25 ... 8 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos Phi
(0.5...1), 50/60 Hz, 25 °C
At Energy Measurement 2 +/- 10%, 8 A ... 32 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos-Phi
(0.5...1), 50/60 Hz, 25 °C
At Apparent Power Measurement 1 +/- 3%, 0.25 A ... 8 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos-Phi
(0.5...1), 50/60 Hz, 25 °C
At Apparent Power Measurement 2 +/- 5 %, 8 A ... 32 A, 0.85 X 110 V ... 1.1 X 690 V (Line-To-Line Voltages), Cos Phi
(0.5...1), 50/60 Hz, 25 °C
Accuracy Of Ground-Fault Monitoring In The Range 30 % .. 120 %/Is: +/- 10 % (Class Ci-A), In Range 15 % .. 30 % Ie:
+/- 25 % (Class Ci-B), Both Values Acc. To Iec 60947-1 Annex T
Temperature Drift Per °C 0.02 %/°C; Reference Temperature: 25°C
Measured Variable Frequency 45 ... 65 Hz
Installation/ Mounting/ Dimensions
Mounting Position Any
Fastening Method Screw And Snap-On Mounting
Height 84 Mm
Width 45 Mm
Depth 64 Mm
Required Spacing
Top 30 Mm
Bottom 30 Mm
Left 0 Mm
Right 0 Mm
Diameter Of Inlet Opening 7.5 Mm
Diameter Of Inlet Opening For Current Measurement 7.5 Mm

Connections/ Terminals

Type Of Electrical Connection
For Main Current Circuit Straight-Through Transformers
For Auxiliary And Control Circuit Screw-Type Terminals
Type Of Electrical Connection At The Measurement Inputs For
Voltage Screw-Type Terminals
Type Of Connectable Conductor Cross-Sections At The
Measurement Inputs For Voltage
Finely Stranded With Core End Processing 1X (0.25 ... 2.5 Mm²), 2X (0.25 ... 1.0 Mm²)
Solid 1X (0.25 ... 2.5 Mm²), 2X (0.25 ... 1.0 Mm²)
For Awg Cables Solid 1X (24 ... 14), 2X (24 ... 18)
For Awg Cables Stranded 1X (20 ... 14), 2X (20 ... 16)
Tightening Torque At The Measurement Inputs For Voltage 0.5 ... 0.6 N·M
Tightening Torque [Lbf·In] At The Measurement Inputs For
Voltage 4.4 ... 5.3 Lbf·In

Ambient Conditions

Installation Altitude At Height Above Sea Level
1 Maximum 2 000 M
2 Maximum 3 000 M; Max. +50 °C (No Protective Separation)
3 Maximum 4 000 M; Max. +40 °C (No Protective Separation)
Ambient Temperature
During Operation -25 ... +60 °C
During Storage -40 ... +80 °C
During Transport -40 ... +80 °C
Environmental Category
During Operation According To Iec 60721 3K6 (No Formation Of Ice, No Condensation, Relative Humidity 10 ... 95%), 3C3
(No Salt Mist), 3S2 (Sand Must Not Get Into The Devices), 3M6
During Storage According To Iec 60721 1K6 (No Condensation, Relative Humidity 10 ... 95%), 1C2 (No Salt Mist), 1S2
(Sand Must Not Get Into The Devices), 1M4
During Transport According To Iec 60721 2K2, 2C1, 2S1, 2M2
Relative Humidity During Operation 10 ... 95 %
Short-Circuit Protection
Product Function Short Circuit Protection No
Iec 61508
Safety Integrity Level (Sil) According To Iec 61508 1
Atex
Certificate Of Suitability
Iecex Yes; Iecex Ptb 18.0004X
According To Atex Directive 2014/34/Eu Bvs 06 Atex F001, Ptb 18 Atex 5003 X
According To Ukca Its21Ukex0464, Its21Ukex0455X
Explosion Device Group And Category According To Atex
Directive 2014/34/Euii (2) G, Ii (2 ) D, I (M2) / I (1G/M2), Ii (1/2) G, Ii (1G/2D)
Galvanic Isolation
(Electrically) Protective Separation According To Iec 60947-1 All Circuits With Protective Separation (Double Creepage Paths And Clearances),
The Information In The "Protective Separation" Test Report, No. A0258, Must Be
Observed (Link See Further Information)

Main Circuit

Number Of Poles For Main Current Circuit 3
Adjustable Current Response Value Current Of The Current-
Dependent Overload Release0.3 ... 4 A
Operating Voltage
At Ac
— At 50 Hz Rated Value 110 ... 690 V
— At 60 Hz Rated Value 110 ... 690 V
Operating Frequency Rated Value 50 ... 60 Hz
Control Circuit/
Type Of Voltage Ac
Inrush Current Maximum 40 A; 10 X Io

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible