Description for 3VA5580-1BB36-0AA0 Siemens

3VA5580-1BB36-0AA0 Siemens - molded case switch 3VA5 UL frame 800 max short-circuit curr. rating 100kA @ 480 V 3-pole MCS110, In=800A without overload protection self protection Ii=12 x In Al-lug, line and load side

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 3VA5580-1BB36-0AA0
Product Description molded case switch 3VA5 UL frame 800 max short-circuit curr. rating 100kA @ 480 V 3-pole MCS110, In=800A without overload protection self protection Ii=12 x In Al-lug, line and load side
Product family 3VA Molded Case Circuit Breakers up to 2000 A, UL / IEC
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : EAR99
Estimated dispatch time (Working Days) 30 Day/Days
Net Weight (kg) 16,986 Kg
Packaging Dimension 250,00 x 360,00 x 180,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042949440130
UPC Not available
Commodity Code 85362090
LKZ_FDB/ CatalogID LV10
Product Group 5385
Group Code P360
Country of origin Mexico
Compliance with the substance restrictions according to RoHS directive Since: 09.06.2020
Product class C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Model

Product Brand Name Sentron
Product Designation Molded-Case Circuit Breaker
Product Designation / According To Ul File Cmas
Design Of The Product Molded Case Switch
Design Of The Load Switch / According To Ul 489 / Heating, Air
Conditioning, And Refrigeration Circuit Breaker (Hacr Type)Yes
Design Of The Load Switch / According To Ul 489 / High-Intensity-
Discharge Circuit Breaker (Hid Type)No
Design Of The Load Switch / According To Ul 489 / Switching Duty
Circuit Breaker (Swd Type)No
Design Of The Overcurrent Release Mcs110
Protection Function Of The Overcurrent Release I
Number Of Poles 3

General Technical Data

Insulation Voltage / Rated Value 800 V
Operating Voltage / At Dc / Rated Value 750 V
Operating Voltage / At Ac / Rated Value 690 V
Power Loss [W] / Maximum 210 W
Power Loss [W] / For Rated Value Of The Current / At Ac / In Hot
Operating State / Per Pole70 W
Mechanical Service Life (Operating Cycles) / Typical 10 000
Electrical Endurance (Operating Cycles) / At Ac-1 / At 380/415 V 5 800
Electrical Endurance (Operating Cycles) / At Ac-1 / At 690 V 4 000
Electrical Endurance (Operating Cycles) / At 480 V 5 800
Electrical Endurance (Operating Cycles) / At 600 V 4 000
Product Feature / For Neutral Conductors / Upgradable/Retrofittable
/ Short-Circuit And Overload Proofno

Product Function

Communication Function No
Other Measurement Function No
Net Weight 16.986 Kg

Current

Marking / According To Ul 489 / 100%-Rated Breaker No

Switching Capacity According To Iec 60947

Design Of Short-Circuit Protection For Switching Power Values In Dc Networks, See The 3Va Molded Case Circuit
Breaker Device Manual; Link To Be Found Under Service & Support In The Last
Chapter

Adjustable Parameters

Adjustable Response Value Setting Current (Ii) / For I-Tripping
Minimum 9 600 A
Maximum 9 600 A
Adjustable Setting Current (Inn) / For N-Tripping
Minimum 0 A
Maximum 0 A
Product Function / Grounding Protection No

Product Component

Undervoltage Release No
Voltage Trigger No
Trip Indicator No
Height [In] 12.91 In
Height 328 Mm
Width [In] 8.27 In
Type Of Connectable Conductor Cross-Sections / Of The Round
Conductor Terminal / Stranded4 X (4/0 - 500 Kcmil)
Width 210 Mm
Depth [In] 4.72 In
Depth 120 Mm

Connections

Arrangement Of Electrical Connectors / For Main Current Circuit Front Connection
Type Of Electrical Connection / For Main Current Circuit Circular Conductor Terminal On Both Sides

Auxiliary Circuit

Number Of Co Contacts / For Auxiliary Contacts 0

Accessories

Product Extension / Optional / Motor Drive No

Environmental Conditions

Protection Class Ip / On The Front Ip40
Ambient Temperature
During Operation / Minimum -25 °C
During Operation / Maximum 70 °C
During Storage / Minimum -40 °C
During Storage / Maximum 80 °C
Reference Code / According To Iec 81346-2 Q
Approvals / Certificates
General Product Approval
Confirmation
General Product Approval Emv Test Certificates Marine / Shipping
Miscellaneous
Type Test Certific-
Ates/Test Report
Other Environment
Miscellaneous Confirmation Miscellaneous Environmental Con-
Firmations

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible