This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1055-1MA00-7BA2

6AG1055-1MA00-7BA2 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1055-1MA00-7BA2 Siemens

6AG1055-1MA00-7BA2 Siemens - SIPLUS LOGO! AM2 based on 6ED1055-1MA00-0BA2 with conformal coating, -40…+70 °C, start up -25 °C, expansion module, PS/: 12/24 V DC, 2 AI, 0-10 V or 0/4-20 mA for LOGO! 8

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£251.07 Exc. VAT
£301.28 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1055-1MA00-7BA2
Product Description SIPLUS LOGO! AM2 based on 6ED1055-1MA00-0BA2 with conformal coating, -40…+70 °C, start up -25 °C, expansion module, PS/: 12/24 V DC, 2 AI, 0-10 V or 0/4-20 mA for LOGO! 8
Product family SIPLUS LOGO! expansion modules
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,133 Kg
Packaging Dimension 7,00 x 9,50 x 5,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618064211
UPC 804766488290
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4601
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 22.07.2017
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc)
12 V Dc Yes; 10.8 V Dc To 28.8 V Dc
24 V Dc Yes; 10.8 V Dc To 28.8 V Dc
Input Current
Current Consumption, Typ. 30 Ma

Analog Inputs

Number Of Analog Inputs 2
Input Ranges
Voltage Yes
Current Yes
Resistance Thermometer No
Input Ranges (Rated Values), Voltages
0 To +10 V Yes
Input Ranges (Rated Values), Currents
0 To 20 Ma Yes; 0 Ma Or 4 Ma To 20 Ma
Input Ranges (Rated Values), Resistance Thermometer
Pt 100 No
Emc
Emission Of Radio Interference Acc. To En 55 011
Limit Class B, For Use In Residential Areas Yes
Degree And Class Of Protection
Ip Degree Of Protection Ip20
Standards, Approvals, Certificates
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 16.5 Kg
— Global Warming Potential, (During Production) [Co2
Eq]3.22 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]13.4 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.124 Kg

Ambient Temperature During Operation

Min. -40 °C; = Tmin; Startup @ -25 °C
Max. 70 °C; = Tmax
At Cold Restart, Min. -25 °C; Incl. Condensation / Frost Permitted (No Commissioning Under
Condensation Conditions)
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation / Frost (No Commissioning In Bedewed State),
Horizontal Installation
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A

Dimensions

Width 35.5 Mm
Height 90 Mm
Depth 58 Mm

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible