This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1134-4MB02-2AB0

6AG1134-4MB02-2AB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1134-4MB02-2AB0 Siemens

6AG1134-4MB02-2AB0 Siemens - SIPLUS ET 200S EM 2 AE I HF based on 6ES7134-4MB02-0AB0 with conformal coating, -25…+70 °C, electronic module 15 mm overall width, cycle time per module: 0.5 ms, +/-20 mA; 15 bit+sign, 4.. 20 mA; 15 bit, operational limit +/-0.1% with SF LED (group fault)

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1134-4MB02-2AB0
Product Description SIPLUS ET 200S EM 2 AE I HF based on 6ES7134-4MB02-0AB0 with conformal coating, -25…+70 °C, electronic module 15 mm overall width, cycle time per module: 0.5 ms, +/-20 mA; 15 bit+sign, 4.. 20 mA; 15 bit, operational limit +/-0.1% with SF LED (group fault)
Product family Not available
Product Lifecycle (PLM) PM410:Product cancellation
PLM Effective Date Product is cancelled since: 01.10.2023
Notes This product is a Spare Part, please visit the Spares & Service section for more information If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : N / AL : N
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,045 Kg
Packaging Dimension 6,20 x 9,00 x 2,20
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948551028
UPC 040892657364
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4398
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.01.2012
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

Isochronous Mode Yes

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Reverse Polarity Protection Yes
Input Current
From Load Voltage L+ (Without Load), Max. 48 Ma
From Backplane Bus 3.3 V Dc, Max. 10 Ma
Output Voltage / Header
Supply Voltage Of The Transmitters / Header
Present Yes
Short-Circuit Proof Yes
Power Loss
Power Loss , Typ. 1.2 W
Address Area
Address Space Per Module
Address Space Per Module, Max. 4 Byte

Analog Inputs

Number Of Analog Inputs 2
Permissible Input Current For Current Input (Destruction Limit),
Max.50 Ma
Cycle Time (All Channels) Max. 0.5 Ms; 0.5 Ms For 2 Channels Without Noise Suppression, 18 / 21 Ms Per
Channel With Noise Suppression
Input Ranges (Rated Values), Currents
-20 Ma To +20 Ma Yes
4 Ma To 20 Ma Yes
Cable Length
Shielded, Max. 200 M
Analog Value Generation For The Inputs
Measurement Principle Sigma Delta
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 16 Bit
Integration Time, Parameterizable Yes
Interference Voltage Suppression For Interference
Frequency F1 In Hz60 / 50 Hz / No
Conversion Time (Per Channel) 0.04 Ms; Without Noise Suppression 17/20 Ms Per Channel With Error
Smoothing Of Measured Values
Parameterizable Yes; In 4 Stages: 1X, 4X, 16X, 32X Cycle Time
Step: None Yes; 1X
Step: Low Yes; 4X
Step: Medium Yes; 16X
Step: High Yes; 32X
Errors/Accuracies
Operation Al Error Limit In Overall Temperature Range
Current, Relative To Input Range, (+/-) 0.1 %; 0.2% Without Interference Frequency Suppression
Basic Error Limit (Operational Limit At 25 °C)
Current, Relative To Input Range, (+/-) 0.05 %; 0.1% Without Interference Frequency Suppression
Interrupts/Diagnostics/Status Information
Alarms
Hardware Interrupt Yes
Diagnoses
Wire-Break Yes; Measuring Range 4 To 20 Ma Only
Group Error Yes
Overflow/Underflow Yes
Diagnostics Indication Led
Group Error Sf (Red) Yes
Parameter
Remark 12 Bytes, 4 Bytes In Compatibility Mode
Diagnostics Wire Break Disable / Enable
Group Diagnostics Disable / Enable
Overflow/Underflow Disable / Enable
Potential Separation
Potential Separation Analog Inputs
Between The Channels No; However, Increased Permissible Potential Difference Between The Inputs.
Between The Channels And Backplane Bus Yes
Between The Channels And Load Voltage L+ Yes
Standards, Approvals, Certificates
Ce Mark Yes

Ambient Temperature During Operation

Min. -25 °C; = Tmin
Max. 70 °C; = Tmax
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost Permitted (No Commissioning In Bedewed
State)
Resistance
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental * The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04During Operation!

Dimensions

Width 15 Mm
Height 81 Mm
Depth 52 Mm
Weight S
Weight , Approx. 45 G