Description for 6AG1136-6AA00-2CA1 Siemens

6AG1136-6AA00-2CA1 Siemens - SIPLUS ET 200SP F-AI 4xI 2-/4-wire HF based on 6ES7136-6AA00-0CA1 with conformal coating, -30…+60 °C, fail-safe analog inputs up to PL e (ISO 13849) up to SIL 3 (IEC 61508)

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1136-6AA00-2CA1
Product Description SIPLUS ET 200SP F-AI 4xI 2-/4-wire HF based on 6ES7136-6AA00-0CA1 with conformal coating, -30…+60 °C, fail-safe analog inputs up to PL e (ISO 13849) up to SIL 3 (IEC 61508)
Product family SIPLUS analog F-input modules
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,066 Kg
Packaging Dimension 7,00 x 7,80 x 2,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618095406
UPC 195125026001
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4257
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 04.04.2018
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version See Entry Id: 109746275
Cir - Configuration In Run
Reparameterization Possible In Run No
Calibration Possible In Run No

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Input Current
Current Consumption (Rated Value) 0.38 A
Current Consumption, Max. 0.4 A
Encoder Supply
24 V Encoder Supply
24 V Yes; Min. L+ (-1.5 V)
Short-Circuit Protection Yes
Output Current, Max. 300 Ma; Total Current Of All Encoders/Channels
Power
Power Available From The Backplane Bus 70 Mw
Power Loss
Power Loss , Typ. 2 W
Address Area
Address Space Per Module
Inputs 14 Byte; S7-300/400F Cpu, 13 Byte
Outputs 5 Byte; S7-300/400F Cpu, 4 Byte
Hardware Configuration
Automatic Encoding
Electronic Coding Element Type F Yes

Analog Inputs

Number Of Analog Inputs 4
For Current Measurement 4
Permissible Input Current For Current Input (Destruction Limit),
Max.35 Ma
Input Ranges (Rated Values), Currents
0 To 20 Ma Yes
— Input Resistance (0 To 20 Ma) 125 Ω
4 Ma To 20 Ma Yes
— Input Resistance (4 Ma To 20 Ma) 125 Ω
Cable Length
Shielded, Max. 1 000 M
Analog Value Generation For The Inputs
Measurement Principle Sigma Delta
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 16 Bit
Integration Time, Parameterizable Yes
Integration Time (Ms) 20 / 16,667
Interference Voltage Suppression For Interference
Frequency F1 In Hz50 / 60 Hz
Smoothing Of Measured Values
Number Of Smoothing Levels 7
Parameterizable Yes
Step: None Yes; 1X Conversion Cycle Time
Step: Low Yes; 2X / 4X Conversion Cycle Time
Step: Medium Yes; 8X / 16X Conversion Cycle Time
Step: High Yes; 32X / 64X Conversion Cycle Time
Encoder
Connection Of Signal Encoders
For Current Measurement As 2-Wire Transducer Yes
— Burden Of 2-Wire Transmitter, Max. 650 Ω
For Current Measurement As 4-Wire Transducer Yes
Errors/Accuracies
Linearity Error (Relative To Input Range), (+/-) 0.1 %
Temperature Error (Relative To Input Range), (+/-) 0.023 %/K
Repeat Accuracy In Steady State At 25 °C (Relative To Input
Range), (+/-)0.1 %
Operation Al Error Limit In Overall Temperature Range
Current, Relative To Input Range, (+/-) 2.6 %
Basic Error Limit (Operational Limit At 25 °C)
Current, Relative To Input Range, (+/-) 0.1 %
Interference Voltage Suppression For F = N X (F1 +/- 1 %), F1 = Interference Frequency
Series Mode Interference (Peak Value Of Interference <
Rated Value Of Input Range), Min.40 Db
Common Mode Interference, Min. 70 Db
Interrupts/Diagnostics/Status Information
Alarms
Diagnostic Alarm Yes
Limit Value Alarm Yes
Diagnoses
Monitoring The Supply Voltage Yes
Wire-Break Yes; Measuring Range 4 To 20 Ma Only
Short-Circuit Yes
Diagnostics Indication Led
Run Led Yes; Green Led
Error Led Yes; Red Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Pwr Led
Channel Status Display Yes; Green Led
For Channel Diagnostics Yes; Red Led
For Module Diagnostics Yes; Green/Red Led
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsyes
Permissible Potential Difference
Between The Inputs (Ucm) 10 Vpp
Isolation
Isolation Tested With 707 V Dc (Type Test)
Standards, Approvals, Certificates
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 88.3 Kg
— Global Warming Potential, (During Production) [Co2
Eq]13.1 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]76.6 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-1.37 Kg
Highest Safety Class Achievable In Safety Mode
Performance Level According To Iso 13849-1 Ple
Category According To Iso 13849-1 Cat. 4
Sil Acc. To Iec 61508 Sil 3
Probability Of Failure (For Service Life Of 20 Years And Repair Time Of 100 Hours)
— Low Demand Mode: Pfdavg In Accordance With
Sil3< 5.00E-05
— High Demand/Continuous Mode: Pfh In Accordance
With Sil3< 1.00E-09 1/H

Ambient Temperature During Operation

Horizontal Installation, Min. -30 °C; = Tmin (Incl. Condensation/Frost)
Horizontal Installation, Max. 60 °C; = Tmax; +70 °C With Spacing Modules (6Ag1193-6Bn00-7Ba0) Or
Configured Slots To The Left And Right Of The Module
Vertical Installation, Min. -30 °C; = Tmin
Vertical Installation, Max. 50 °C; = Tmax
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 4 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Restrictions For Installation Altitudes > 2 000 M, See Entry Id: 109771992
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation / Frost (No Commissioning In Bedewed State),
Horizontal Installation
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-3Yes; Class 3M8 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Use On Land Craft, Rail Vehicles And Special-Purpose Vehicles
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-5Yes; Class 5M2 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
— Against Mechanical Environmental Conditions In
Agriculture Acc. To Iso 15003Yes; Level 1 (Location Le) Using The Siplus Mounting Kit Et 200Sp
(6Ag1193-6Aa00-0Aa0)
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold, Fungal And Dry Rot Spores (Excluding Fauna)
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
— Against Mechanical Environmental Conditions Acc. Yes; Class 6M4 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
To En 60721-3-6 0Aa0)
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A

Dimensions

Width 15 Mm
Height 73 Mm
Depth 58 Mm
Weight S
Weight , Approx. 48 G