Description for 6AG1136-6BA01-2CA0 Siemens

6AG1136-6BA01-2CA0 Siemens - SIPLUS ET 200SP F-DI 4/8x24 V DC HF based on 6ES7136-6BA01-0CA0 with conformal coating, -40…+60 °C, fail-safe digital inputs up to PL e (ISO 13849-1), SIL3 (IEC 61508)

Extended Description for 6AG1136-6BA01-2CA0 Siemens

6AG1136-6BA01-2CA0 Siemens - SIPLUS ET 200SP F-DI 4/8x24 V DC HF based on 6ES7136-6BA01-0CA0 with conformal coating, -40…+60 °C, fail-safe digital inputs up to PL e (ISO 13849-1), SIL3 (IEC 61508)

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1136-6BA01-2CA0
Product Description SIPLUS ET 200SP F-DI 4/8x24 V DC HF based on 6ES7136-6BA01-0CA0 with conformal coating, -40…+60 °C, fail-safe digital inputs up to PL e (ISO 13849-1), SIL3 (IEC 61508)
Product family SIPLUS digital F-input modules
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 65 Day/Days
Net Weight (kg) 0,061 Kg
Packaging Dimension 6,90 x 7,50 x 3,20
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618124816
UPC 195125313798
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4257
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 12.08.2021
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Reach Information There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern. We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version See Entry Id: 109746275; Simatic Safety V17 With Hsp 0360 Or Higher
Step 7 Configurable/Integrated From Version As 6Es7136-6Ba00-0Ca0
Cir - Configuration In Run
Reparameterization Possible In Run No

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Power Supply According To Nec Class 2 Required No
Input Current
Current Consumption, Max. 40 Ma; Without Load
Encoder Supply
Number Of Outputs 8
24 V Encoder Supply
24 V Yes; Min. L+ (-1.5 V)
Short-Circuit Protection Yes; Electronic (Response Threshold 0.7 A To 1.8 A)
Output Current Per Channel, Max. 300 Ma
Output Current Per Module, Max. 800 Ma; Total Current Of All Encoders
Power Loss
Power Loss , Typ. 2 W
Address Area
Address Space Per Module
Inputs 7 Byte; S7-300/400F Cpu, 6 Byte
Outputs 5 Byte; S7-300/400F Cpu, 4 Byte
Hardware Configuration
Automatic Encoding Yes
Electronic Coding Element Type F Yes
Digital Inputs
Number Of Digital Inputs 8
Source/Sink Input Yes; P-Reading
Input Characteristic Curve In Accordance With Iec 61131, Type 1 Yes
Input Voltage
Rated Value (Dc) 24 V
For Signal "0" -30 To +5 V
For Signal "1" +15 To +30 V
Input Current
For Signal "1", Typ. 3.7 Ma
Input Delay (For Rated Value Of Input Voltage)
For Standard Inputs
— Parameterizable Yes
— At "0" To "1", Min. 0.4 Ms
— At "0" To "1", Max. 20 Ms
— At "1" To "0", Min. 0.4 Ms
— At "1" To "0", Max. 20 Ms
For Technological Functions
— Parameterizable No
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 500 M
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes
Alarms
Diagnostic Alarm Yes
Hardware Interrupt No
Diagnostics Indication Led
Run Led Yes; Green Led
Error Led Yes; Red Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Pwr Led
Channel Status Display Yes; Green Led
For Channel Diagnostics Yes; Red Led
For Module Diagnostics Yes; Green/Red Diag Led
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsno
Isolation
Isolation Tested With 707 V Dc (Type Test)
Standards, Approvals, Certificates
Suitable For Safety Functions Yes
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 52 Kg
— Global Warming Potential, (During Production) [Co2
Eq]6.8 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]45.8 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.628 Kg
Highest Safety Class Achievable In Safety Mode
Performance Level According To Iso 13849-1 Ple
Category According To Iso 13849-1 Cat. 4
Sil Acc. To Iec 61508 Sil 3
Probability Of Failure (For Service Life Of 20 Years And Repair Time Of 100 Hours)
— Low Demand Mode: Pfdavg In Accordance With
Sil3< 2.00E-05
— High Demand/Continuous Mode: Pfh In Accordance
With Sil3< 1.00E-09 1/H

Ambient Temperature During Operation

Horizontal Installation, Min. -40 °C; = Tmin (Incl. Condensation/Frost)
Horizontal Installation, Max. 60 °C; = Tmax; +70 °C With Spacing Modules (6Ag1193-6Bn00-7Ba0) Or
Configured Slots To The Left And Right Of The Module
Vertical Installation, Min. -40 °C; = Tmin
Vertical Installation, Max. 50 °C; = Tmax
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 4 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Restrictions For Installation Altitudes > 2 000 M, See Entry Id: 109771992
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation / Frost (No Commissioning In Bedewed State),
Horizontal Installation
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-3Yes; Class 3M8 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Use On Land Craft, Rail Vehicles And Special-Purpose Vehicles
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-5Yes; Class 5M2 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
— Against Mechanical Environmental Conditions In
Agriculture Acc. To Iso 15003Yes; Level 1 (Location Le) Using The Siplus Mounting Kit Et 200Sp
(6Ag1193-6Aa00-0Aa0)
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold, Fungal And Dry Rot Spores (Excluding Fauna)
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-6Yes; Class 6M4 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A

Dimensions

Width 15 Mm
Height 73 Mm
Depth 58 Mm
Weight S
Weight , Approx. 29 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible