This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1138-6CG00-2BA0

6AG1138-6CG00-2BA0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1138-6CG00-2BA0 Siemens

6AG1138-6CG00-2BA0 Siemens - SIPLUS ET 200SP TM timer DIDQ 10x24V based on 6ES7138-6CG00-0BA0 with conformal coating, -40…+60 °C, time-controlled digital inputs and outputs 4 DI, 6 DQ with time stamp count, PWM, oversampling

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£458.09 Exc. VAT
£549.71 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1138-6CG00-2BA0
Product Description SIPLUS ET 200SP TM timer DIDQ 10x24V based on 6ES7138-6CG00-0BA0 with conformal coating, -40…+60 °C, time-controlled digital inputs and outputs 4 DI, 6 DQ with time stamp count, PWM, oversampling
Product family SIPLUS TM Timer DIDQ 10x24 V time-based IO module
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : EAR99H
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,059 Kg
Packaging Dimension 6,80 x 7,70 x 2,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618077907
UPC 195125031869
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4257
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 09.11.2016
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 4,4'-isopropylidenediphenol (Bisphenol A, BPA) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M 0
Isochronous Mode Yes
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version See Entry Id: 109746275

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes; Against Destruction
Input Current
Current Consumption, Max. 50 Ma; Without Load
Encoder Supply
Number Of Outputs 1
24 V Encoder Supply
24 V Yes; L+ (-0.8 V)
Short-Circuit Protection Yes
Output Current, Max. 500 Ma; Observe Derating
Power Loss
Power Loss , Typ. 1.5 W
Address Area
Address Space Per Module
Inputs 26 Byte
Outputs 32 Byte
Digital Inputs
Number Of Digital Inputs 4
Digital Inputs, Parameterizable Yes
Input Characteristic Curve In Accordance With Iec 61131, Type 3 Yes
Digital Input Functions, Parameterizable
Digital Input With Time Stamp Yes
— Number, Max. 4
Counter Yes
— Number, Max. 3
Counter For Incremental Encoder Yes
— Number, Max. 1
Digital Input With Oversampling Yes
— Number, Max. 4
Hw Enable For Digital Input Yes
— Number, Max. 1
Hw Enable For Digital Output Yes
— Number, Max. 3
Input Voltage
Type Of Input Voltage Dc
Rated Value (Dc) 24 V
For Signal "0" -30 To +5 V
For Signal "1" +11 To +30V
Permissible Voltage At Input, Min. -30 V
Permissible Voltage At Input, Max. 30 V
Input Current
For Signal "1", Typ. 2.5 Ma
Input Delay (For Rated Value Of Input Voltage)
Minimum Pulse Width For Program Reactions 3 Μs For Parameterization "None"
For Standard Inputs
— Parameterizable Yes; None / 0.05 / 0.1 / 0.4 / 0.8 Ms
— At "0" To "1", Min. 4 Μs
— At "1" To "0", Min. 4 Μs
Cable Length
Shielded, Max. 1 000 M; Depending On Sensor, Cable Quality And Rate Of Change
Unshielded, Max. 600 M; Depending On Sensor, Cable Quality And Rate Of Change
Digital Outputs
Type Of Digital Output Transistor
Number Of Digital Outputs 6
Current-Sinking Yes; With High Speed Output
Current-Sourcing Yes
Digital Outputs, Parameterizable Yes
Short-Circuit Protection Yes; Electronic/Thermal
Response Threshold, Typ. 1.7 A With Standard Output, 0.5 A With High Speed Output
Limitation Of Inductive Shutdown Voltage To -0.8 V
Digital Output Functions, Parameterizable
Digital Output With Time Stamp Yes
— Number, Max. 6
Pwm Output Yes
— Number, Max. 6
Digital Output With Oversampling Yes
— Number, Max. 6
Switching Capacity Of The Outputs
With Resistive Load, Max. 0.5 A; 0.1 A With High Speed Output
On Lamp Load, Max. 5 W; 1 W With High Speed Output
Load Resistance Range
Lower Limit 48 Ω; 240 Ohm With High Speed Output
Upper Limit 12 Kω
Output Voltage
Type Of Output Voltage Dc
For Signal "0", Max. 1 V; With High Speed Output
For Signal "1", Min. 23.2 V; L+ (-0.8 V)
Output Current
For Signal "1" Rated Value 0.5 A; 0.1 A With High Speed Output, Observe Derating
For Signal "1" Permissible Range, Max. 0.6 A; 0.12 A With High Speed Output, Observe Derating
For Signal "1" Minimum Load Current 2 Ma
For Signal "0" Residual Current, Max. 0.5 Ma
Output Delay With Resistive Load
"0" To "1", Max. 1 Μs; With High Speed Output, 5 Μs With Standard Output
"1" To "0", Max. 1 Μs; With High Speed Output, 6 Μs With Standard Output
Switching Frequency
With Resistive Load, Max. 10 Khz
On Lamp Load, Max. 10 Hz
Total Current Of The Outputs
Current Per Module, Max. 3.5 A; Observe Derating
Cable Length
Shielded, Max. 1 000 M; Depending On Load And Cable Quality
Unshielded, Max. 600 M; Depending On Load And Cable Quality
Encoder
Connectable Encoders
Incremental Encoder (Asymmetrical) Yes
24 V Initiator Yes
2-Wire Sensor Yes
— Permissible Quiescent Current (2-Wire Sensor), Max. 1.5 Ma
Encoder Signals, Incremental Encoder (Asymmetrical)
Input Voltage 24 V
Input Frequency, Max. 50 Khz
Counting Frequency, Max. 200 Khz; With Quadruple Evaluation
Cable Length, Shielded, Max. 600 M; Depending On Input Frequency, Encoder And Cable Quality; Max. 200 M
At 50 Khz
Incremental Encoder With A/B Tracks, 90° Phase Offset Yes
Pulse Encoder Yes
Interface Types
Input Characteristic Curve In Accordance With Iec 61131,
Type 3Yes
Isochronous Mode
Bus Cycle Time (Tdp), Min. 375 Μs
Jitter, Max. 1 Μs
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes
Substitute Values Connectable Yes
Alarms
Diagnostic Alarm Yes
Diagnoses
Monitoring The Supply Voltage Yes
Short-Circuit Yes
Diagnostics Indication Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Pwr Led
Channel Status Display Yes
For Module Diagnostics Yes; Green/Red Diag Led
Integrated Functions
Counter Yes
Number Of Counters 3
Counting Frequency, Max. 200 Khz; With Quadruple Evaluation
Counting Functions
Continuous Counting Yes
Potential Separation
Potential Separation Channels
Between The Channels And Backplane Bus Yes
Standards, Approvals, Certificates
Suitable For Safety Functions No

Ambient Temperature During Operation

Horizontal Installation, Min. -40 °C; = Tmin (Incl. Condensation/Frost)
Horizontal Installation, Max. 60 °C; = Tmax; +70 °C With Spacing Modules (6Ag1193-6Bn00-7Ba0) Or
Configured Slots To The Left And Right Of The Module
Vertical Installation, Min. -40 °C; = Tmin (Incl. Condensation/Frost)
Vertical Installation, Max. 50 °C; = Tmax; See Derating Basedon (E.G. Manual)
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068- 100 %; Rh Incl. Condensation / Frost (No Commissioning In Bedewed State),
2-38, Max. Horizontal Installation
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-3Yes; Class 3M8 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-6Yes; Class 6M4 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A
Decentralized Operation
To Simatic S7-1500 Yes

Dimensions

Width 15 Mm
Height 73 Mm
Depth 58 Mm
Weight S
Weight , Approx. 45 G

Documentation