This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1193-6BP00-7BU0

6AG1193-6BP00-7BU0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1193-6BP00-7BU0 Siemens

6AG1193-6BP00-7BU0 Siemens - SIPLUS ET 200SP BU20-P16+A0+2B based on 6ES7193-6BP00-0BU0 with conformal coating, -40…+70 °C, BU type U0, push-in terminals, without AUX terminals, bridged to the left, WxH: 20 mm x 117 mm

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£67.19 Exc. VAT
£80.63 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1193-6BP00-7BU0
Product Description SIPLUS ET 200SP BU20-P16+A0+2B based on 6ES7193-6BP00-0BU0 with conformal coating, -40…+70 °C, BU type U0, push-in terminals, without AUX terminals, bridged to the left, WxH: 20 mm x 117 mm
Product family SIPLUS BaseUnits
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 60 Day/Days
Net Weight (kg) 0,061 Kg
Packaging Dimension 4,00 x 12,50 x 3,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618099336
UPC 804766901997
Commodity Code 85366990
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4257
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 09.02.2018
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc) 120 V
For P1 And P2 Bus 120 V
For Aux Bus 120 V
Rated Value (Ac) 240 V; 400 V (L1 - L2 - L3); 240 V (L1, N)
For P1 And P2 Bus 240 V
For Aux Bus 240 V
For Process Terminals 240 V
External Protection For Power Supply Lines Yes
Mains Filter
Integrated No
Current Carrying Capacity
Up To 60 °C, Max. 10 A
Up To 70 °C, Max. 10 A
For P1 And P2 Bus, Max. 10 A
For Aux Bus, Max. 10 A
For Process Terminals, Max. 10 A
Hardware Configuration
Automatic Encoding Yes
Formation Of Potential Groups
New Potential Group No
Potential Group Continued From The Left Yes
Slots
Number Of Slots 1
Potential Separation
Between Backplane Bus And Supply Voltage Yes
Between The Potential Groups No
Isolation
Isolation Tested With 2 545 V Dc/2 S (Routine Test)
Standards, Approvals, Certificates
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 0.873 Kg
— Global Warming Potential, (During Production) [Co2
Eq]0.866 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]0 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.0011 Kg

Ambient Temperature During Operation

Horizontal Installation, Min. -40 °C; = Tmin (Incl. Condensation/Frost)
Horizontal Installation, Max. 70 °C; = Tmax
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 2 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-3Yes; Class 3M8 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold, Fungal And Dry Rot Spores (Excluding Fauna)
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-6Yes; Class 6M4 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A
Connection Method
Terminals
Terminal Type Push-In Terminal
Conductor Cross-Section, Min. 0.14 Mm²; 0.2 Mm² Without Wire End Ferrule
Conductor Cross-Section, Max. 2.5 Mm²; 1.5 Mm² With Wire End Ferrule
Number Of Process Terminals To I/O Module 16
Number Of Terminals To Aux Bus 0
Number Of Add-On Terminals 0
Number Of Terminals With Connection To P1 And P2 Bus 2

Dimensions

Width 20 Mm
Height 117 Mm
Depth 35 Mm
Weight S
Weight , Approx. 50 G

Documentation