This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1321-7TH00-4AB0

6AG1321-7TH00-4AB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1321-7TH00-4AB0 Siemens

6AG1321-7TH00-4AB0 Siemens - SIPLUS PCS 7 SM 321 16DI based on 6ES7321-7TH00-0AB0 with conformal coating, 0…+60 °C, digital input 16 DI; 24 V DC, 1x 40-pole, diagnostics-capable, for contacts (wired/ not wired), NAMUR encoder, 3/4-wire BERO, with chatter monitoring; pulse stretching, open-circuit detection connection IM 153-2 required

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£1,604.30 Exc. VAT
£1,925.16 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1321-7TH00-4AB0
Product Description SIPLUS PCS 7 SM 321 16DI based on 6ES7321-7TH00-0AB0 with conformal coating, 0…+60 °C, digital input 16 DI; 24 V DC, 1x 40-pole, diagnostics-capable, for contacts (wired/ not wired), NAMUR encoder, 3/4-wire BERO, with chatter monitoring; pulse stretching, open-circuit detection connection IM 153-2 required
Product family SIPLUS S7-300 SM 321
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 19.12.2023

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,388 Kg
Packaging Dimension 15,00 x 13,00 x 5,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948489406
UPC Not available
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group X0SN
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Product is not RoHS-compliant
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Reverse Polarity Protection Yes
Input Current
From Load Voltage L+ (Without Load), Max. 100 Ma
From Backplane Bus 5 V Dc, Max. 100 Ma
Encoder Supply
Number Of Outputs 4
Type Of Output Voltage 1Vs1/2Vs1: 18 V, 1Vs2/2Vs2: 8.2 V
Short-Circuit Protection Yes; Electronic
Additional (Redundant) Feed No
Output Current
Rated Value 190 Ma; At 18V: 190Ma, At 8.2V: 60Ma
Permissible Range, Upper Limit Up To 60 Degree: At 18V: 0 To 110Ma, At 8.2V: 0 To 60Ma; Up To 40 Degree: At
18V: 0 To 190Ma, At 8.2V: 0 To 60Ma
Power Loss
Power Loss , Typ. 11 W
Digital Inputs
Number Of Digital Inputs 16
Input Characteristic Curve In Accordance With Iec 61131, Type 1 No
Input Characteristic Curve In Accordance With Iec 61131, Type 2 Yes
Number Of Simultaneously Controllable Inputs
Horizontal Installation
— Up To 60 °C, Max. 16
Vertical Installation
— Up To 40 °C, Max. 16
Input Voltage
Type Of Input Voltage Dc
Rated Value (Dc) 8.2 V; 8.2V/18V
Input Current
For Signal "0", Min. 0.35 Ma
For Signal "0", Max. (Permissible Quiescent Current) 1.2 Ma
For Signal "1", Typ. 10 Ma; For Namur: 2.1 To 7 Ma, For 10K Ohm/47K Ohm Contact: Typical 10Ma,
For 4 Wire Beros: Typical 10 Ma
Input Delay (For Rated Value Of Input Voltage)
For Standard Inputs
— At "0" To "1", Min. 2.5 Ms
— At "0" To "1", Max. 3.5 Ms
— At "1" To "0", Min. 2.5 Ms
— At "1" To "0", Max. 3.5 Ms
Cable Length
Shielded, Max. 400 M; Max. 200M With 8.2 V Sensor, Max. 400M With 18 V Sensor
Unshielded, Max. Not Permitted
Interrupts/Diagnostics/Status Information
Alarms Yes
Diagnostics Function Yes
Alarms
Diagnostic Alarm Yes
Hardware Interrupt Yes
Diagnoses
Diagnostic Information Readable Yes
Wire-Break Yes
Diagnostics Indication Led
Group Error Sf (Red) Yes
Status Indicator Digital Input (Green) Yes
Encoder Supply Vs (Green) Yes
Potential Separation
Potential Separation Digital Inputs
Between The Channels Yes
Between The Channels, In Groups Of 8
Between The Channels And Backplane Bus Yes
Isolation
Isolation Tested With 600 V Dc
Standards, Approvals, Certificates
Ce Mark Yes
Ul Approval Yes; File E239877
Rcm (Formerly C-Tick) Yes
Kc Approval Yes
Eac (Formerly Gost-R) Yes

Ambient Temperature During Operation

Min. 0 °C
Max. 60 °C
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Connection Method
Required Front Connector 40-Pin

Dimensions

Width 40 Mm
Height 125 Mm
Depth 120 Mm