Description for 6AG1331-7SF00-4AB0 Siemens

6AG1331-7SF00-4AB0 Siemens - SIPLUS S7-300 SM 331 AI 20-pole based on 6ES7331-7SF00-0AB0 with conformal coating, 0…+60 °C, without PTB approval

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1331-7SF00-4AB0
Product Description SIPLUS S7-300 SM 331 AI 20-pole based on 6ES7331-7SF00-0AB0 with conformal coating, 0…+60 °C, without PTB approval
Product family Not available
Product Lifecycle (PLM) PM410:Product cancellation
PLM Effective Date Product is cancelled since: 08.05.2024
Notes This product is a Spare Part, please visit the Spares & Service section for more information If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : N / AL : N
Estimated dispatch time (Working Days) 65 Day/Days
Net Weight (kg) 0,256 Kg
Packaging Dimension 13,20 x 15,20 x 5,10
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4025515137719
UPC Not available
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4398
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Product is not RoHS-compliant
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Input Current
From Backplane Bus 5 V Dc, Max. 120 Ma
Power Loss
Power Loss , Typ. 0.6 W

Analog Inputs

Number Of Analog Inputs 8; 8X Thermocouples; 4X Rtd Thermoresistors
Input Ranges
Voltage Yes
Current No
Thermocouple Yes
Resistance Thermometer Yes
Resistance Yes
Input Ranges (Rated Values), Thermocouples
Type B Yes
— Input Resistance (Type B) 10 M Ω
Type E Yes
— Input Resistance (Type E) 10 M Ω
Type J Yes
— Input Resistance (Type J) 10 M Ω
Type K Yes
— Input Resistance (Type K) 10 M Ω
Type L Yes
— Input Resistance (Type L) 10 M Ω
Type N Yes
— Input Resistance (Type N) 10 M Ω
Type R Yes
— Input Resistance (Type R) 10 M Ω
Type S Yes
— Input Resistance (Type S) 10 M Ω
Type T Yes
— Input Resistance (Type T) 10 M Ω
Type U Yes
— Input Resistance (Type U) 10 M Ω
Input Ranges (Rated Values), Resistance Thermometer
Ni 100 Yes
— Input Resistance (Ni 100) 10 M Ω
Pt 100 Yes
— Input Resistance (Pt 100) 10 M Ω
Pt 200 Yes
— Input Resistance (Pt 200) 10 M Ω
Cable Length
Shielded, Max. 200 M; Tc: 50 M
Analog Value Generation For The Inputs
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 16 Bit; 10 Bit To 15 Bit + Sign
Integration Time, Parameterizable Yes; 2.5 To 100 Ms
Interference Voltage Suppression For Interference
Frequency F1 In Hz10 To 400 Hz
Encoder
Connection Of Signal Encoders
For Current Measurement As 2-Wire Transducer Yes
For Current Measurement As 4-Wire Transducer Yes
Errors/Accuracies
Operation Al Error Limit In Overall Temperature Range
Resistance Thermometer, Relative To Input Range, (+/-) 0.09 To 0.04%
Basic Error Limit (Operational Limit At 25 °C)
Resistance Thermometer, Relative To Input Range, (+/-) 0.1 %
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes
Diagnoses
Diagnostic Information Readable Yes
Overrange Yes
Wire-Break In Signal Transmitter Cable Yes
Short-Circuit Of The Signal Encoder Cable Yes
Diagnostics Indication Led
Group Error Sf (Red) Yes
Channel Fault Indicator F (Red) Yes
Ex(I) Characteristics
Module For Ex(I) Protection Yes
Maximum Values For Connecting Terminals For Gas Group Iic
Uo (No-Load Voltage), Max. 5.9 V
Io (Short-Circuit Current), Max. 28.8 Ma
Po (Power Output), Max. 41.4 Mw
Co (Permissible External Capacity), Max. 43 Μf
Lo (Permissible External Inductivity), Max. 40 Mh
Standards, Approvals, Certificates
Ce Mark Yes
Ul Approval Yes; File E239877
Rcm (Formerly C-Tick) Yes
Kc Approval Yes
Eac (Formerly Gost-R) Yes
Use In Hazardous Areas
Atex Certificate Kema 09 Atex 0077X
Railway Application
En 50155 No

Ambient Temperature During Operation

Min. 0 °C; = Tmin
Max. 60 °C; = Tmax
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax Ambient Air Temperature-Barometric Pressure-Altitude
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Connection Method
Required Front Connector 20-Pin

Dimensions

Width 40 Mm
Height 125 Mm
Depth 120 Mm
Weight S
Weight , Approx. 210 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible