This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1350-1AH03-2AY0

6AG1350-1AH03-2AY0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1350-1AH03-2AY0 Siemens

6AG1350-1AH03-2AY0 Siemens - ***spare part*** SIPLUS S7-300 FM350-1 based on 6ES7350-1AH03-0AE0 with conformal coating, -25…+60 °C, counter module FM 350-1 for S7-300, counter functions up to 500 kHz 1 channel for connection of 5 V and 24 V incremental encoders isochronous mode; measuring range types incl. configuration package on CD-ROM

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1350-1AH03-2AY0
Product Description ***spare part*** SIPLUS S7-300 FM350-1 based on 6ES7350-1AH03-0AE0 with conformal coating, -25…+60 °C, counter module FM 350-1 for S7-300, counter functions up to 500 kHz 1 channel for connection of 5 V and 24 V incremental encoders isochronous mode; measuring range types incl. configuration package on CD-ROM
Product family Not available
Product Lifecycle (PLM) PM410:Product cancellation
PLM Effective Date Product is cancelled since: 05.11.2020
Notes This product is a Spare Part, please visit the Spares & Service section for more information If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : N / AL : N
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,280 Kg
Packaging Dimension 12,90 x 15,30 x 5,10
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948411513
UPC 804766249044
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4398
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.09.2014
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Auxiliary Voltage 1L+, Load Voltage 2L+
Rated Value (Dc) 24 V; A Power Supply According To En 50155 Shall Be Used
Permissible Range, Lower Limit (Dc) 20.4 V; Dynamic 18.5 V
Permissible Range, Upper Limit (Dc) 28.8 V; Dynamic 30.2 V
Input Current
From Load Voltage 1L+ (Without Load), Max. 40 Ma
From Backplane Bus 5 V Dc, Max. 160 Ma
Encoder Supply
5 V Encoder Supply
5 V Yes; 5.2 V ±2 %
Output Current, Max. 300 Ma
24 V Encoder Supply
24 V Yes; 1L+ (-3 V)
Output Current, Max. 400 Ma
Power Loss
Power Loss , Typ. 4.5 W
Digital Inputs
Number Of Digital Inputs 3
Functions 1 For Gate Start, 1 For Gate Stop, 1 For Setting The Counter
Input Voltage
For Signal "0" -28.8 ... +5V
For Signal "1" +11 To +28.8V
Input Current
For Signal "1", Typ. 9 Ma
Digital Outputs
Number Of Digital Outputs 2
Short-Circuit Protection Yes; Clocked Electronically
Limitation Of Inductive Shutdown Voltage To 2L+ (-39 V)
Output Voltage
For Signal "0", Max. 3 V
For Signal "1", Min. 2L+ (-1,5 V)
Output Current
For Signal "1" Rated Value 0.5 A
For Signal "1" Permissible Range For 0 To 60 °C, Min. 5 Ma
For Signal "1" Permissible Range For 0 To 60 °C, Max. 0.6 A
Output Delay With Resistive Load
"0" To "1", Max. 300 Μs
Encoder
Connectable Encoders
Incremental Encoder (Symmetrical) Yes; With 2 Pulse Trains Offset By 90°
Incremental Encoder (Asymmetrical) Yes
24 V Initiator Yes
24 V Directional Element Yes; 1 Pulse Train, 1 Direction Level
Counter
Number Of Counter Inputs 1; 32 Bit Or ±31 Bit
Counter Input 5 V
Type Rs 422
Terminating Resistor 220 Ω
Differential Input Voltage 1,3 V
Counting Frequency, Max. 500 Khz
Counter Input 24 V
Input Voltage For Signal "0" -28.8 ... +5V
Input Voltage For Signal "1" +11 To +28.8V
Input Current For Signal "1", Typ. 9 Ma
Counting Frequency, Max. 200 Khz
Minimum Pulse Width 2.5 Μs
Potential Separation
Potential Separation Digital Inputs
Between The Channels And Backplane Bus Yes; Optocoupler
Potential Separation Digital Outputs
Between The Channels And Backplane Bus Yes; Optocoupler
Potential Separation Counter
Between The Channels And Backplane Bus Yes; Optocoupler
Isolation
Isolation Tested With 500 V
Standards, Approvals, Certificates
Ce Mark Yes
Ul Approval Yes; File E239877
Rcm (Formerly C-Tick) Yes
Kc Approval Yes
Eac (Formerly Gost-R) Yes
Railway Application
En 50155 Yes; Sections 4, 5 And 12; No Further Agreements Apply; T1, Category 1, Class
A/B, En 50155:2007

Ambient Temperature During Operation

Min. -25 °C; = Tmin
Max. 60 °C; = Tmax; The Rated Temperature Range Of -25 ... +55 °C (T1) Applies For
The Use On Railway Vehicles According To En50155
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Land Craft, Rail Vehicles And Special-Purpose Vehicles
— To Biologically Active Substances According To En
60721-3-5Yes; Class 5B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 5B3 On Request
— To Chemically Active Substances According To En
60721-3-5Yes; Class 5C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 50155 (St2); *
— To Mechanically Active Substances According To En
60721-3-5Yes; Class 5S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Connection Method
Required Front Connector 1X 20-Pin

Dimensions

Width 40 Mm
Height 125 Mm
Depth 120 Mm
Weight S
Weight , Approx. 250 G