This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1407-0KA02-7AA0

6AG1407-0KA02-7AA0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1407-0KA02-7AA0 Siemens

6AG1407-0KA02-7AA0 Siemens - SIPLUS S7-400 PS 407 10 A based on 6ES7407-0KA02-0AA0 with conformal coating, -25…+70 °C, 10 A, wide range, 120/230 V UC; 5 V DC/10 A

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£1,797.54 Exc. VAT
£2,157.05 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1407-0KA02-7AA0
Product Description SIPLUS S7-400 PS 407 10 A based on 6ES7407-0KA02-0AA0 with conformal coating, -25…+70 °C, 10 A, wide range, 120/230 V UC; 5 V DC/10 A
Product family SIPLUS S7-400 power supplies
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 1,343 Kg
Packaging Dimension 23,00 x 30,00 x 6,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948654705
UPC 804766337208
Commodity Code 85044095
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4656
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.09.2014
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc)
120 V Dc Yes
230 V Dc Yes
Rated Value (Ac)
120 V Ac Yes
230 V Ac Yes
Line Frequency
Rated Value 50 Hz Yes
Rated Value 60 Hz Yes
Permissible Range, Lower Limit 47 Hz
Permissible Range, Upper Limit 63 Hz
Mains Buffering
Mains/Voltage Failure Stored Energy Time 20 Ms
Mains Buffering According To Namur Recommendation Yes
Input Current
Rated Value At 120 V Dc 1 A
Rated Value At 230 V Dc 0.5 A
Rated Value At 120 V Ac 0.9 A
Rated Value At 230 V Ac 0.5 A
Inrush Current, Max. 63 A; Full Width At Half Maximum 1 Ms
Leakage Current, Max. 3.5 Ma
Output Voltage / Header
Type Of Output Voltage Dc
Rated Value (Dc)
5 V Dc Yes
24 V Dc Yes
Output Current
For Backplane Bus (5 V Dc), Max. 10 A; No Base Load Required
For Backplane Bus (24 V Dc), Max. 1 A; Idling-Proof
Short-Circuit Protection Yes
Power
Active Power Input, Typ. 95 W
Power Loss
Power Loss , Typ. 20 W
Battery
Backup Battery
Backup Battery (Optional) Yes; 0 °C To +60 °C: 2X Lithium Aa; 3.6 V/2.3 Ah // -25 °C To +70 °C And/Or 100
% Rh: 2X External Battery Box 6Ag1971-0Aa00-7Aa0 And 2X Mono Cell
Design D
Hardware Configuration
Slots
Required Slots 2
Potential Separation
Primary/Secondary Yes
Isolation
Overvoltage Category Ii
Emc
Compliance With Line Harmonic Distortion Limits
Compliance With Line Harmonic Distortion Acc. To Iec
61000-3-2, Iec 61000-3-3Yes
Degree And Class Of Protection
Equipment Protection Class I, With Protective Conductor

Ambient Temperature During Operation

Min. -25 °C; Using The External Battery Box Siplus 6Ag1971-0Aa00-7Aa0 For Buffer
Mode
Max. 70 °C; Using The External Battery Box Siplus 6Ag1971-0Aa00-7Aa0 For Buffer
Mode
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 2 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning If There Is Condensation).
In Buffer Mode, Use Battery Box Siplus 6Ag1971-0Aa00-7Aa0 For High
Humidity
Resistance
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A
Connection Method
Design Of Electrical Connection 3X 1.5 Mm², Solid Or Stranded Wire With End Sleeve, External Diameter 3 Mm To 9
Mm

Dimensions

Width 50 Mm
Height 290 Mm
Depth 217 Mm
Weight S
Weight , Approx. 1 200 G

Documentation