Description for 6AG1505-0KA00-7AB0 Siemens

6AG1505-0KA00-7AB0 Siemens - SIPLUS S7-1500 PS 1505 25W 24VD based on 6ES7505-0KA00-0AB0 with conformal coating, -40…+70 °C, start up -25 °C, system power supply supplies the backplane bus of the S7-1500 with operating voltage

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£370.22 Exc. VAT
£444.26 Inc. VAT

Product

Article Number (Market Facing Number) 6AG1505-0KA00-7AB0
Product Description SIPLUS S7-1500 PS 1505 25W 24VD based on 6ES7505-0KA00-0AB0 with conformal coating, -40…+70 °C, start up -25 °C, system power supply supplies the backplane bus of the S7-1500 with operating voltage
Product family SIPLUS system power supplies
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 60 Day/Days
Net Weight (kg) 0,363 Kg
Packaging Dimension 15,00 x 15,00 x 4,30
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948655962
UPC 887621829964
Commodity Code 85044095
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4657
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 25.02.2013
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 4,4'-isopropylidenediphenol (Bisphenol A, BPA) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc) 24 V; Selv
Permissible Range, Lower Limit (Dc) 19.2 V; Static 19.2 V, Dynamic 18.5 V
Permissible Range, Upper Limit (Dc) 28.8 V; Static 28.8 V, Dynamic 30.2 V
Reverse Polarity Protection Yes
Short-Circuit Protection Yes
Mains Buffering
Mains/Voltage Failure Stored Energy Time 20 Ms
Output Current
Short-Circuit Protection Yes
Power
Infeed Power To The Backplane Bus 25 W; > +60 °C Max. Power Input 12.5 W
Power Loss
Power Loss At Nominal Rating Conditions 6.2 W
Interrupts/Diagnostics/Status Information
Status Indicator Yes
Potential Separation
Primary/Secondary Yes; Electrical Isolation For Max. 60 V Ac/75 V Dc (Base Isolation)
Isolation
Isolation Tested With 707 V Dc (Type Test)
Emc
Interference Immunity Against Voltage Surge
Interference Immunity On Supply Lines Acc. To Iec 61000-
4-5Yes; ±1 Kv (Acc. To Iec 61000-4-5; 1995; Surge Symm.), ±2 Kv (Acc. To Iec
61000-4-5; 1995; Surge Asymm.), No External Protective Circuit Required
Degree And Class Of Protection
Ip Degree Of Protection Ip20
Equipment Protection Class Iii, With Protective Conductor

Ambient Temperature During Operation

Min. -40 °C; = Tmin (Incl. Condensation/Frost); Start-Up @ -25 °C
Max. 70 °C; = Tmax; For Vertical Mounting Position Tmax = +40 °C
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold And Fungal Spores (Excluding Fauna); Class 6B3 On
Request
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-6Yes; Class 6S3 Incl. Sand, Dust; *
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A

Dimensions

Width 35 Mm
Height 147 Mm
Depth 129 Mm
Weight S
Weight , Approx. 350 G