This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG1517-3HP00-4AB0

6AG1517-3HP00-4AB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG1517-3HP00-4AB0 Siemens

6AG1517-3HP00-4AB0 Siemens - SIPLUS S7-1500 CPU 1517H-3 PN based on 6ES7517-3HP00-0AB0 with conformal coating, 0…+60 °C, central processing unit with 2 MB work memory for program and 8 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd interface: PROFINET RT, 3rd interface: H-SYNC, SIMATIC Memory Card required

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG1517-3HP00-4AB0
Product Description SIPLUS S7-1500 CPU 1517H-3 PN based on 6ES7517-3HP00-0AB0 with conformal coating, 0…+60 °C, central processing unit with 2 MB work memory for program and 8 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd interface: PROFINET RT, 3rd interface: H-SYNC, SIMATIC Memory Card required
Product family SIPLUS CPU 1517H-3 PN
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 65 Day/Days
Net Weight (kg) 2,297 Kg
Packaging Dimension 1,00 x 1,00 x 1,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618102722
UPC 195125376014
Commodity Code 85371091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4657
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 31.10.2018
Product class B: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Mains Buffering
Mains/Voltage Failure Stored Energy Time 5 Ms
Input Current
Current Consumption (Rated Value) 1.5 A
Inrush Current, Max. 2.4 A; Rated Value
I²T 0.02 A²·S
Power Loss
Power Loss , Typ. 24 W
Memory
Number Of Slots For Simatic Memory Card 1
Simatic Memory Card Required Yes
Work Memory
Integrated (For Program) 2 Mbyte
Integrated (For Data) 8 Mbyte
Load Memory
Plug-In (Simatic Memory Card), Max. 32 Gbyte
Backup
Maintenance-Free Yes
Cpu Processing Times
For Bit Operations, Typ. 4 Ns
For Word Operations, Typ. 6 Ns
For Fixed Point Arithmetic, Typ. 6 Ns
For Floating Point Arithmetic, Typ. 24 Ns
Cpu-Blocks
Number Of Elements (Total) 12 000; Blocks (Ob, Fb, Fc, Db) And Udts
Db
Number Range Number Range: 1 To 59 999
Size, Max. 8 Mbyte; For Non-Optimized Block Accesses, The Max. Size Of The Db Is 64 Kb
Fb
Number Range 0 ... 65 535
Size, Max. 1 Mbyte
Fc
Number Range 0 ... 65 535
Size, Max. 1 Mbyte
Ob
Size, Max. 1 Mbyte
Number Of Free Cycle Obs 100
Number Of Time Alarm Obs 20
Number Of Delay Alarm Obs 20
Number Of Cyclic Interrupt Obs 20
Number Of Process Alarm Obs 50
Number Of Startup Obs 100
Number Of Asynchronous Error Obs 4
Number Of Synchronous Error Obs 2
Number Of Diagnostic Alarm Obs 1
Nesting Depth
Per Priority Class 24
Counters, Timers And Their Retentivity
S7 Counter
Number 2 048
Retentivity
— Adjustable Yes
Iec Counter
Number Any (Only Limited By The Main Memory)
Retentivity
— Adjustable Yes
S7 Times
Number 2 048
Retentivity
— Adjustable Yes
Iec Timer
Number Any (Only Limited By The Main Memory)
Retentivity
— Adjustable Yes
Data Areas And Their Retentivity
Retentive Data Area (Incl. Timers, Counters, Flags), Max. 768 Kbyte
Flag
Size, Max. 16 Kbyte
Number Of Clock Memories 8; 8 Clock Memory Bit, Grouped Into One Clock Memory Byte
Data Blocks
Retentivity Adjustable Yes
Retentivity Preset No
Local Data
Per Priority Class, Max. 64 Kbyte; Max. 16 Kb Per Block
Address Area
Number Of Io Modules 16 384; Max. Number Of Modules / Submodules
I/O Address Area
Inputs 32 Kbyte
Outputs 32 Kbyte
Per Integrated Io Subsystem
— Inputs (Volume) 16 Kbyte
— Outputs (Volume) 16 Kbyte
Subprocess Images
Number Of Subprocess Images, Max. 32
Hardware Configuration
Number Of Io Controllers
Integrated 1
Time Of Day
Clock
Type Hardware Clock
Backup Time 6 Wk; At 40 °C Ambient Temperature, Typically
Deviation Per Day, Max. 10 S; Typ.: 2 S
Operating Hours Counter
Number 16
Clock Synchronization
Supported Yes
In As, Master No
In As, Device No
On Ethernet Via Ntp Yes
Interfaces
Number Of Profinet Interfaces 1
1. Interface
Interface Types
Rj 45 (Ethernet) Yes; X1
Number Of Ports 2
Integrated Switch Yes
Protocols
Ip Protocol Yes; Ipv4
Profinet Io Controller Yes
Profinet Io Device No
Simatic Communication Yes; Only Server
Open Ie Communication Yes
Web Server No
Media Redundancy Yes
Profinet Io Controller
Services
— Pg/Op Communication Yes
— Isochronous Mode No
— Irt No
— Profienergy Yes
— Number Of Connectable Io Devices, Max. 256
Update Time For Rt
— For Send Cycle Of 1 Ms 1 Ms To 512 Ms
2. Interface
Interface Types
Rj 45 (Ethernet) Yes; X2
Number Of Ports 1
Integrated Switch No
Protocols
Ip Protocol Yes; Ipv4
Profinet Io Controller No
Profinet Io Device No
Simatic Communication Yes; Only Server
Open Ie Communication Yes
Web Server No
Media Redundancy No
3. Interface
Interface Type Pluggable Interface Module (If)
Plug-In Interface Modules Synchronization Module 6Ag1960-1Cb00-4Aa5 Or 6Ag1960-1Fb00-4Aa5
4. Interface
Interface Type Pluggable Synchronization Submodule (Fo)
Plug-In Interface Modules Synchronization Module 6Ag1960-1Cb00-4Aa5 Or 6Ag1960-1Fb00-4Aa5
Interface Types
Rj 45 (Ethernet)
100 Mbps Yes
Autonegotiation Yes
Autocrossing Yes
Industrial Ethernet Status Led Yes
Protocols
Profisafe No
Number Of Connections
Number Of Connections, Max. 160
Number Of Connections Reserved For Es/Hmi/Web 10
Redundancy Mode
Media Redundancy
— Mrp Yes; Manager Auto Is Permanently Set In Tia. Max. 50 Nodes Are Possible
— Mrpd No
— Switchover Time On Line Break, Typ. 200 Ms; Profinet Mrp
— Number Of Stations In The Ring, Max. 50
Simatic Communication
S7 Routing No
S7 Communication, As Server Yes
S7 Communication, As Client No
Open Ie Communication
Tcp/Ip Yes
— Data Length, Max. 64 Kbyte
— Several Passive Connections Per Port, Supported Yes
Iso-On-Tcp (Rfc1006) Yes
— Data Length, Max. 64 Kbyte
Udp Yes
— Data Length, Max. 2 Kbyte; 1 472 Bytes For Udp Broadcast
— Udp Multicast Yes; Max. 5 Multicast Circuits
Dhcp No
Snmp Yes
Dcp Yes
Lldp Yes
Web Server
Http No
Https No
Opc Ua
Opc Ua Client No
Opc Ua Server No
Further Protocols
Modbus Yes; Modbus Tcp
S7 Message Functions
Program Alarms No
Test Commissioning Functions
Joint Commission (Team Engineering) No
Status Block Yes; Up To 16 Simultaneously
Single Step No
Status/Control
Status/Control Variable Yes
Variables Inputs/Outputs, Memory Bits, Dbs, Distributed I/Os, Timers, Counters
Number Of Variables, Max.
— Of Which Status Variables, Max. 200; Per Job
— Of Which Control Variables, Max. 200; Per Job
Forcing
Forcing, Variables Peripheral Inputs/Outputs
Number Of Variables, Max. 200
Diagnostic Buffer
Present Yes
Number Of Entries, Max. 3 200
— Of Which Powerfail-Proof 1 000
Traces
Number Of Configurable Traces 8
Memory Size Per Trace, Max. 512 Kbyte
Interrupts/Diagnostics/Status Information
Diagnostics Indication Led
Run/Stop Led Yes
Error Led Yes
Maint Led Yes
Connection Display Link Tx/Rx Yes
Supported Technology Objects
Motion Control No
Control Ler
Pid_Compact No
Pid_3Step No
Pid-Temp No
Counting And Measuring
High-Speed Counter No
Standards, Approvals, Certificates
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 570 Kg
— Global Warming Potential, (During Production) [Co2
Eq]96.9 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]483 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-9.97 Kg

Ambient Temperature During Operation

Horizontal Installation, Min. 0 °C; = Tmin
Horizontal Installation, Max. 60 °C; = Tmax; Display: 50 °C, The Display Is Switched Off At An Operating
Temperature Of Typically 50 °C
Vertical Installation, Min. 0 °C; = Tmin
Vertical Installation, Max. 40 °C; Display: 40 °C, At An Operating Temperature Of Typically 40 °C, The
Display Is Switched Off
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M) // Tmin ... (Tmax
- 10 K) At 795 Hpa ... 658 Hpa (+2 000 M ... +3 500 M) // Tmin ... (Tmax -20 K)
At 658 Hpa ... 540 Hpa (+3 500 M ... +5 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation / Frost (No Commissioning In Bedewed State),
Horizontal Installation
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
Use On Ships/At Sea
— To Biologically Active Substances According To En
60721-3-6Yes; Class 6B2 Mold, Fungal And Dry Rot Spores (Excluding Fauna)
— To Chemically Active Substances According To En
60721-3-6Yes; Class 6C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En Yes; Class 6S3 Incl. Sand, Dust; *
60721-3-6
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A
Configuration / Header
Configuration / Programming / Header
Programming Language
— Lad Yes
— Fbd Yes
— Stl Yes
— Scl Yes
— Cfc No
— Graph No
Know-How Protection
User Program Protection/Password Protection Yes
Copy Protection No
Block Protection Yes
Access Protection
Password For Display Yes
Protection Level: Write Protection Yes
Protection Level: Read/Write Protection Yes
Protection Level: Complete Protection Yes

Dimensions

Width 210 Mm
Height 147 Mm
Depth 129 Mm
Weight S
Weight , Approx. 2 119 G; Interface Modules: 2X 18 G

Documentation