This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6AG21326BH014BA0

6AG21326BH014BA0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6AG21326BH014BA0 Siemens

6AG21326BH014BA0 Siemens - SIPLUS ET 200SP DQ 16X24VDC/0.5A TX RAIL

Extended Description for 6AG21326BH014BA0 Siemens

6AG21326BH014BA0 Siemens - SIPLUS ET 200SP DQ 16X24VDC/ 0.5A TX RAIL -40?+70°C TX with 85°C for 10min with Conformal Coating BasedOn: 6ES7132-6BH01-0BA0 . (PNP.P-switching) Packing unit: 1 piece. fits to BU-type A0. Colour Code CC00. substitute value output. module diagnostics for: short-circuit to L+ and ground. wire break. supply voltage

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6AG2132-6BH01-4BA0
Product Description SIPLUS ET 200SP DQ 16x24VDC/ 0.5A TX rail based on 6ES7132-6BH01-0BA0 with conformal coating, -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes), digital output module, suitable for BU type A0, color code CC00, source output (PNP,sourcing output) substitute value output, module diagnostics for: short circuit to L+ and M, wire break, supply voltage
Product family SIPLUS extreme RAIL digital outputs
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 45 Day/Days
Net Weight (kg) 0,036 Kg
Packaging Dimension 6,50 x 7,60 x 2,30
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047618089634
UPC 804766781346
Commodity Code 85389091
LKZ_FDB/ CatalogID A&DSE/SIP ADD
Product Group 4C03
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 04.04.2018
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Isochronous Mode No
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version See Entry Id: 109746275
Operating Mode
Dq Yes
Dq With Energy-Saving Function No
Pwm No
Oversampling No
Mso No
Redundancy
Redundancy Capability Yes

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Input Current
Current Consumption, Max. 60 Ma; Without Load
Output Voltage / Header
Rated Value (Dc) 24 V
Power Loss
Power Loss , Typ. 1 W
Address Area
Address Space Per Module
Inputs + 2 Bytes For Qi Information
Outputs 2 Byte
Hardware Configuration
Automatic Encoding Yes
Mechanical Coding Element Yes
Selection Of Baseunit For Connection Variants
1-Wire Connection Bu Type A0
2-Wire Connection Bu Type A0 + Potential Distributor Module
3-Wire Connection Bu Type A0 + Potential Distributor Module
4-Wire Connection Bu Type A0 + Potential Distributor Module
Digital Outputs
Type Of Digital Output Source Output (Pnp, Current-Sourcing)
Number Of Digital Outputs 16; > +60 °C Max. Total Current 1.0 A
Current-Sinking No
Current-Sourcing Yes
Digital Outputs, Parameterizable Yes
Short-Circuit Protection Yes
Response Threshold, Typ. 1 A
Open-Circuit Detection Yes
Limitation Of Inductive Shutdown Voltage To Typ. L+ (-50 V)
Control Ling A Digital Input Yes
Switching Capacity Of The Outputs
With Resistive Load, Max. 0.5 A
On Lamp Load, Max. 5 W
Load Resistance Range
Lower Limit 48 Ω
Upper Limit 12 Kω
Output Current
For Signal "1" Rated Value 0.5 A
For Signal "0" Residual Current, Max. 0.1 Ma
Output Delay With Resistive Load
"0" To "1", Typ. 50 Μs
"1" To "0", Typ. 100 Μs
Parallel Switching Of Two Outputs
For Uprating No
For Redundant Control Of A Load Yes
Switching Frequency
With Resistive Load, Max. 100 Hz
With Inductive Load, Max. 2 Hz
On Lamp Load, Max. 10 Hz
Total Current Of The Outputs
Current Per Channel, Max. 0.5 A
Current Per Module, Max. 8 A
Total Current Of The Outputs (Per Module)
Horizontal Installation
— Up To 30 °C, Max. 8 A
— Up To 40 °C, Max. 8 A
— Up To 50 °C, Max. 6 A
— Up To 60 °C, Max. 4 A
— Up To 70 °C, Max. 1 A
Vertical Installation
— Up To 30 °C, Max. 8 A; In All Other Mounting Positions
— Up To 40 °C, Max. 6 A; In All Other Mounting Positions
— Up To 50 °C, Max. 4 A; In All Other Mounting Positions
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes
Substitute Values Connectable Yes
Alarms
Diagnostic Alarm Yes
Diagnoses
Monitoring The Supply Voltage Yes
Wire-Break Yes; Module-Wise
Short-Circuit To M Yes; Module-Wise
Short-Circuit To L+ Yes; Module-Wise
Diagnostics Indication Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Pwr Led
Channel Status Display Yes; Green Led
For Channel Diagnostics No
For Module Diagnostics Yes; Green/Red Diag Led
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsno
Isolation
Isolation Tested With 750 V Dc (Type Test) And According To En 50155 (Routine Test)
Standards, Approvals, Certificates
Suitable For Safety Functions No
Suitable For Safety-Related Tripping Of Standard Modules Yes
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 29.3 Kg
— Global Warming Potential, (During Production) [Co2
Eq]3.98 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]25.6 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.245 Kg
Railway Application
En 50121-3-2 Yes; Emc For Rail Vehicles
En 50121-4 Yes; Emc For Signal And Telecommunications Systems
En 50121-5 Yes; Emc For Fixed Installations And Railway Power Supply Equipment (Shielded
Cables Required)
En 50124-1 Yes; Railway Applications - Overvoltage Category Ov2; Pollution Degree Pd2;
Rated Surge Voltage Uni = 0.5 Kv; Unm = 24 V Dc
En 50125-1 Yes; Rail Vehicles - See Ambient Conditions
En 50125-2 Yes; Stationary Electrical Equipment - See Ambient Conditions
En 50125-3 Yes; Signal And Telecommunications Systems - See Ambient Conditions;
Vibrations And Shocks: Application Point Outside Of Tracks (1 M To 3 M Away
From Track)
En 50155 Yes; Rail Vehicles - Temperature Class Ot4, St1/St2, Horizontal Mounting
Position
En 61373 Yes; Rail Vehicles - Vibrations And Shocks: Category 1 Class A/B
Fire Protection Acc. To En 45545-2 Yes; For Proof Of Conformity, See Service & Support

Ambient Temperature During Operation

Horizontal Installation, Min. -40 °C; = Tmin (Incl. Condensation/Frost)
Horizontal Installation, Max. 70 °C; = Tmax; +85 °C For 10 Min (Ot4, St1/St2 Acc. To En 50155)
Vertical Installation, Min. -40 °C; = Tmin
Vertical Installation, Max. 50 °C; = Tmax
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 2 000 M
Ambient Air Temperature-Barometric Pressure-Altitude Tmin ... Tmax At 1 140 Hpa ... 795 Hpa (-1 000 M ... +2 000 M)
Relative Humidity
With Condensation, Tested In Accordance With Iec 60068-
2-38, Max.100 %; Rh Incl. Condensation/Frost (No Commissioning Under Condensation
Conditions)
Resistance
Coolants And Lubricants
— Resistant To Commercially Available Coolants And
Lubricantsyes; Incl. Diesel And Oil Droplets In The Air
Use In Stationary Industrial Systems
— To Biologically Active Substances According To En
60721-3-3Yes; Class 3B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 3B3 On Request
— To Chemically Active Substances According To En
60721-3-3Yes; Class 3C4 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-3Yes; Class 3S4 Incl. Sand, Dust, *
— Against Mechanical Environmental Conditions Acc. Yes; Class 3M8 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
To En 60721-3-3 0Aa0)
Use On Land Craft, Rail Vehicles And Special-Purpose Vehicles
— To Biologically Active Substances According To En
60721-3-5Yes; Class 5B2 Mold, Fungus And Dry Rot Spores (With The Exception Of Fauna);
Class 5B3 On Request
— To Chemically Active Substances According To En
60721-3-5Yes; Class 5C3 (Rh < 75 %) Incl. Salt Spray Acc. To En 60068-2-52 (Severity
Degree 3); *
— To Mechanically Active Substances According To En
60721-3-5Yes; Class 5S3 Incl. Sand, Dust; *
— Against Mechanical Environmental Conditions Acc.
To En 60721-3-5Yes; Class 5M2 Using The Siplus Mounting Kit Et 200Sp (6Ag1193-6Aa00-
0Aa0)
— Against Mechanical Environmental Conditions In
Agriculture Acc. To Iso 15003Yes; Level 1 (Location Le) Using The Siplus Mounting Kit Et 200Sp
(6Ag1193-6Aa00-0Aa0)
Usage In Industrial Process Technology
— Against Chemically Active Substances Acc. To En
60654-4Yes; Class 3 (Excluding Trichlorethylene)
— Environmental Conditions For Process, Measuring
And Control Systems Acc. To Ansi/Isa-71.04Yes; Level Gx Group A/B (Excluding Trichlorethylene; Harmful Gas
Concentrations Up To The Limits Of En 60721-3-3 Class 3C4 Permissible); Level
Lc3 (Salt Spray) And Level Lb3 (Oil)
Remark
— Note Regarding Classification Of Environmental
Conditions Acc. To En 60721, En 60654-4 And
Ansi/Isa-71.04* The Supplied Plug Covers Must Remain In Place Over The Unused Interfaces
During Operation!
Conformal Coating
Coatings For Printed Circuit Board Assemblies Acc. To En
61086Yes; Class 2 For High Reliability
Protection Against Fouling Acc. To En 60664-3 Yes; Type 1 Protection
Electronic Equipment On Rolling Stock Acc. To En 50155 Yes; Class Pc2 Protective Coating Acc. To En 50155:2017
Military Testing According To Mil-I-46058C, Amendment 7 Yes; Discoloration Of Coating Possible During Service Life
Qualification And Performance Of Electrical Insulating
Compound For Printed Board Assemblies According To Ipc-
Cc-830Ayes; Conformal Coating, Class A

Dimensions

Width 15 Mm
Height 73 Mm
Depth 58 Mm
Weight S
Weight , Approx. 30 G
Other
Note: For Use In Railway Applications, Also Observe The Product Information "Siplus
Extreme Rail" A5E37661960A, Online Support Article 109736776

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible