Description for 6ES71326BD202BA0 Siemens

6ES71326BD202BA0 Siemens - SIMATIC ET 200SP, DQ 4X24VDC/2A ST

Extended Description for 6ES71326BD202BA0 Siemens

6ES71326BD202BA0 Siemens - SIMATIC et 200sp, digital output module, dq 4x24VDC/2a standard, packing unit 10 pieces, fits to bu-type a0, color code cc02, module diagnosis

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7132-6BD20-2BA0
Product Description SIMATIC ET 200SP, digital output module, DQ 4x 24VDC/2A Standard, Pack quantity: 10 units, suitable for BU type A0, Color code CC02, Module diagnostics
Product family Digital output modules
Product Lifecycle (PLM) PM300:Active Product
PLM Effective Date Product phase-out since: 01.01.2025

Delivery information

Export Control Regulations AL : N / ECCN : EAR99H
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,310 Kg
Packaging Dimension 8,20 x 14,90 x 6,80
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1
Minimum order quantity 10

Additional Product Information

EAN 4047623405696
UPC 804766181146
Commodity Code 85389091
LKZ_FDB/ CatalogID ST76
Product Group 4520
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 31.03.2015
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 4,4'-isopropylidenediphenol (Bisphenol A, BPA) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Isochronous Mode No
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version V11 Sp2 / V13
Step 7 Configurable/Integrated From Version V5.5 Sp3 / -
Profibus From Gsd Version/Gsd Revision Gsd Revision 5
Profinet From Gsd Version/Gsd Revision Gsdml V2.3
Operating Mode
Dq Yes
Dq With Energy-Saving Function No
Pwm No
Oversampling No
Mso No

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Input Current
Current Consumption, Max. 60 Ma; Without Load
Output Voltage / Header
Rated Value (Dc) 24 V
Power Loss
Power Loss , Typ. 1 W
Address Area
Address Space Per Module
Address Space Per Module, Max. 1 Byte; + 1 Byte For Qi Information
Hardware Configuration
Automatic Encoding Yes
Mechanical Coding Element Yes
Type Of Mechanical Coding Element Type A
Selection Of Baseunit For Connection Variants
1-Wire Connection Bu Type A0
2-Wire Connection Bu Type A0
3-Wire Connection Bu Type A0 With Aux Terminals Or Potential Distributor Module
4-Wire Connection Bu Type A0 + Potential Distributor Module
Digital Outputs
Type Of Digital Output Source Output (Pnp, Current-Sourcing)
Number Of Digital Outputs 4
Current-Sinking No
Current-Sourcing Yes
Digital Outputs, Parameterizable Yes
Short-Circuit Protection Yes
Response Threshold, Typ. 2.8 To 5.2 A
Limitation Of Inductive Shutdown Voltage To Typ. L+ (-50 V)
Control Ling A Digital Input Yes
Switching Capacity Of The Outputs
With Resistive Load, Max. 2 A
On Lamp Load, Max. 10 W
Load Resistance Range
Lower Limit 12 Ω
Upper Limit 3 400 Ω
Output Current
For Signal "1" Rated Value 2 A
For Signal "0" Residual Current, Max. 0.1 Ma
Output Delay With Resistive Load
"0" To "1", Typ. 50 Μs
"0" To "1", Max. 50 Μs
"1" To "0", Typ. 100 Μs
"1" To "0", Max. 100 Μs
Parallel Switching Of Two Outputs
For Uprating No
For Redundant Control Of A Load Yes
Switching Frequency
With Resistive Load, Max. 100 Hz
With Inductive Load, Max. 2 Hz
On Lamp Load, Max. 10 Hz
Total Current Of The Outputs
Current Per Channel, Max. 2 A
Current Per Module, Max. 8 A
Total Current Of The Outputs (Per Module)
Horizontal Installation
— Up To 40 °C, Max. 8 A
— Up To 50 °C, Max. 6 A
— Up To 60 °C, Max. 4 A
Vertical Installation
— Up To 30 °C, Max. 8 A
— Up To 40 °C, Max. 6 A
— Up To 50 °C, Max. 4 A
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes
Substitute Values Connectable Yes
Alarms
Diagnostic Alarm Yes
Diagnoses
Monitoring The Supply Voltage Yes
Wire-Break Yes; Module-Wise
Short-Circuit Yes; Module-Wise
Group Error Yes
Diagnostics Indication Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Pwr Led
Channel Status Display Yes; Green Led
For Channel Diagnostics No
For Module Diagnostics Yes; Green/Red Diag Led
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsno
Isolation
Isolation Tested With 707 V Dc (Type Test)
Standards, Approvals, Certificates
Suitable For Safety Functions No
Suitable For Safety-Related Tripping Of Standard Modules Yes; See Faq Entry Id: 39198632
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 29.3 Kg
— Global Warming Potential, (During Production) [Co2
Eq]3.98 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]25.6 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.245 Kg
Highest Safety Class Achievable In Safety Mode
Performance Level According To Iso 13849-1 Pl D
Sil Acc. To Iec 61508 Sil 2

Ambient Temperature During Operation

Horizontal Installation, Min. -30 °C; < 0 °C As Of Fs08
Horizontal Installation, Max. 60 °C
Vertical Installation, Min. -30 °C; < 0 °C As Of Fs08
Vertical Installation, Max. 50 °C
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M; Restrictions For Installation Altitudes > 2 000 M, See Manual

Dimensions

Width 15 Mm
Height 73 Mm
Depth 58 Mm
Weight S
Weight , Approx. 30 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible