This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6ES7141-5AH00-0BL0

6ES7141-5AH00-0BL0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6ES7141-5AH00-0BL0 Siemens

6ES7141-5AH00-0BL0 Siemens - SIMATIC ET 200AL, IO-Link, DI 16x 24 V DC, 8x M12, Degree of protection IP67

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£129.08 Exc. VAT
£154.90 Inc. VAT

Product

Article Number (Market Facing Number) 6ES7141-5AH00-0BL0
Product Description SIMATIC ET 200AL, IO-Link, DI 16x 24 V DC, 8x M12, Degree of protection IP67
Product family IO-Link I/O modules
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,181 Kg
Packaging Dimension 5,70 x 18,00 x 5,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047623411352
UPC 195125114241
Commodity Code 85389091
LKZ_FDB/ CatalogID ST76
Product Group X03V
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 03.08.2020
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage 1L+
Rated Value (Dc) 24 V; Supply From 1Us+ Of The Io-Link Master
Permissible Range, Lower Limit (Dc) 18 V
Permissible Range, Upper Limit (Dc) 30 V
Reverse Polarity Protection Yes; Against Destruction; Encoder Power Supply Outputs Applied With Reversed
Polarity
Input Current
Current Consumption (Rated Value) 20 Ma; Without Load
Encoder Supply
Number Of Outputs 8; Supply From 1Us+ Of The Io-Link Master
24 V Encoder Supply
Short-Circuit Protection Yes; Per Module, Electronic
Output Current, Max. 0.7 A; Total Current Of All Encoders (Depending On Io-Link Master Supply Via
1Us+)
Power Loss
Power Loss , Typ. 2.4 W
Digital Inputs
Number Of Digital Inputs 16
Input Characteristic Curve In Accordance With Iec 61131, Type 3 Yes
Number Of Simultaneously Controllable Inputs
All Mounting Positions
— Up To 55 °C, Max. 16
Input Voltage
Rated Value (Dc) 24 V
For Signal "0" -30 To +5 V
For Signal "1" +11 To +30V
Input Current
For Signal "1", Typ. 3 Ma
Input Delay (For Rated Value Of Input Voltage)
For Standard Inputs
— At "0" To "1", Min. 1.2 Ms
— At "0" To "1", Max. 4.8 Ms
— At "1" To "0", Min. 1.2 Ms
— At "1" To "0", Max. 4.8 Ms
Cable Length
Unshielded, Max. 30 M
Encoder
Connectable Encoders
2-Wire Sensor Yes
— Permissible Quiescent Current (2-Wire Sensor), Max. 1.5 Ma
Io-Link
Io-Link Protocol 1.1 Yes
Transmission Rate 38.4 Kbd (Com2)
Cycle Time, Min. 2.5 Ms
Size Of Process Data, Input Per Module 2 Byte
Size Of Process Data, Output Per Module 0 Byte
Supported Io-Link Profiles Common Profile
Cable Length Unshielded, Max. 20 M
Connection Of Io-Link Devices
Port Type A Yes
Interrupts/Diagnostics/Status Information
Alarms
Diagnostic Alarm Yes; Parameterizable
Diagnoses
Short-Circuit Yes; Sensor Supply To M; Module By Module
Diagnostics Indication Led
Channel Status Display Yes; Green Led
For Module Diagnostics Yes; Green/Red Led
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And The Power Supply Of The
Electronicsno
Isolation
Isolation Tested With 707 V Dc (Type Test)
Degree And Class Of Protection
Ip Degree Of Protection Ip65/67

Ambient Temperature During Operation

Min. -30 °C
Max. 55 °C
Connection Method
Design Of Electrical Connection For The Inputs And Outputs M12, 5-Pin, A-Coded
Type Of Electrical Connection For Io-Link M12, 5-Pin, A-Coded

Dimensions

Width 45 Mm
Height 159 Mm
Depth 40 Mm
Weight S
Weight , Approx. 155 G