Description for 6ES7143-5BF00-0BA0 Siemens

6ES7143-5BF00-0BA0 Siemens - ET 200AL, DIQ 4+DQ 4X24VDC/0, 5A, 8XM8

Extended Description for 6ES7143-5BF00-0BA0 Siemens

6ES7143-5BF00-0BA0 Siemens - SIMATIC et 200al, diq 4+dq 4x24VDC/0,5a, 8xm8, degree of protection IP67

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£115.96 Exc. VAT
£139.15 Inc. VAT

Product

Article Number (Market Facing Number) 6ES7143-5BF00-0BA0
Product Description SIMATIC ET 200AL, DIQ 4+DQ 4x 24 V DC/0.5 A, 8XM8, Degree of protection IP67
Product family Digital I/O modules
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,170 Kg
Packaging Dimension 4,70 x 17,70 x 4,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047623403470
UPC 887621843090
Commodity Code 85389091
LKZ_FDB/ CatalogID ST76
Product Group 4522
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 14.08.2014
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 4,4'-isopropylidenediphenol (Bisphenol A, BPA) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version Step 7 V13 Sp1 Or Higher
Step 7 Configurable/Integrated From Version From V5.5 Sp4 Hotfix 3
Profibus From Gsd Version/Gsd Revision Gsd As Of Revision 5
Profinet From Gsd Version/Gsd Revision Gsdml V2.3.1

Supply Voltage

Load Voltage 1L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 20.4 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes; Against Destruction; Encoder Power Supply Outputs Applied With Reversed
Polarity, Loads Pick Up
Load Voltage 2L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 20.4 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes; Against Destruction; Load Increasing
Input Current
Current Consumption (Rated Value) 40 Ma; Without Load
From Load Voltage 1L+ (Unswitched Voltage) 4 A; Maximum Value
From Load Voltage 2L+, Max. 4 A; Maximum Value
Encoder Supply
Number Of Outputs 4
24 V Encoder Supply
Short-Circuit Protection Yes; Per Module, Electronic
Output Current, Max. 0.7 A; Total Current Of All Encoders
Power Loss
Power Loss , Typ. 2.5 W
Digital Inputs
Number Of Digital Inputs 4; Parameterizable As Diq
Input Characteristic Curve In Accordance With Iec 61131, Type 3 Yes
Number Of Simultaneously Controllable Inputs
All Mounting Positions
— Up To 55 °C, Max. 4
Input Voltage
Rated Value (Dc) 24 V
For Signal "0" -3 To +5V
For Signal "1" +11 To +30V
Input Current
For Signal "1", Typ. 3.2 Ma
Input Delay (For Rated Value Of Input Voltage)
For Standard Inputs
— At "0" To "1", Min. 1.2 Ms
— At "0" To "1", Max. 4.8 Ms
— At "1" To "0", Min. 1.2 Ms
— At "1" To "0", Max. 4.8 Ms
Cable Length
Unshielded, Max. 30 M
Digital Outputs
Number Of Digital Outputs 8; 4 Dq Fixed, 4 Diq Parameterizable
In Groups Of 4; 2 Load Groups For 4 Outputs Each
Short-Circuit Protection Yes; Per Channel, Electronic
Response Threshold, Typ. 0.7 A
Limitation Of Inductive Shutdown Voltage To 2L+ (-47 V)
Switching Capacity Of The Outputs
On Lamp Load, Max. 5 W
Load Resistance Range
Lower Limit 48 Ω
Upper Limit 4 Kω
Output Voltage
For Signal "1", Min. L+ (-0.8 V)
Output Current
For Signal "1" Rated Value 0.5 A
For Signal "0" Residual Current, Max. 0.5 Ma
Switching Frequency
With Resistive Load, Max. 100 Hz
With Inductive Load, Max. 0.5 Hz
On Lamp Load, Max. 1 Hz
Total Current Of The Outputs
Current Per Group, Max. 2 A
Cable Length
Unshielded, Max. 30 M
Encoder
Connectable Encoders
2-Wire Sensor Yes
— Permissible Quiescent Current (2-Wire Sensor), Max. 1.5 Ma
Interrupts/Diagnostics/Status Information
Substitute Values Connectable Yes; Channel By Channel, Parameterizable
Alarms
Diagnostic Alarm Yes; Parameterizable
Diagnoses
Short-Circuit Yes; Outputs To M; Encoder Supply To M; Module By Module
Diagnostics Indication Led
Channel Status Display Yes; Green Led
For Module Diagnostics Yes; Green/Red Led
For Load Voltage Monitoring Yes; Green Led
Potential Separation
Between The Load Voltages Yes
Potential Separation Channels
Between The Channels, In Groups Of 4; Diq Channels Are Isolated From Dq Channels
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsno; Diq Channels Are Non-Isolated And Dq Channels Are Isolated From Supply
Voltage 1L+
Isolation
Isolation Tested With 707 V Dc (Type Test)
Degree And Class Of Protection
Ip Degree Of Protection Ip65/67
Standards, Approvals, Certificates
Suitable For Safety-Related Tripping Of Standard Modules Yes; From Fs01
Highest Safety Class Achievable For Safety-Related Tripping Of Standard Modules
Performance Level According To Iso 13849-1 Pl D
Category According To Iso 13849-1 Cat. 3
Sil Acc. To Iec 62061 Sil 2
Remark On Safety-Oriented Shutdown Https://Support.Industry.Siemens.Com/Cs/De/En/View/39198632

Ambient Temperature During Operation

Min. -30 °C
Max. 55 °C
Connection Method
Design Of Electrical Connection For The Inputs And Outputs M8, 3-Pole
Design Of Electrical Connection For Supply Voltage M8, 4-Pole
Et-Connection
Et-Connection M8, 4-Pin, Shielded

Dimensions

Width 30 Mm
Height 159 Mm
Depth 40 Mm
Weight S
Weight , Approx. 145 G