This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6ES7144-6JF00-0BB0

6ES7144-6JF00-0BB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6ES7144-6JF00-0BB0 Siemens

6ES7144-6JF00-0BB0 Siemens - SIMATIC ET 200eco PN, AI 8xRTD/TC, M12-L, 8x M12, 16-bit resolution, channel diagnostics for wire break at input, shared device with 2 controllers, prioritized startup, MSI, MRP, S2 redundancy, I&M0...3, multi-fieldbus, PN IO, Ethernet IP, Modbus TCP, degree of protection IP67 / IP69K

Free Delivery to UK Mainland on orders over £25

Direct from Manufacturer

Fetching stock
2 - 4 W.Weeks

£471.75 Exc. VAT
£566.10 Inc. VAT

Product

Article Number (Market Facing Number) 6ES7144-6JF00-0BB0
Product Description SIMATIC ET 200eco PN, AI 8xRTD/TC, M12-L, 8x M12, 16-bit resolution, channel diagnostics for wire break at input, shared device with 2 controllers, prioritized startup, MSI, MRP, S2 redundancy, I&M0...3, multi-fieldbus, PN IO, Ethernet IP, Modbus TCP, degree of protection IP67 / IP69K
Product family Analog I/O devices
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,818 Kg
Packaging Dimension 7,10 x 19,80 x 5,80
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047623411673
UPC 195125387768
Commodity Code 85389091
LKZ_FDB/ CatalogID ST76
Product Group X00R
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 30.06.2022
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Isochronous Mode No
Prioritized Startup Yes
Measuring Range Scalable Yes
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version Step 7 V17 Or Higher With Hsp 0369
Profinet From Gsd Version/Gsd Revision Gsdml V2.4.X
Multi Fieldbus Configuration Tool (Mfct) From V1.3 Sp1
Operating Mode
Msi Yes
Cir - Configuration In Run
Calibration Possible In Run Yes

Supply Voltage

Power Supply According To Nec Class 2 Required No
Load Voltage 1L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 20.4 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes; Against Destruction
Input Current
Current Consumption (Rated Value) 85 Ma; Without Load
From Load Voltage 1L+ (Unswitched Voltage) 12 A; Maximum Value
From Load Voltage 2L+, Max. 12 A; Maximum Value
Power Loss
Power Loss , Typ. 6.3 W
Address Area
Address Space Per Module
Inputs 16 Byte; + 1 Byte For Qi Information
Hardware Configuration
Submodules
Number Of Configurable Submodules, Max. 2

Analog Inputs

Number Of Analog Inputs 8
For Voltage Measurement 8
For Resistance/Resistance Thermometer Measurement 8
For Thermocouple Measurement 8
Permissible Input Voltage For Voltage Input (Destruction Limit),
Max.24 V
Constant Measurement Current For Resistance-Type Transmitter,
Typ.0.7 Ma
Cycle Time (All Channels), Min. Sum Of The Basic Conversion Times And Additional Processing Times (Depending
On The Parameterization Of The Active Channels); For Line Compensation In Case
Of A Three-Wire Connection, An Additional Cycle Is Necessary
Technical Unit For Temperature Measurement Adjustable Yes; Degrees Celsius / Degrees Fahrenheit / Kelvin
Input Ranges (Rated Values), Voltages
-80 Mv To +80 Mv Yes; 16 Bit Incl. Sign
— Input Resistance (-80 Mv To +80 Mv) 10 M Ω
Input Ranges (Rated Values), Thermocouples
Type B Yes; 16 Bit Incl. Sign
— Input Resistance (Type B) 10 M Ω
Type C Yes; 16 Bit Incl. Sign
— Input Resistance (Type C) 10 M Ω
Type E Yes; 16 Bit Incl. Sign
— Input Resistance (Type E) 10 M Ω
Type J Yes; 16 Bit Incl. Sign
— Input Resistance (Type J) 10 M Ω
Type K Yes; 16 Bit Incl. Sign
— Input Resistance (Type K) 10 M Ω
Type L Yes; 16 Bit Incl. Sign
— Input Resistance (Type L) 10 M Ω
Type N Yes; 16 Bit Incl. Sign
— Input Resistance (Type N) 10 M Ω
Type R Yes; 16 Bit Incl. Sign
— Input Resistance (Type R) 10 M Ω
Type S Yes; 16 Bit Incl. Sign
— Input Resistance (Type S) 10 M Ω
Type T Yes; 16 Bit Incl. Sign
— Input Resistance (Type T) 10 M Ω
Type U Yes; 16 Bit Incl. Sign
— Input Resistance (Type U) 10 M Ω
Input Ranges (Rated Values), Resistance Thermometer
Ni 100 Yes; Standard/Climate
— Input Resistance (Ni 100) 10 M Ω
Ni 1000 Yes; Standard/Climate
— Input Resistance (Ni 1000) 10 M Ω
Ni 120 Yes; Standard/Climate
— Input Resistance (Ni 120) 10 M Ω
Ni 200 Yes; Standard/Climate
— Input Resistance (Ni 200) 10 M Ω
Ni 500 Yes; Standard/Climate
— Input Resistance (Ni 500) 10 M Ω
Pt 100 Yes; Standard/Climate
— Input Resistance (Pt 100) 10 M Ω
Pt 1000 Yes; Standard/Climate
— Input Resistance (Pt 1000) 10 M Ω
Pt 200 Yes; Standard/Climate
— Input Resistance (Pt 200) 10 M Ω
Pt 500 Yes; Standard/Climate
— Input Resistance (Pt 500) 10 M Ω
Input Ranges (Rated Values), Resistors
0 To 150 Ohms Yes
— Input Resistance (0 To 150 Ohms) 10 M Ω
0 To 300 Ohms Yes
— Input Resistance (0 To 300 Ohms) 10 M Ω
0 To 600 Ohms Yes
— Input Resistance (0 To 600 Ohms) 10 M Ω
0 To 3000 Ohms Yes
— Input Resistance (0 To 3000 Ohms) 10 M Ω
0 To 6000 Ohms Yes
— Input Resistance (0 To 6000 Ohms) 10 M Ω
Thermocouple (Tc)
Temperature Compensation
— Parameterizable Yes
— Internal Temperature Compensation Yes
— External Temperature Compensation With
Compensations Socketyes
— Dynamic Reference Temperature Value Yes
— Fixed Reference Temperature Yes
Cable Length
Shielded, Max. 30 M
Analog Value Generation For The Inputs
Analog Value Display Simatic S7 Format
Measurement Principle Integrating
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 16 Bit
Integration Time, Parameterizable Yes; Channel By Channel
Integration Time (Ms) 0.84 / 16.7 (50) / 20 (60) / 60 (180)
Basic Conversion Time, Including Integration Time (Ms) 4.50 / 21.5 (54) / 24 (64) / 64 (184)
— Additional Conversion Time For Wire-Break Monitoring 2 Ms; For 3/4-Wire Transducer 4 Ms
Interference Voltage Suppression For Interference
Frequency F1 In Hznone / 60 / 50 / 16.7
Smoothing Of Measured Values
Parameterizable Yes
Step: None Yes; 1X Cycle Time
Step: Low Yes; 4X Cycle Time
Step: Medium Yes; 16X Cycle Time
Step: High Yes; 32X Cycle Time
Encoder
Connection Of Signal Encoders
For Resistance Measurement With Two-Wire Connection Yes
For Resistance Measurement With Three-Wire Connection Yes
For Resistance Measurement With Four-Wire Connection Yes
Errors/Accuracies
Linearity Error (Relative To Input Range), (+/-) 0.01 %; ±0.1 % For Resistance Thermometers And Resistance
Temperature Error (Relative To Input Range), (+/-) 0.0009 %/K; ±0.005 % / K At Thermocouple
Crosstalk Between The Inputs, Max. -70 Db
Repeat Accuracy In Steady State At 25 °C (Relative To Input
Range), (+/-)0.008 %
Temperature Error Of Internal Compensation ±1,5 °C
Operation Al Error Limit In Overall Temperature Range
Voltage, Relative To Input Range, (+/-) 0.2 %
Resistance, Relative To Input Range, (+/-) 0.1 %; See Deviations In The Manual
Resistance Thermometer, Relative To Input Range, (+/-) 0.1 %; See Deviations In The Manual
Thermocouple, Relative To Input Range, (+/-) 0.3 %
Basic Error Limit (Operational Limit At 25 °C)
Voltage, Relative To Input Range, (+/-) 0.1 %
Resistance, Relative To Input Range, (+/-) 0.05 %; See Deviations In The Manual
Resistance Thermometer, Relative To Input Range, (+/-) 0.05 %; See Deviations In The Manual
Thermocouple, Relative To Input Range, (+/-) 0.15 %
Interference Voltage Suppression For F = N X (F1 +/- 0.5 %), F1 = Interference Frequency
Series Mode Interference (Peak Value Of Interference <
Rated Value Of Input Range), Min.40 Db
Interfaces
Number Of Profinet Interfaces 1
1. Interface
Interface Type Profinet With 100 Mbit/S Full Duplex (100Base-Tx)
Interface Types
M12 Port Yes; 2X M12, 4-Pin, D-Coded
Number Of Ports 2
Integrated Switch Yes
Protocols
Profinet Io Device Yes
Open Ie Communication Yes
Interface Types
M12 Port
Autonegotiation Yes
Autocrossing Yes
Transmission Rate, Max. 100 Mbit/S
Protocols
Supports Protocol For Profinet Io Yes
Profisafe No
Ethernet /Ip Yes
Modbus Tcp Yes
Profinet Io Device
Services
— Irt Yes; 250 Μs To 4 Ms In 125 Μs Frame
— Prioritized Startup Yes
— Shared Device Yes
— Number Of Io Controllers With Shared Device, Max. 2
Redundancy Mode
Profinet System Redundancy (S2) Yes
— On S7-1500R/H Yes
— On S7-400H Yes
Profinet System Redundancy (R1) No
H-Sync Forwarding Yes
Media Redundancy
— Mrp Yes
Ethernet /Ip
Services
— Cip Implicit Messaging Yes
— Cip Explicit Messaging Yes
— Cip Safety No
— Shared Device Yes; 2X Ethernet/Ip Scanner
— Number Of Scanners With Shared Device, Max. 2
Updating Times
— Requested Packet Interval (Rpi) 2 Ms
Redundancy Mode
— Dlr (Device Level Ring) No
Address Area
— Address Space Per Module, Max. 38 Byte
— Largeforwardopen (Class3) No
Modbus Tcp
Services
— Read Coils (Code=1) Yes
— Read Discrete Inputs (Code=2) Yes
— Read Holding Registers (Code=3) Yes
— Write Single Coil (Code=5) Yes
— Write Multiple Coils (Code=15) Yes
— Write Multiple Registers (Code=16) Yes
— Parameter Change By Master No
— Modbus Tcp Security Protocol No
Address Space Per Station
— Address Space Per Station, Max. 38 Byte
— Access-Consistent Address Space 2 Byte
Updating Time
— I/O Request Interval 2 Ms

Connections

— Number Of Connections Per Device 12
Open Ie Communication
Tcp/Ip Yes; (Only Ethernet/Ip Or Modbus Tcp)
Snmp Yes
Lldp Yes
Arp Yes
Interrupts/Diagnostics/Status Information
Alarms
Diagnostic Alarm Yes; Parameterizable
Maintenance Interrupt Yes; Parameterizable
Limit Value Alarm Yes; Two Upper And Two Lower Limit Values In Each Case
Diagnoses
Diagnostic Information Readable Yes
Monitoring The Supply Voltage Yes
— Parameterizable Yes
Wire-Break Yes; Not For ±80 Mv
Overflow/Underflow Yes
Diagnostics Indication Led
Run Led Yes; Green Led
Error Led Yes; Red Led
Maint Led Yes; Yellow Led
Ns Led Yes; Green/Red Led
Ms Led Yes; Green/Red Led
Io Led Yes; Red/Green/Yellow Leds
Channel Status Display Yes; Green Led
For Channel Diagnostics Yes; Red Led
Connection Display Link Tx/Rx Yes; Green Led, Only Link
Potential Separation
Between The Load Voltages Yes
Between Ethernet And Electronics Yes
Potential Separation Channels
Between The Channels No
Between The Channels And The Power Supply Of The
Electronicsyes
Isolation
Tested With
24 V Dc Circuits 707 V Dc (Type Test)
Test Voltage For Interface, Rms Value [Vrms] 1 500 V; According To Ieee 802.3
Degree And Class Of Protection
Ip Degree Of Protection Ip65/67/69K
Standards, Approvals, Certificates
Suitable For Safety-Related Tripping Of Standard Modules Yes; From Fs01
Suitable For Applications According To Ams 2750 Yes; Declaration Of Conformity, See Online Support Entry 109757262
Suitable For Applications According To Cqi-9 Yes; Based On Ams 2750 F
Highest Safety Class Achievable For Safety-Related Tripping Of Standard Modules
Performance Level According To Iso 13849-1 Pl D
Category According To Iso 13849-1 Cat. 3
Sil Acc. To Iec 62061 Sil 2
Remark On Safety-Oriented Shutdown Https://Support.Industry.Siemens.Com/Cs/De/En/View/39198632
Use In Hazardous Areas
Explosion Protection Category For Gas Atex, Ukex, Iecex, Cccex For Zone 2
Explosion Protection Category For Dust Atex, Ukex, Iecex, Cccex For Zone 22
Product Functions / Security / Header
Signed Firmware Update Yes
Safely Removing Data Yes

Ambient Temperature During Operation

Min. -40 °C
Max. 60 °C
Altitude During Operation Relating To Sea Level
Ambient Air Temperature-Barometric Pressure-Altitude Up To Max. 5 000 M, At Installation Height > 2 000 M Additional Restrictions
Connection Method
Design Of Electrical Connection 4/5-Pin M12 Circular Connectors
Design Of Electrical Connection For The Inputs And Outputs M12, 5-Pin, A-Coded
Design Of Electrical Connection For Supply Voltage M12, 4-Pin, L-Coded

Dimensions

Width 45 Mm
Height 200 Mm
Depth 48 Mm
Weight S
Weight , Approx. 780 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible