Description for 6ES7231-5PF32-0XB0 Siemens

6ES7231-5PF32-0XB0 Siemens - S7-1200, ANALOG INPUT SM 1231 RTD, 8 AI

Extended Description for 6ES7231-5PF32-0XB0 Siemens

6ES7231-5PF32-0XB0 Siemens - SIMATIC s7-1200, analog input, sm 1231rtd, 8 x ai rtd module

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7231-5PF32-0XB0
Product Description SIMATIC S7-1200, Analog input, SM 1231 RTD, 8xAI RTD module
Product family SM 1231 RTD signal module
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,283 Kg
Packaging Dimension 8,80 x 10,90 x 8,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 6940408101883
UPC 887621549800
Commodity Code 85389091
LKZ_FDB/ CatalogID ST72
Product Group 4508
Group Code R132
Country of origin China
Compliance with the substance restrictions according to RoHS directive Since: 30.08.2013
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2,2',6,6'-tetrabromo... CAS-No. 79-94-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead titanium zircon... CAS-No. 12626-81-2 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead titanium zirconium oxide Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc) 24 V
Input Current
Current Consumption, Typ. 40 Ma
From Backplane Bus 5 V Dc, Typ. 80 Ma
Power Loss
Power Loss , Typ. 1.5 W

Analog Inputs

Number Of Analog Inputs 8; Resistance Thermometer
Permissible Input Voltage For Voltage Input (Destruction Limit),
Max.±35 V
Technical Unit For Temperature Measurement Adjustable Degrees Celsius/Degrees Fahrenheit
Input Ranges
Voltage No
Current No
Thermocouple No
Resistance Thermometer Yes; Resistance-Type Transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000,
Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, Lg-Ni1000
Resistance Yes; 150 Ω, 300 Ω, 600 Ω
Input Ranges (Rated Values), Resistance Thermometer
Cu 10 Yes
— Input Resistance (Cu 10) 10 Ω
Ni 100 Yes
— Input Resistance (Ni 100) 100 Ω
Ni 1000 Yes
— Input Resistance (Ni 1000) 1 000 Ω
Lg-Ni 1000 Yes
— Input Resistance (Lg-Ni 1000) 1 000 Ω
Ni 120 Yes
— Input Resistance (Ni 120) 120 Ω
Ni 200 Yes
— Input Resistance (Ni 200) 200 Ω
Ni 500 Yes
— Input Resistance (Ni 500) 500 Ω
Pt 100 Yes
— Input Resistance (Pt 100) 100 Ω
Pt 1000 Yes
— Input Resistance (Pt 1000) 1 000 Ω
Pt 200 Yes
— Input Resistance (Pt 200) 200 Ω
Pt 500 Yes
— Input Resistance (Pt 500) 500 Ω
Input Ranges (Rated Values), Resistors
0 To 150 Ohms Yes
0 To 300 Ohms Yes
0 To 600 Ohms Yes
Thermocouple (Tc)
Temperature Compensation
— Parameterizable No
Analog Value Generation For The Inputs
Measurement Principle Integrating
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 15 Bit; + Sign
Integration Time, Parameterizable No
Interference Voltage Suppression For Interference
Frequency F1 In Hz85 Db At 50 / 60 / 400 Hz
Errors/Accuracies
Temperature Error (Relative To Input Range), (+/-) 25 °C ±0.1%, To 55 °C ±0.2% Total Measurement Range
Repeat Accuracy In Steady State At 25 °C (Relative To Output
Range), (+/-)0.05 %
Interference Voltage Suppression For F = N X (F1 +/- 1 %), F1 = Interference Frequency
Common Mode Interference, Min. 120 Db
Interrupts/Diagnostics/Status Information
Alarms Yes
Diagnostics Function Yes; Can Be Read Out
Alarms
Diagnostic Alarm Yes
Diagnoses
Monitoring The Supply Voltage Yes
Wire-Break Yes
Diagnostics Indication Led
For Status Of The Inputs Yes
For Maintenance Yes
Degree And Class Of Protection
Ip Degree Of Protection Ip20
Standards, Approvals, Certificates
Ce Mark Yes
Csa Approval Yes
Ul Approval Yes
Culus Yes
Fm Approval Yes
Rcm (Formerly C-Tick) Yes
Kc Approval Yes
Marine Approval Yes
Ecological Footprint
Environmental Product Declaration Yes
Global Warming Potential
— Global Warming Potential, (Total) [Co2 Eq] 43.1 Kg
— Global Warming Potential, (During Production) [Co2
Eq]7.62 Kg
— Global Warming Potential, (During Operation) [Co2
Eq]36 Kg
— Global Warming Potential, (After End Of Life Cycle)
[Co2 Eq]-0.544 Kg

Ambient Conditions

Free Fall
Fall Height, Max. 0.3 M; Five Times, In Product Package

Ambient Temperature During Operation

Min. -20 °C
Max. 60 °C
Horizontal Installation, Min. -20 °C
Horizontal Installation, Max. 60 °C
Vertical Installation, Min. -20 °C
Vertical Installation, Max. 50 °C
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Air Pressure Acc. To Iec 60068-2-13
Operation, Min. 795 Hpa
Operation, Max. 1 080 Hpa
Storage/Transport, Min. 660 Hpa
Storage/Transport, Max. 1 080 Hpa
Relative Humidity
Operation At 25 ℃ Without Condensation, Max. 95 %
Pollutant Concentrations
So2 At Rh < 60% Without Condensation S02: < 0.5 Ppm; H2S: < 0.1 Ppm; Rh < 60% Condensation-Free
Connection Method
Required Front Connector Yes
Mechanics/Material
Enclosure Material (Front)
Plastic Yes

Dimensions

Width 70 Mm
Height 100 Mm
Depth 75 Mm
Weight S