This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6ES7331-7KB02-0AB0

6ES7331-7KB02-0AB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6ES7331-7KB02-0AB0 Siemens

6ES7331-7KB02-0AB0 Siemens - ASM_I/O_6ES7331-7KB02-0AB0_Analog_Input

Extended Description for 6ES7331-7KB02-0AB0 Siemens

6ES7331-7KB02-0AB0 Siemens - SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 2 AI, 9/12/14 BITS RESOLUTION, U/I/THERMOCOUPLE/RESISTANCE, INTERRUPT, DIAGNOSTICS, 1 X 20 PIN, REMOVE/INSERT W. BACKPLANE BUS

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7331-7KB02-0AB0
Product Description SIMATIC S7-300, Analog input SM 331, isolated, 2 AI, Resolution 9/12/14 bits, U/I/thermocouple/resistor, alarm, diagnostics, 1x 20-pole, Removing/inserting with active backplane bus
Product family SM 331 analog input modules
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 01.10.2023

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,249 Kg
Packaging Dimension 12,80 x 15,10 x 5,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4025515066781
UPC 662643177299
Commodity Code 85389091
LKZ_FDB/ CatalogID ST73
Product Group 2288
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 31.03.2008
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2,2',6,6'-tetrabromo... CAS-No. 79-94-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Perfluorobutane sulfonic ... > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Perfluorobutane sulfonic acid (PFBS) and its salts Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Reverse Polarity Protection Yes
Input Current
From Load Voltage L+ (Without Load), Max. 30 Ma
From Backplane Bus 5 V Dc, Max. 50 Ma
Power Loss
Power Loss , Typ. 1 W

Analog Inputs

Number Of Analog Inputs 2
For Resistance Measurement 1
Permissible Input Voltage For Voltage Input (Destruction Limit),
Max.20 V; Continuous; 75 V For Max. 1 S (Mark To Space Ratio 1:20)
Permissible Input Current For Current Input (Destruction Limit),
Max.40 Ma
Constant Measurement Current For Resistance-Type Transmitter,
Typ.1.67 Ma
Input Ranges
Voltage Yes
Current Yes
Thermocouple Yes
Resistance Thermometer Yes
Resistance Yes
Input Ranges (Rated Values), Voltages
0 To +10 V No
1 V To 5 V Yes
— Input Resistance (1 V To 5 V) 100 K Ω
1 V To 10 V No
-1 V To +1 V Yes
— Input Resistance (-1 V To +1 V) 10 M Ω
-10 V To +10 V Yes
— Input Resistance (-10 V To +10 V) 100 K Ω
-2.5 V To +2.5 V Yes
— Input Resistance (-2.5 V To +2.5 V) 100 K Ω
-250 Mv To +250 Mv Yes
— Input Resistance (-250 Mv To +250 Mv) 10 M Ω
-5 V To +5 V Yes
— Input Resistance (-5 V To +5 V) 100 K Ω
-50 Mv To +50 Mv No
-500 Mv To +500 Mv Yes
— Input Resistance (-500 Mv To +500 Mv) 10 M Ω
-80 Mv To +80 Mv Yes
— Input Resistance (-80 Mv To +80 Mv) 10 M Ω
Input Ranges (Rated Values), Currents
0 To 20 Ma Yes
— Input Resistance (0 To 20 Ma) 25 Ω
-10 Ma To +10 Ma Yes
— Input Resistance (-10 Ma To +10 Ma) 25 Ω
-20 Ma To +20 Ma Yes
— Input Resistance (-20 Ma To +20 Ma) 25 Ω
-3.2 Ma To +3.2 Ma Yes
— Input Resistance (-3.2 Ma To +3.2 Ma) 25 Ω
4 Ma To 20 Ma Yes
— Input Resistance (4 Ma To 20 Ma) 25 Ω
Input Ranges (Rated Values), Thermocouples
Type B No
Type E Yes
— Input Resistance (Type E) 10 M Ω
Type J Yes
— Input Resistance (Type J) 10 M Ω
Type K Yes
— Input Resistance (Type K) 10 M Ω
Type L No
Type N Yes
— Input Resistance (Type N) 10 M Ω
Type R No
Type S No
Type T No
Type U No
Type Txk/Txk(L) To Gost No
Input Ranges (Rated Values), Resistance Thermometer
Cu 10 No
Ni 100 Yes
— Input Resistance (Ni 100) 10 M Ω; Standard
Ni 1000 No
Lg-Ni 1000 No
Ni 120 No
Ni 200 No
Ni 500 No
Pt 100 Yes
— Input Resistance (Pt 100) 10 Kω; Standard
Pt 1000 No
Pt 200 No
Pt 500 No
Input Ranges (Rated Values), Resistors
0 To 150 Ohms Yes
— Input Resistance (0 To 150 Ohms) 10 M Ω
0 To 300 Ohms Yes
— Input Resistance (0 To 300 Ohms) 10 M Ω
0 To 600 Ohms Yes
— Input Resistance (0 To 600 Ohms) 10 M Ω
0 To 6000 Ohms No
Thermocouple (Tc)
Temperature Compensation
— Parameterizable Yes
— Internal Temperature Compensation Yes
— External Temperature Compensation With
Compensations Socketyes
— For Definable Comparison Point Temperature Yes
Characteristic Linearization
Parameterizable Yes
— For Thermocouples Type E, J, K, L, N
— For Resistance Thermometer Pt100 (Standard, Climatic Range), Ni100 (Standard, Climatic Range)
Cable Length
Shielded, Max. 200 M; 50 M At 80 Mv And Thermocouples
Analog Value Generation For The Inputs
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 15 Bit; Unipolar: 9/12/12/14 Bit; Bipolar: 9 Bit + Sign/12 Bit + Sign/12 Bit + Sign/14
Bit + Sign
Integration Time, Parameterizable Yes; 2,5 / 16,67 / 20 / 100 Ms
Basic Conversion Time (Ms) 3 / 17 / 22 / 102 Ms
Interference Voltage Suppression For Interference
Frequency F1 In Hz400 / 60 / 50 / 10 Hz
Encoder
Connection Of Signal Encoders
For Voltage Measurement Yes
For Current Measurement As 2-Wire Transducer Yes
For Current Measurement As 4-Wire Transducer Yes
For Resistance Measurement With Two-Wire Connection Yes
For Resistance Measurement With Three-Wire Connection Yes
For Resistance Measurement With Four-Wire Connection Yes
Errors/Accuracies
Operation Al Error Limit In Overall Temperature Range
Voltage, Relative To Input Range, (+/-) 1 %; ±1% (80 Mv); ±0.6% (250 Mv To 1 000 Mv); ±0.8% (2.5 V To 10 V)
Current, Relative To Input Range, (+/-) 0.7 %; From 3.2 To 20 Ma
Resistance, Relative To Input Range, (+/-) 0.7 %; 150, 300, 600 Ohm
Resistance Thermometer, Relative To Input Range, (+/-) 0.7 %; ±0.7 % (Pt100/ Ni100); ±0.8 % (Pt100 Climate)
Thermocouple, Relative To Input Range, (+/-) 1.1 %; Type E, J, K, L, N
Basic Error Limit (Operational Limit At 25 °C)
Voltage, Relative To Input Range, (+/-) 0.6 %; ±0.6% (80 Mv, 2.5 V To 10 V); ±0.4% (250 Mv To 1 000 Mv)
Current, Relative To Input Range, (+/-) 0.5 %; 3.2 To 20 Ma
Resistance, Relative To Input Range, (+/-) 0.5 %; 150, 300, 600 Ohm
Resistance Thermometer, Relative To Input Range, (+/-) 0.6 %; ±0.5% (Pt100/ Ni100), ±0.6% (Pt100 Climate)
Thermocouple, Relative To Input Range, (+/-) 0.7 %; Type E, N, J, K, L
Interrupts/Diagnostics/Status Information
Diagnostics Function Yes; Parameterizable
Alarms
Diagnostic Alarm Yes
Limit Value Alarm Yes; Parameterizable, Channel 0
Diagnoses
Diagnostic Information Readable Yes
Diagnostics Indication Led
Group Error Sf (Red) Yes
Potential Separation
Potential Separation Analog Inputs
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And The Power Supply Of The
Electronicsyes; Not For 2-Wire Transmitters
Isolation
Isolation Tested With 500 V Dc
Connection Method
Required Front Connector 20-Pin

Dimensions

Width 40 Mm
Height 125 Mm
Depth 120 Mm
Weight S