Product

Article Number (Market Facing Number) 6ES7355-0VH10-0AE0
Product Description SIMATIC S7-300, Control Unit FM 355 C, 4 channels, continuous, 4 AI+8 DI+4 AO incl. multi-language configuration package, Manual and Getting Started (de, de, fr, en fr, it) on CD-ROM
Product family FM 355 controller module
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 01.10.2023

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 1 Day/Days
Net Weight (kg) 0,579 Kg
Packaging Dimension 12,60 x 15,40 x 8,90
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4025515061625
UPC 662643176445
Commodity Code 85389091
LKZ_FDB/ CatalogID ST73
Product Group 2291
Group Code R132
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 20.06.2017
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2,2',6,6'-tetrabromo... CAS-No. 79-94-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Perfluorobutane sulfonic ... > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Perfluorobutane sulfonic acid (PFBS) and its salts Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 20.4 V
Permissible Range, Upper Limit (Dc) 28.8 V
Input Current
From Load Voltage L+ (Without Load), Max. 310 Ma; Typ. 260 Ma
From Backplane Bus 5 V Dc, Max. 75 Ma; Typ. 50 Ma
Power Loss
Power Loss , Typ. 6.5 W
Power Loss , Max. 7.8 W
Digital Inputs
Number Of Digital Inputs 8
Input Characteristic Curve In Accordance With Iec 61131, Type 2 Yes
Input Voltage
Rated Value (Dc) 24 V
For Signal "0" -3 To +5V
For Signal "1" 13 To 30V
Input Current
For Signal "1", Typ. 7 Ma
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M

Analog Inputs

Number Of Analog Inputs 4
Permissible Input Voltage For Voltage Input (Destruction Limit),
Max.30 V
Permissible Input Current For Current Input (Destruction Limit),
Max.40 Ma
Input Ranges
Voltage Yes
Current Yes
Thermocouple Yes
Resistance Thermometer Yes
Input Ranges (Rated Values), Voltages
0 To +10 V Yes
— Input Resistance (0 To 10 V) 100 K Ω
-1.75 V To +11.75 V Yes
— Input Resistance (-1.75 V To +11.75 V) 100 K Ω
-80 Mv To +80 Mv Yes
— Input Resistance (-80 Mv To +80 Mv) 10 M Ω
Input Ranges (Rated Values), Currents
0 To 20 Ma Yes
— Input Resistance (0 To 20 Ma) 50 Ω
0 To 23.5 Ma Yes
— Input Resistance (0 To 23.5 Ma) 50 Kω
-3.5 Ma To +23.5 Ma Yes
— Input Resistance (-3.5 Ma To +23.5 Ma) 50 Ω
4 Ma To 20 Ma Yes
— Input Resistance (4 Ma To 20 Ma) 50 Kω
Input Ranges (Rated Values), Thermocouples
Type B Yes
— Input Resistance (Type B) 10 M Ω
Type J Yes
— Input Resistance (Type J) 10 M Ω
Type K Yes
— Input Resistance (Type K) 10 M Ω
Type R Yes
— Input Resistance (Type R) 10 M Ω
Type S Yes
— Input Resistance (Type S) 10 M Ω
Input Ranges (Rated Values), Resistance Thermometer
Pt 100 Yes
— Input Resistance (Pt 100) 10 M Ω
Thermocouple (Tc)
Temperature Compensation
— Internal Temperature Compensation Yes
— External Temperature Compensation With Pt100 Yes
Characteristic Linearization
Parameterizable Yes
— For Thermocouples Type B, J, K, R, S
— For Resistance Thermometer Pt100 (Standard)
Cable Length
Shielded, Max. 200 M; 50 M At 80 Mv And Thermocouples
Analog Outputs
Number Of Analog Outputs 4
Voltage Output, Short-Circuit Protection Yes
Voltage Output, Short-Circuit Current, Max. 25 Ma
Current Output, No-Load Voltage, Max. 18 V
Output Ranges, Voltage
0 To 10 V Yes
-10 V To +10 V Yes
Output Ranges, Current
0 To 20 Ma Yes
4 Ma To 20 Ma Yes
Connection Of Actuators
For Voltage Output Two-Wire Connection Yes
For Current Output Two-Wire Connection Yes
Load Impedance (In Rated Range Of Output)
With Voltage Outputs, Min. 1 Kω
With Voltage Outputs, Capacitive Load, Max. 1 Μf
With Current Outputs, Max. 500 Ω
With Current Outputs, Inductive Load, Max. 1 Mh
Cable Length
Shielded, Max. 200 M; 50 M At 80 Mv And Thermocouples
Analog Value Generation For The Inputs
Integration And Conversion Time/Resolution Per Channel
Resolution With Overrange (Bit Including Sign), Max. 14 Bit; 12 Bit Or 14 Bit, Parameterizable
Analog Value Generation For The Outputs
Settling Time
For Resistive Load 0.1 Ms
For Capacitive Load 3.3 Ms
For Inductive Load 0.5 Ms
Encoder
Connection Of Signal Encoders
For Voltage Measurement Yes
For Current Measurement As 4-Wire Transducer Yes
Connectable Encoders
2-Wire Sensor Yes
— Permissible Quiescent Current (2-Wire Sensor), Max. 1.5 Ma
Errors/Accuracies
Operation Al Error Limit In Overall Temperature Range
Voltage, Relative To Input Range, (+/-) 0.6 %; ±0.6 To ±1%
Current, Relative To Input Range, (+/-) 0.6 %; ±0.6 To ±1%
Resistance Thermometer, Relative To Input Range, (+/-) 0.6 %; ±0.6 To ±1%
Voltage, Relative To Output Range, (+/-) 0.5 %
Current, Relative To Output Range, (+/-) 0.6 %
Basic Error Limit (Operational Limit At 25 °C)
Voltage, Relative To Input Range, (+/-) 0.4 %; 80 Mv: ±0.6 %; 250 To 1 000 Mv: ±0.4 %; 2.5 To 10 V: ±0.6 %; 3.2 To 20
Ma: ±0.5 %
Current, Relative To Input Range, (+/-) 0.4 %; ±0.4 To ±0.6 %
Resistance Thermometer, Relative To Input Range, (+/-) 0.4 %; ±0.4 To ±0.6 %
Voltage, Relative To Output Range, (+/-) 0.3 %
Current, Relative To Output Range, (+/-) 0.5 %
Interrupts/Diagnostics/Status Information
Substitute Values Connectable Yes; Parameterizable
Integrated Functions
Counter No
Control Technology
Number Of Closed-Loop Controllers 4
Potential Separation
Potential Separation Controller
Between The Channels No
Between The Channels And Backplane Bus Yes; Optocoupler
Isolation
Isolation Tested With 500 V Dc
Connection Method
Required Front Connector 2X 20-Pin

Dimensions

Width 80 Mm
Height 125 Mm
Depth 120 Mm
Weight S
Weight , Approx. 470 G