6ES7422-1FH00-0AA0 Siemens - MODULE OUTPUT S7400 16DO 120/230VAC 2A

Extended Description for 6ES7422-1FH00-0AA0 Siemens

6ES7422-1FH00-0AA0 Siemens - SIMATIC S7-400, SM 422 DIGITAL OUTPUT MODULE, OPTIC. ISOLATED, 16 DO, 120/230V AC, 2A

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7422-1FH00-0AA0
Product Description SIMATIC S7-400, digital output SM 422, isolated 16 DO; 120/230 V AC, 2 A
Product family SM 422 digital output module
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 5 Day/Days
Net Weight (kg) 0,954 Kg
Packaging Dimension 23,60 x 30,30 x 4,10
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4019169046114
UPC 662643184297
Commodity Code 85389091
LKZ_FDB/ CatalogID ST74
Product Group 4041
Group Code R338
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.03.2008
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Load Voltage L1
Rated Value (Ac) 230 V; 120/230 V Ac
Permissible Range, Lower Limit (Ac) 79 V
Permissible Range, Upper Limit (Ac) 264 V
Permissible Frequency Range, Lower Limit 47 Hz
Permissible Frequency Range, Upper Limit 63 Hz
Input Current
From Load Voltage L+ (Without Load), Max. 1.5 Ma
From Backplane Bus 5 V Dc, Max. 400 Ma
Power Loss
Power Loss , Typ. 16 W
Digital Outputs
Number Of Digital Outputs 16
Short-Circuit Protection Yes; Fuse 8 A, 250 V; Per Group
Required Current For Fuse Shutdown, Min. 100 A
Response Time, Max. 100 Ms
Control Ling A Digital Input Yes; Possible
Size Of Motor Starters According To Nema, Max. Size 5 According To Nema
Spare Fuses Fuse 8 A, 250 V, Quick Response
Zero-Crossing Switch No
Switching Capacity Of The Outputs
On Lamp Load, Max. 50 W
Output Voltage
For Signal "1", Min. L1 (-18.1 V)
For Signal "1" (At Max. Current), Min. L1 (-1.3 Vrms)
For Signal "1" (At Min. Current), Min. L1 (-18.1 Vrms)
Output Current
For Signal "1" Rated Value 2 A
For Signal "1" Permissible Range, Min. 10 Ma
For Signal "1" Permissible Range, Max. 2 A
For Signal "1" Permissible Surge Current, Max. 50 A; Per Cycle
For Signal "0" Residual Current, Max. 2.6 Ma
Output Delay With Resistive Load
"0" To "1", Max. 1 Ms
"1" To "0", Max. 1 Ac Cycle
Parallel Switching Of Two Outputs
For Redundant Control Of A Load Yes; Possible (Only Outputs With The Same Load Voltage)
Switching Frequency
With Resistive Load, Max. 10 Hz
With Inductive Load, Max. 0.5 Hz
With Inductive Load (Acc. To Iec 60947-5-1, Ac15), Max. 0.5 Hz
On Lamp Load, Max. 1 Hz
Total Current Of The Outputs (Per Group)
All Mounting Positions
— Up To 40 °C, Max. 4 A; 6 A With Fan Assembly
— Up To 60 °C, Max. 2 A; 5 A With Fan Subassembly; Per 4 Adjacent Outputs
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M
Interrupts/Diagnostics/Status Information
Diagnostics Function Not Parameterizable
Diagnostics Indication Led
Internal Fault Intf (Red) Yes; Fuse Blown
External Fault Extf (Red) Yes; Missing Load Voltage
Potential Separation
Potential Separation Digital Outputs
Between The Channels Yes
Between The Channels, In Groups Of 4
Between The Channels And Backplane Bus Yes
Isolation
Isolation Tested With 1 500 V Ac

Dimensions

Width 25 Mm
Height 290 Mm
Depth 210 Mm
Weight S
Weight , Approx. 800 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image