This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6ES7550-1AA00-0AB0

6ES7550-1AA00-0AB0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6ES7550-1AA00-0AB0 Siemens

6ES7550-1AA00-0AB0 Siemens - SIMATIC S7-1500, TM count 2x24 V counter module, 2 channels for 24 V incremental or encoder 3 DI, 2 DQ per channel

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7550-1AA00-0AB0
Product Description SIMATIC S7-1500, TM count 2x24 V counter module, 2 channels for 24 V incremental or encoder 3 DI, 2 DQ per channel
Product family Not available
Product Lifecycle (PLM) PM490:Start of final year of support
PLM Effective Date Product discontinued since: 01.10.2023
Notes Product is no longer available. Successor: 6ES7550-1AA01-0AB0 Compare Products

Successor information

Successor 6ES7550-1AA01-0AB0
Successor Description SIMATIC S7-1500, TM count 2x 24 V counter module, 2 channels for 24 V incremental encoder or pulse encoder, 3 DI, 2 DQ per channel

Delivery information

Export Control Regulations ECCN : EAR99H / AL : N
Estimated dispatch time (Working Days) 60 Day/Days
Net Weight (kg) 0,384 Kg
Packaging Dimension 16,10 x 19,30 x 5,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4025515080008
UPC Not available
Commodity Code 85389091
LKZ_FDB/ CatalogID ST73
Product Group 4B56
Group Code R151
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 25.02.2013
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Product Function

I&M Data Yes; I&M0 To I&M3
Isochronous Mode Yes
Engineering With
Step 7 Tia Portal Configurable/Integrated From Version V12 (Fw V1.0) ... V15 (Fw V1.3)/V12 (Fw V1.0), V13 (Fw V1.1)
Profibus From Gsd Version/Gsd Revision Gsd Revision 5
Profinet From Gsd Version/Gsd Revision V2.3 / -
Installation Type/Mounting
Rail Mounting Yes; S7-1500 Mounting Rail

Supply Voltage

Load Voltage L+
Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Input Current
Current Consumption, Max. 75 Ma; Without Load
Encoder Supply
Number Of Outputs 1; A Common 24V Encoder Supply For Both Channels
24 V Encoder Supply
24 V Yes; L+ (-0.8 V)
Short-Circuit Protection Yes
Output Current, Max. 1 A; Total Current Of All Encoders/Channels
Power
Power Available From The Backplane Bus 1.3 W
Power Loss
Power Loss , Typ. 4 W
Address Area
Address Space Per Module
Inputs 16 Byte; Per Channel
Outputs 12 Byte; Per Channel; 4 Bytes For Motion Control
Digital Inputs
Number Of Digital Inputs 6; 3 Per Channel
Digital Inputs, Parameterizable Yes
Input Characteristic Curve In Accordance With Iec 61131, Type 3 Yes
Digital Input Functions, Parameterizable
Gate Start/Stop Yes
Capture Yes
Synchronization Yes
Freely Usable Digital Input Yes
Input Voltage
Type Of Input Voltage Dc
Rated Value (Dc) 24 V
For Signal "0" -5 ... +5 V
For Signal "1" +11 To +30V
Permissible Voltage At Input, Min. -30 V; -5 V Continuous, -30 V Brief Reverse Polarity Protection
Permissible Voltage At Input, Max. 30 V
Input Current
For Signal "1", Typ. 2.5 Ma
Input Delay (For Rated Value Of Input Voltage)
For Standard Inputs
— Parameterizable Yes; None / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 Ms
— At "0" To "1", Min. 6 Μs; For Parameterization "None"
— At "1" To "0", Min. 6 Μs; For Parameterization "None"
For Technological Functions
— Parameterizable Yes
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M
Digital Outputs
Type Of Digital Output Transistor
Number Of Digital Outputs 4; 2 Per Channel
Digital Outputs, Parameterizable Yes
Short-Circuit Protection Yes; Electronic/Thermal
Response Threshold, Typ. 1 A
Limitation Of Inductive Shutdown Voltage To L+ (-33 V)
Control Ling A Digital Input Yes
Digital Output Functions, Parameterizable
Switching Tripped By Comparison Values Yes
Freely Usable Digital Output Yes
Switching Capacity Of The Outputs
With Resistive Load, Max. 0.5 A; Per Digital Output
On Lamp Load, Max. 5 W
Load Resistance Range
Lower Limit 48 Ω
Upper Limit 12 Kω
Output Voltage
Type Of Output Voltage Dc
For Signal "1", Min. 23.2 V; L+ (-0.8 V)
Output Current
For Signal "1" Rated Value 0.5 A; Per Digital Output
For Signal "1" Permissible Range, Max. 0.6 A; Per Digital Output
For Signal "1" Minimum Load Current 2 Ma
For Signal "0" Residual Current, Max. 0.5 Ma
Output Delay With Resistive Load
"0" To "1", Max. 50 Μs
"1" To "0", Max. 50 Μs
Switching Frequency
With Resistive Load, Max. 10 Khz
With Inductive Load, Max. 0.5 Hz; Acc. To Iec 60947-5-1, Dc-13; Observe Derating Curve
On Lamp Load, Max. 10 Hz
Total Current Of The Outputs
Current Per Module, Max. 2 A
Cable Length
Shielded, Max. 1 000 M
Unshielded, Max. 600 M
Encoder
Connectable Encoders
2-Wire Sensor Yes
— Permissible Quiescent Current (2-Wire Sensor), Max. 1.5 Ma
Encoder Signals, Incremental Encoder (Asymmetrical)
Input Voltage 24 V
Input Frequency, Max. 200 Khz
Counting Frequency, Max. 800 Khz; With Quadruple Evaluation
Cable Length, Shielded, Max. 600 M; Depending On Input Frequency, Encoder And Cable Quality; Max. 50 M At
200 Khz
Signal Filter, Parameterizable Yes
Incremental Encoder With A/B Tracks, 90° Phase Offset Yes
Incremental Encoder With A/B Tracks, 90° Phase Offset
And Zero Trackyes
Pulse Encoder Yes
Pulse Encoder With Direction Yes
Pulse Encoder With One Impulse Signal Per Count Direction Yes
Interface Types
Source/Sink Input Yes
Input Characteristic Curve In Accordance With Iec 61131,
Type 3Yes
Isochronous Mode
Filtering And Processing Time (Tci), Min. 130 Μs
Bus Cycle Time (Tdp), Min. 250 Μs
Interrupts/Diagnostics/Status Information
Alarms
Diagnostic Alarm Yes
Hardware Interrupt Yes
Diagnoses
Monitoring The Supply Voltage Yes
Wire-Break Yes
Short-Circuit Yes
A/B Transition Error At Incremental Encoder Yes
Diagnostics Indication Led
Run Led Yes; Green Led
Error Led Yes; Red Led
Maint Led Yes; Yellow Led
Monitoring Of The Supply Voltage (Pwr-Led) Yes; Green Led
Channel Status Display Yes; Green Led
For Channel Diagnostics Yes; Red Led
Status Indicator Forward Counting (Green) Yes
Status Indicator Backward Counting (Green) Yes
Integrated Functions
Counter Yes
Number Of Counters 2
Counting Frequency, Max. 800 Khz; With Quadruple Evaluation
Counting Functions
Can Be Used With To High_Speed_Counter Yes
Continuous Counting Yes
Counter Response Parameterizable Yes
Hardware Gate Via Digital Input Yes
Software Gate Yes
Event-Controlled Stop Yes
Synchronization Via Digital Input Yes
Counting Range, Parameterizable Yes
Comparator
— Number Of Comparators 2; Per Channel
— Direction Dependency Yes
— Can Be Changed From User Program Yes
Position Detection
Incremental Acquisition Yes
Suitable For S7-1500 Motion Control Yes

Measuring Functions

Measuring Time, Parameterizable Yes
Dynamic Measurement Period Adjustment Yes
Number Of Thresholds, Parameterizable 2
Measuring Range
— Frequency Measurement, Min. 0.04 Hz
— Frequency Measurement, Max. 800 Khz
— Cycle Duration Measurement, Min. 1.25 Μs
— Cycle Duration Measurement, Max. 25 S
Accuracy
— Frequency Measurement 100 Ppm; Depending On Measuring Interval And Signal Evaluation
— Cycle Duration Measurement 100 Ppm; Depending On Measuring Interval And Signal Evaluation
— Velocity Measurement 100 Ppm; Depending On Measuring Interval And Signal Evaluation
Potential Separation
Potential Separation Channels
Between The Channels No
Between The Channels And Backplane Bus Yes
Between The Channels And Load Voltage L+ No
Isolation
Isolation Tested With 707 V Dc (Type Test)

Ambient Temperature During Operation

Horizontal Installation, Min. 0 °C
Horizontal Installation, Max. 60 °C; Please Note Derating For Inductive Loads
Vertical Installation, Min. 0 °C
Vertical Installation, Max. 40 °C; Please Note Derating For Inductive Loads
Altitude During Operation Relating To Sea Level
Installation Altitude Above Sea Level, Max. 5 000 M; Restrictions For Installation Altitudes > 2 000 M, See Et 200Mp System
Manual
Decentralized Operation
To Simatic S7-300 Yes
To Simatic S7-400 Yes
To Simatic S7-1200 Yes
To Simatic S7-1500 Yes
To Standard Profibus Master Yes; Fw V1.1 And Higher
To Standard Profinet Controller Yes

Dimensions

Width 35 Mm
Height 147 Mm
Depth 129 Mm
Weight S
Weight , Approx. 250 G

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible