Description for 6ES7677-2FA41-0FM0 Siemens

6ES7677-2FA41-0FM0 Siemens - SIMATIC ET 200SP Open Controllers, CPU 1515SP PC F +HMI 2048PT, 4 GB RAM, 30 GB CFAST with WES 7 P 64 bit pre-installed, mit S7-1500 Fail-safe SWC CPU 1505SP F pre-installed with WinCC Runtime Advanced V14 pre-installed with 2048 PowerTags license, Interfaces: 1x slot CFAST, 1x slot SD/MMC, 1x connection for ET 200SP bus adapter PROFINET 1x 10/100/1000 Mbit/s Ethernet, 3x USB, 1x DVI-I graphics card connection, Documentation on DVD, Restore DVD

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6ES7677-2FA41-0FM0
Product Description SIMATIC ET 200SP Open Controllers, CPU 1515SP PC F +HMI 2048PT, 4 GB RAM, 30 GB CFAST with WES 7 P 64 bit pre-installed, mit S7-1500 Fail-safe SWC CPU 1505SP F pre-installed with WinCC Runtime Advanced V14 pre-installed with 2048 PowerTags license, Interfaces: 1x slot CFAST, 1x slot SD/MMC, 1x connection for ET 200SP bus adapter PROFINET 1x 10/100/1000 Mbit/s Ethernet, 3x USB, 1x DVI-I graphics card connection, Documentation on DVD, Restore DVD
Product family Not available
Product Lifecycle (PLM) PM490:Start of final year of support
PLM Effective Date Product discontinued since: 01.01.2023
Notes Product was deleted without replacement If you need assistance please contact our local Siemens office

Delivery information

Export Control Regulations ECCN : 5A992 / AL : N
Estimated dispatch time (Working Days) 15 Day/Days
Net Weight (kg) 1,073 Kg
Packaging Dimension 14,40 x 19,20 x 9,50
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4047623407942
UPC 804766522628
Commodity Code 85371091
LKZ_FDB/ CatalogID STWINAC
Product Group 4A7C
Group Code R152
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 16.12.2016
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 2,2',6,6'-tetrabromo... CAS-No. 79-94-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Supply Voltage

Rated Value (Dc) 24 V
Permissible Range, Lower Limit (Dc) 19.2 V
Permissible Range, Upper Limit (Dc) 28.8 V
Reverse Polarity Protection Yes
Mains Buffering
Mains/Voltage Failure Stored Energy Time 5 Ms
Input Current
Current Consumption (Rated Value) 1.5 A; Full Processor Load, Incl. Et 200Sp Modules And Using Usb
Current Consumption (In No-Load Operation), Typ. 0.6 A
Inrush Current, Max. 4.7 A; Rated Value
Power
Active Power Input, Max. 36 W; Incl. Et 200Sp Modules And Using Usb
Infeed Power To The Backplane Bus 8.75 W
Power Loss
Power Loss , Typ. 15 W; Without Et 200Sp Modules And Without Using Usb
Processor
Processor Type Dual-Core 1 Ghz, Amd G Series Apu T40E
Memory
Type Of Memory Ddr3-Sdram
Main Memory 4 Gb Ram
Cfast Memory Card Yes; 30 Gb Flash Memory
Simatic Memory Card Required No
Work Memory
Integrated (For Program) 1.5 Mbyte
Integrated (For Data) 5 Mbyte
Integrated (For Cpu Function Library Of Cpu Runtime) 10 Mbyte
Load Memory
Integrated (On Pc Mass Storage) 320 Mbyte
Backup
With Ups Yes; All Memory Areas Declared Retentive
With Non-Volatile Memory Yes
Cpu Processing Times
For Bit Operations, Typ. 10 Ns
For Word Operations, Typ. 12 Ns
For Fixed Point Arithmetic, Typ. 16 Ns
For Floating Point Arithmetic, Typ. 64 Ns
Cpu-Blocks
Number Of Elements (Total) 6 000; In Addition To Blocks Such As Dbs, Fbs And Fcs, Udts, Global
Constants, Etc. Are Also Regarded As Elements
Db
Number, Max. 5 999; Number Range: 1 To 65535
Size, Max. 5 Mbyte
Fb
Number, Max. 5 998; Number Range: 1 To 65535
Size, Max. 512 Kbyte
Fc
Number, Max. 5 999; Number Range: 1 To 65535
Size, Max. 512 Kbyte
Ob
Size, Max. 1 048 Kbyte
Number Of Free Cycle Obs 100
Number Of Time Alarm Obs 20
Number Of Delay Alarm Obs 20
Number Of Cyclic Interrupt Obs 20
Number Of Process Alarm Obs 50
Number Of Dpv1 Alarm Obs 3
Number Of Isochronous Mode Obs 1
Number Of Technology Synchronous Alarm Obs 2
Number Of Startup Obs 100
Number Of Asynchronous Error Obs 4
Number Of Synchronous Error Obs 2
Number Of Diagnostic Alarm Obs 1
Nesting Depth
Per Priority Class 24; Up To 8 Possible For F-Blocks
Counters, Timers And Their Retentivity
S7 Counter
Number 2 048
Retentivity
— Adjustable Yes
Iec Counter
Number Any (Only Limited By The Main Memory)
Retentivity
— Adjustable Yes
S7 Times
Number 2 048
Retentivity
— Adjustable Yes
Iec Timer
Number Any (Only Limited By The Main Memory)
Retentivity
— Adjustable Yes
Data Areas And Their Retentivity
Retentive Data Area (Incl. Timers, Counters, Flags), Max. 410 Kbyte; For Storage In Nvram; For Storage In Mass Storage 5 242 020 Bytes
Flag
Size, Max. 16 Kbyte
Number Of Clock Memories 8; 8 Clock Memory Bit, Grouped Into One Clock Memory Byte
Data Blocks
Retentivity Adjustable Yes
Retentivity Preset No
Local Data
Per Priority Class, Max. 64 Kbyte; Max. 16 Kb Per Block
Address Area
Number Of Io Modules 8 192
I/O Address Area
Inputs 32 Kbyte; All Inputs Are In The Process Image
Outputs 32 Kbyte; All Outputs Are In The Process Image
Of Which Per Assigned Pc Interface
— Inputs (Volume) 8 Kbyte
— Outputs (Volume) 8 Kbyte
Subprocess Images
Number Of Subprocess Images, Max. 32
Hardware Configuration
Integrated Power Supply Yes
Number Of Distributed Io Systems 20
Number Of Dp Masters
Via Cm 1
Rack
Modules Per Rack, Max. 64; Cpu 1515Sp Pc + 64 Modules + Server Module
Number Of Lines, Max. 1
Ptp Cm
Number Of Ptp Cms The Number Of Connectable Ptp Cms Is Only Limited By The Number Of Available
Slots
Time Of Day
Clock
Type Hardware Clock
Hardware Clock (Real-Time) Yes; Resolution: 1 S
Backup Time 6 Wk; At 40 °C Ambient Temperature, Typically
Deviation Per Day, Max. 10 S; Typ.: 2 S
Clock Synchronization
Supported Yes
To Dp, Master No
On Ethernet Via Ntp Yes
On Windows Clock, Device Yes
Interfaces
Number Of Industrial Ethernet Interfaces 2
Number Of Profinet Interfaces 1
Number Of Profibus Interfaces 1
Number Of Rs 485 Interfaces 1; Via Cm Dp Module
Number Of Usb Interfaces 3; 3X Usb 2.0 On The Front, 500 Ma Each - Of Which 2X 500 Ma And 1X 100 Ma
Simultaneously
Number Of Sd Card Slots 1
Video Interfaces
Graphics Interface 1X Dvi-I
1. Interface
Interface Type Profinet
Automatic Detection Of Transmission Rate Yes
Autonegotiation Yes
Autocrossing Yes
Number Of Connections 88
Interface Types
Rj 45 (Ethernet) Yes; Via Busadapter Ba 2X Rj45
— Transmission Rate, Max. 100 Mbit/S
— Industrial Ethernet Status Led Yes
Number Of Ports 2
Integrated Switch Yes
Busadapter (Profinet) Yes; Applicable Busadapter: Ba 2X Rj45, Ba 2X Fc
Protocols
Profinet Io Controller Yes
Profinet Io Device Yes
Simatic Communication Yes
Open Ie Communication Yes
Web Server Yes
Profinet Io Controller
Services
— Isochronous Mode Yes
— Shortest Clock Pulse 500 Μs
— Irt Yes
— Prioritized Startup Yes; Max. 32 Profinet Devices
— Number Of Connectable Io Devices, Max. 128
— Of Which Io Devices With Irt, Max. 64
— Of Which In Line, Max. 64
— Number Of Connectable Io Devices For Rt, Max. 128
— Of Which In Line, Max. 128
— Number Of Io Devices That Can Be Simultaneously
Activated/Deactivated, Max.8
— Io Devices Changing During Operation (Partner
Ports), Supportedyes
— Number Of Io Devices Per Tool, Max. 8
— Updating Times The Minimum Value Of The Update Time Also Depends On Communication Share
Set For Profinet Io, On The Number Of Io Devices, And On The Quantity Of
Configured User Data
Update Time For Irt
— For Send Cycle Of 500 Μs 500 Μs To 8 Ms
— For Send Cycle Of 1 Ms 1 Ms To 16 Ms
— For Send Cycle Of 2 Ms 2 Ms To 32 Ms
— For Send Cycle Of 4 Ms 4 Ms To 64 Ms
— With Irt And Parameterization Of "Odd" Send Cycles Update Time = Set "Odd" Send Clock (Any Multiple Of 125 Μs: 375 Μs, 625 Μs ... 3
875 Μs)
Update Time For Rt
— For Send Cycle Of 500 Μs 500 Μs To 256 Ms
— For Send Cycle Of 1 Ms 1 Ms To 512 Ms
— For Send Cycle Of 2 Ms 2 Ms To 512 Ms
— For Send Cycle Of 4 Ms 4 Ms To 512 Ms
Profinet Io Device
Services
— Isochronous Mode No
— Irt Yes
— Prioritized Startup Yes
— Shared Device Yes
— Number Of Io Controllers With Shared Device, Max. 4
2. Interface
Interface Type Integrated Ethernet Interface
Automatic Detection Of Transmission Rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface Types
Rj 45 (Ethernet) Yes; Integrated
— Transmission Rate, Max. 1 000 Mbit/S
— Industrial Ethernet Status Led No
Number Of Ports 1
3. Interface
Interface Type Profibus With Cm Dp
Number Of Connections 44
Interface Types
Rs 485 Yes
Protocols
Profibus Dp Master Yes
Profibus Dp Device Yes
Simatic Communication Yes
Profibus Dp Master
Max. Number Of Dp Devices 125
Services
— Equidistance No
— Isochronous Mode No
Interface Types
Rs 485
Transmission Rate, Max. 12 Mbit/S
Protocols
Profisafe Yes; V2.4 / V2.6
Number Of Connections
Number Of Connections, Max. 88
Number Of Connections Reserved For Es/Hmi/Web 10
Number Of S7 Routing Paths 16
Redundancy Mode
Media Redundancy
— Mrp Yes
— Mrpd Yes
— Switchover Time On Line Break, Typ. 200 Ms
— Number Of Stations In The Ring, Max. 50
Simatic Communication
Pg/Op Communication Yes
S7 Routing Yes
S7 Communication, As Server Yes
S7 Communication, As Client Yes
User Data Per Job, Max. 64 Kbyte
Open Ie Communication
Tcp/Ip Yes
— Data Length, Max. 64 Kbyte
Iso-On-Tcp (Rfc1006) Yes
— Data Length, Max. 64 Kbyte
Udp Yes
— Data Length, Max. 1 472 Kbyte
Snmp Yes
Dcp Yes
Lldp Yes
Web Server
Http Yes; Via Windows And Profinet Interface
Https Yes; Only Via Profinet Interface
Opc Ua
Opc Ua Server Yes; Data Access (Read, Write, Subscribe), Runtime License Required
— Application Authentication Yes; Available Security Policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256
— Security Policies Yes; Available Security Policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256
— User Authentication Yes; "Anonymous" Or By User Name & Password
Further Protocols
Modbus Yes; Modbus Tcp
S7 Message Functions
Number Of Login Stations For Message Functions, Max. 32
Program Alarms Yes
Number Of Configurable Program Messages, Max. 10 000
Number Of Simultaneously Active Program Alarms
Number Of Program Alarms 1 000
Number Of Alarms For System Diagnostics 200
Number Of Alarms For Motion Technology Objects 160
Test Commissioning Functions
Joint Commission (Team Engineering) Yes; Parallel Online Access Possible For Up To 8 Engineering Systems
Status Block Yes; Up To 8 Simultaneously
Single Step No
Status/Control
Status/Control Variable Yes
Variables Inputs, Outputs, Memory Bits, Db, Times, Counters
Number Of Variables, Max.
— Of Which Status Variables, Max. 200
— Of Which Control Variables, Max. 200
Forcing
Forcing Yes
Forcing, Variables Inputs, Outputs
Number Of Variables, Max. 200
Diagnostic Buffer
Present Yes
Number Of Entries, Max. 1 000
— Of Which Powerfail-Proof 300
Traces
Number Of Configurable Traces 4
Memory Size Per Trace, Max. 512 Kbyte
Interrupts/Diagnostics/Status Information
Diagnostics Indication Led
Run/Stop Led Yes
Error Led Yes
Maint Led Yes
Supported Technology Objects
Motion Control Yes
Number Of Available Motion Control Resources For
Technology Objects2 400
Required Motion Control Resources
— Per Speed-Controlled Axis 40; Per Axis
— Per Positioning Axis 80; Per Axis
— Per Synchronous Axis 160; Per Axis
— Per External Encoder 80; Per External Encoder
— Per Output Cam 20; Per Cam
— Per Cam Track 160; Per Cam Track
— Per Probe 40; Per Probe
Positioning Axis
— Number Of Positioning Axes At Motion Control Cycle
Of 4 Ms (Typical Value)5
— Number Of Positioning Axes At Motion Control Cycle
Of 8 Ms (Typical Value)12
Control Ler
Pid_Compact Yes; Universal Pid Controller With Integrated Optimization
Pid_3Step Yes; Pid Controller With Integrated Optimization For Valves
Pid-Temp Yes; Pid Controller With Integrated Optimization For Temperature
Counting And Measuring
High-Speed Counter Yes
Standards, Approvals, Certificates
Ce Mark Yes
Csa Approval Yes
Culus Yes
Fm Approval Yes
Rcm (Formerly C-Tick) Yes
Highest Safety Class Achievable In Safety Mode
Performance Level According To Iso 13849-1 Ple
Sil Acc. To Iec 61508 Sil 3
Probability Of Failure (For Service Life Of 20 Years And Repair Time Of 100 Hours)
— Low Demand Mode: Pfdavg In Accordance With
Sil3< 2.00E-05
— High Demand/Continuous Mode: Pfh In Accordance
With Sil3< 1.00E-09 1/H

Ambient Temperature During Operation

Min. 0 °C
Up To 60 °C With Max. 32 Et 200Sp Modules And 3X 100 Ma Usb Load; Up To Max.
55 °C With Max. 64 Et 200Sp Modules And 2X Max. 500 Ma And 1X Max. 100
Ma Usb Load
Horizontal Installation, Min. 0 °C
Horizontal Installation, Max. 60 °C
Vertical Installation, Min. 0 °C
Vertical Installation, Max. 50 °C; With Max. 32 Et 200Sp Modules And 3X 100 Ma Usb Load
Ambient Temperature During Storage/Transportation
Min. -40 °C
Max. 70 °C
Vibrations
Operation, Tested According To Iec 60068-2-6 Yes
Transport, Tested Acc. To Iec 60068-2-6 Yes
Shock Testing
Tested According To Iec 60068-2-6 Yes
Tested According To Iec 60068-2-27 Yes
Tested According To Iec 60068-2-29 Yes
Storage/Transport, Tested Acc. To Iec 60068-2-27 Yes

Operating Systems

Pre-Installed Operating System Windows Embedded Standard 7 P 64-Bit
Configuration / Header
Configuration / Programming / Header
Programming Language
— Lad Yes; Incl. Failsafe
— Fbd Yes; Incl. Failsafe
— Stl Yes
— Scl Yes
— Cfc No
— Graph Yes
Know-How Protection
User Program Protection/Password Protection Yes
Copy Protection Yes
Block Protection Yes
Access Protection
Protection Level: Write Protection Yes
Protection Level: Read/Write Protection Yes
Protection Level: Complete Protection Yes
Programming / Cycle Time Monitoring / Header
Lower Limit Adjustable Minimum Cycle Time
Upper Limit Adjustable Maximum Cycle Time
Open Development Interfaces
Size Of Odk So File, Max. 3.8 Mbyte
Peripherals/Options
Sd Card Optionally For Additional Mass Storage

Dimensions

Width 160 Mm
Height 117 Mm
Depth 75 Mm
Weight S
Weight , Approx. 0.83 Kg

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible