This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6SL3210-1KE23-2AP1

6SL3210-1KE23-2AP1 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6SL3210-1KE23-2AP1 Siemens

6SL3210-1KE23-2AP1 Siemens - SINAMICS G120C rated power 3AC380-480V +10/-20% 47-63Hz low overload: 15,0kW at 150% 3s, 110% 57s, 100% 240s high overload: 11,0kW at 200% 3s, 150% 57s, 100% 240s integrated filter class A external 24V I/O interface: 6DI, 2DO,1AI,1AO, 1Mot_t Safe Torque Off integrated Fieldbus: PROFIBUS-DP Protection: IP20/ UL OPEN TYPE Size: FSC 295X140X203(HXWXD)

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6SL3210-1KE23-2AP1
Product Description SINAMICS G120C rated power 3AC380-480V +10/-20% 47-63Hz low overload: 15,0kW at 150% 3s, 110% 57s, 100% 240s high overload: 11,0kW at 200% 3s, 150% 57s, 100% 240s integrated filter class A external 24V I/O interface: 6DI, 2DO,1AI,1AO, 1Mot_t Safe Torque Off integrated Fieldbus: PROFIBUS-DP Protection: IP20/ UL OPEN TYPE Size: FSC 295X140X203(HXWXD)
Product family Not available
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : N
Estimated dispatch time (Working Days) 3 Day/Days
Net Weight (kg) 5,500 Kg
Packaging Dimension 365,00 x 270,00 x 160,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948663394
UPC 887621065485
Commodity Code 85044095
LKZ_FDB/ CatalogID D11.1SD
Product Group 5673
Group Code R220
Country of origin Great Britain
Compliance with the substance restrictions according to RoHS directive Since: 01.07.2006
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): 4,4'-isopropylidenediphenol (Bisphenol A, BPA) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Diboron trioxide CAS-No. 1303-86-2 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Diboron trioxide Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Rated Data

Input
Number Of Phases 3 Ac
Line Voltage 380 ... 480 V +10 % -20 %
Line Frequency 47 ... 63 Hz
Rated Current (Lo) 40.60 A
Rated Current (Ho) 36.40 A
Output
Number Of Phases 3 Ac
Rated Voltage 400V Iec 480V Nec 1)
Rated Power (Lo) 15.00 Kw 20.00 Hp
Rated Power (Ho) 11.00 Kw 15.00 Hp
Rated Current (Lo) 31.00 A
Rated Current (Ho) 25.00 A
Rated Current (In) 32.00 A
Max. Output Current 50.00 A
Pulse Frequency 4 Khz
Output Frequency For Vector Control 0 ... 240 Hz
Output Frequency For V/F Control 0 ... 550 Hz
Overload Capability
Low Overload (Lo)
150 % Base Load Current Il For 3 S, Followed By 110 % Base Load Current Il For 57 S
In A 300 S Cycle Time
High Overload (Ho)
200% Base Load Current Ih For 3 S, Followed By 150% Base Load Current Ih For 57 S
In A 300 S Cycle Time

General Tech. Specifications

Power Factor Λ 0.70 ... 0.85
Offset Factor Cos Φ 0.95
Efficiency Η 0.97
Sound Pressure Level (1M) 66 Db
Power Loss 371.0 W
Filter Class (Integrated) Class A

Communication

Communication Profibus Dpinputs / Outputs
Standard Digital Inputs
Number 6
Switching Level: 0→1 11 V
Switching Level: 1→0 5 V
Max. Inrush Current 15 Ma

Fail-Safe Digital Inputs

Number 1
Digital Outputs
Number As Relay Changeover Contact 1
Output (Resistive Load) Dc 30 V, 0.5 A
Number As Transistor 1
Output (Resistive Load) Dc 30 V, 0.5 A
Analog / Digital Inputs
Number 1 (Differential Input)
Resolution 10 Bit
Switching Threshold As Digital Input
0→1 4 V
1→0 1.6 V
Analog Outputs
Number 1 (Non-Isolated Output)
Ptc/ Kty Interface
1 Motor Temperature Sensor Input, Sensors That Can Be Connected Ptc, Kty And
Thermo-Click, Accuracy ±5 °C
Closed-Loop Control Techniques
V/F Linear / Square-Law / Parameterizable Yes
V/F With Flux Current Control (Fcc) Yes
V/F Eco Linear / Square-Law Yes
Sensorless Vector Control Yes
Vector Control, With Sensor No
Encoderless Torque Control No
Torque Control, With Encoder No
Article No. : 6Sl3210-1Ke23-2Ap1
Technical Data Are Subject To Change! There May Be Discrepancies Between Calculated And Rating Plate Values. Page 2 Of 2 Generated Mon Dec 23 12:37:52 Cet 2024

Ambient Conditions

Cooling Air Cooling Using An Integrated Fan
Cooling Air Requirement 0.018 M³/S (0.636 Ft³/S)
Installation Altitude 1,000 M (3,280.84 Ft)
Ambient Temperature
Operation -10 ... 40 °C (14 ... 104 °F)
Transport -40 ... 70 °C (-40 ... 158 °F)
Storage -25 ... 55 °C (-13 ... 131 °F)
Relative Humidity
Max. Operation95 % At 40 °C (104 °F), Condensation
And Icing Not Permissible

Connections

Signal Cable
Conductor Cross-Section 0.15 ... 1.50 Mm²
(Awg 24 ... Awg 16)

Line Side

Version Plug-In Screw Terminals
Conductor Cross-Section 6.00 ... 16.00 Mm²
(Awg 10 ... Awg 6)

Motor End

Version Plug-In Screw Terminals
Conductor Cross-Section 6.00 ... 16.00 Mm²
(Awg 10 ... Awg 6)
Dc Link (For Braking Resistor)
Version Plug-In Screw Terminals
Conductor Cross-Section 6.00 ... 16.00 Mm²
(Awg 10 ... Awg 6)
Line Length, Max. 15 M (49.21 Ft)
Pe Connection On Housing With M4 Screw

Max. Motor Cable Length

Shielded 50 M (164.04 Ft)
Unshielded 100 M (328.08 Ft)

Mechanical Data

Degree Of Protection Ip20 / Ul Open Type
Frame Size Fsc
Net Weight 4.40 Kg (9.70 Lb)

Dimensions

Width 140 Mm (5.51 In)
Height 295 Mm (11.61 In)
Depth 203 Mm (7.99 In)

Standards

Compliance With Standards Ce, Cul, Ul, Kc, Eac, C-Tick (Rcm)
Ce Marking Emc Directive 2004/108/Ec, Low-
Voltage Directive 2006/95/Ecconverter Losses To Iec61800-9-2*
Efficiency Class Ie2
Comparison With The Reference
Converter (90% / 100%)34.2 %
The Percentage Values Show The Losses In Relation To The Rated Apparent Power Of
The Converter.
The Diagram Shows The Losses For The Points (As Per Standard Iec61800-9-2) Of
The Relative Torque Generating Current (I) Over The Relative Motor Stator Frequency
(F). The Values Are Valid For The Basic Version Of The Converter Without
Options/Components.
*Calculated Values
1)The Output Current And Hp Ratings Are Valid For The Voltage Range 440V-480V177.0 W (0.8 %)
144.0 W (0.7 %)276.0 W (1.3 %) 315.0 W (1.5 %) 371.0 W (1.7 %)
214.0 W (1.0 %) 193.0 W (0.9 %)
151.0 W (0.7 %)
F 90% 50%25%50%I
100%

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible