This webshop is for business use only (B2B) – Orders accepted from registered companies and organisations only. Company details required at checkout.

Siemens

6SL3210-1PE34-8AL0

6SL3210-1PE34-8AL0 Siemens

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for 6SL3210-1PE34-8AL0 Siemens

6SL3210-1PE34-8AL0 Siemens - SINAMICS G120/S120 POWER MODULE PM240-2 FSG C2 WITH BUILT IN BRAKING CHOPPER 3AC380-480V+10/-10% 47-63Hz OUTPUT HIGH OVERLOAD: 200kW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP -20 bis +50 DEG C (HO) OUTPUT LOW OVERLOAD: 250kW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP -20 bis +40 DEG C (LO) 1000x305x357 (HXWXD), FSG PROTECTION IP20 WITHOUT CONTROL UNIT AND PANEL APPROVED FOR CU FIRMWARE- Version V4.7 SP9 AND V5.1

Free Delivery to UK Mainland on orders over £25

Product

Article Number (Market Facing Number) 6SL3210-1PE34-8AL0
Product Description SINAMICS G120/S120 POWER MODULE PM240-2 FSG C2 WITH BUILT IN BRAKING CHOPPER 3AC380-480V+10/-10% 47-63Hz OUTPUT HIGH OVERLOAD: 200kW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP -20 bis +50 DEG C (HO) OUTPUT LOW OVERLOAD: 250kW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP -20 bis +40 DEG C (LO) 1000x305x357 (HXWXD), FSG PROTECTION IP20 WITHOUT CONTROL UNIT AND PANEL APPROVED FOR CU FIRMWARE- Version V4.7 SP9 AND V5.1
Product family Not available
Product Lifecycle (PLM) PM300:Active Product

Delivery information

Export Control Regulations AL : N / ECCN : 9N9999
Estimated dispatch time (Working Days) 15 Day/Days
Net Weight (kg) 122,000 Kg
Packaging Dimension 1190,00 x 395,00 x 591,00
Package size unit of measure MM
Quantity Unit 1 Piece
Packaging Quantity 1

Additional Product Information

EAN 4042948676820
UPC 804766567797
Commodity Code 85044095
LKZ_FDB/ CatalogID D11.1SD
Product Group 2255
Group Code R220
Country of origin Germany
Compliance with the substance restrictions according to RoHS directive Since: 01.01.2018
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty to inform according to the current list of candidates Lead CAS-No. 7439-92-1 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Lead monoxide (lead oxide) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Tris(2-chloroethyl) ... CAS-No. 115-96-8 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Tris(2-chloroethyl) phosphate (TCEP) Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. | Cadmium oxide CAS-No. 1306-19-0 > 0, 1 % (w / w) Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w): Cadmium oxide Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
SCIP number

Rated Data

Input
Number Of Phases 3 Ac
Line Voltage 380 ... 480 V ±10 %
Line Frequency 47 ... 63 Hz
Rated Current (Lo) 470.00 A
Rated Current (Ho) 400.00 A
Output
Number Of Phases 3 Ac
Rated Voltage 400V Iec 480V Nec 1)
Rated Power (Lo) 250.00 Kw 400.00 Hp
Rated Power (Ho) 200.00 Kw 300.00 Hp
Rated Current (Lo) 477.00 A
Rated Current (Ho) 370.00 A
Max. Output Current 740.00 A
Pulse Frequency 2 Khz
Output Frequency For Vector Control 0 ... 200 Hz
Output Frequency For V/F Control 0 ... 550 Hz
Overload Capability
Low Overload (Lo)
1.1 X Rated Output Current (I.E. 110 % Overload) For 57 S With A Cycle Time Of
300 S 1.5 × Rated Output Current (I.E. 150 % Overload) For 3 S With A Cycle Time
Of 300 S
High Overload (Ho)
1.5 × Output Current Rating (I.E., 150 % Overload) For 57 S With A Cycle Time Of
300 S 2 × Output Current Rating (I.E., 200 % Overload) For 3 S With A Cycle Time
Of 300 S

General Tech. Specifications

Power Factor Λ 0.90
Offset Factor Cos Φ 0.98
Efficiency Η 0.98
Sound Pressure Level (1M) 75 Db
Power Loss 6.17 Kw
Filter Class (Integrated) Class A

Ambient Conditions

Cooling Internal Air Cooling
Cooling Air Requirement 0.210 M³/S (7.416 Ft³/S)
Installation Altitude 1,000 M (3,280.84 Ft)
Ambient Temperature
Operation Lo -20 ... 40 °C (-4 ... 104 °F)
Operation Ho -20 ... 50 °C (-4 ... 122 °F)
Transport -25 ... 55 °C (-13 ... 131 °F)
Storage -25 ... 55 °C (-13 ... 131 °F)
Relative Humidity
Max. Operation 95 % Rh, Condensation Not Permitted

Line Side

Version M10 Bolt
Conductor Cross-Section 35.00 ... 2 X 185.00 Mm²
(Awg 2 ... Awg -5)

Motor End

Version M10 Bolt
Conductor Cross-Section 35.00 ... 2 X 185.00 Mm²
(Awg 2 ... Awg -5)
Dc Link (For Braking Resistor)
Version Screw-Type Terminals
Conductor Cross-Section 25.00 ... 70.00 Mm²
(Awg 4 ... Awg -1)
Cable Length 10 M (32.81 Ft)
Pe Connection M10 Screw Studs

Max. Motor Cable Length

Shielded 300 M (984.25 Ft)
Unshielded 450 M (1,476.38 Ft)

Mechanical Data

Degree Of Protection Ip20 / Ul Open Type
Frame Size Fsg
Net Weight 119.40 Kg (263.23 Lb)

Dimensions

Width 305 Mm (12.01 In)
Height 1,000 Mm (39.37 In)
Depth 357 Mm (14.06 In)

Standards

Compliance With Standards Ul, Cul, Ce, C-Tick (Rcm), Eac, Semi
F47
Ce Marking Low-Voltage Directive 2006/95/Ec
Data Sheet For Sinamics Power Module Pm240-2
Article No. : 6Sl3210-1Pe34-8Al0
Technical Data Are Subject To Change! There May Be Discrepancies Between Calculated And Rating Plate Values. Page 2 Of 2 Generated Mon Dec 23 13:19:26 Cet 2024
Converter Losses To Iec61800-9-2*
Efficiency Class Ie2
Comparison With The Reference
Converter (90% / 100%)45.70 %
The Percentage Values Show The Losses In Relation To The Rated Apparent Power Of
The Converter.
The Diagram Shows The Losses For The Points (As Per Standard Iec61800-9-2) Of
The Relative Torque Generating Current (I) Over The Relative Motor Stator Frequency
(F). The Values Are Valid For The Basic Version Of The Converter Without
Options/Components.
*Calculated Values
1)The Output Current And Hp Ratings Are Valid For The Voltage Range 440V-480V1,970.0 W (0.60 %)
1,300.0 W (0.40 %)4,070.0 W (1.20 %) 4,840.0 W (1.50 %) 6,170.0 W (1.90 %)
2,660.0 W (0.80 %) 2,250.0 W (0.70 %)
1,410.0 W (0.40 %)
F 90% 50%25%50%I
100%

Documentation

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us